2016-05-09 08:21:29 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16040574 |
| ADD: 1025 7TH ST. |
| CONT: T. B. D. / TO BE DETEMINED |
| TEL: 561-310-7829 |
| E-MAIL: ????????? |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. MAY 09/ 2016 |
| ACTION: DENIED |
| |
| 1) THE COVERSHEET LIST THIS BUILDING CONSTRUCTION TYPE |
| AS A III-B TYPE CONSTRUCTION, SHEETS A1, A3 & A4 ALL |
| SHOW THIS STRUCTURE WITH WOOD FRAME EXTERIOR WALLS. |
| PLEASE REVIEW CONSTRUCTION TYPE FOR A III-B. PLANS DO |
| NOT CALL OUT FOR FIRE RETARDANT TREATED WOOD FOR THE |
| EXTERIOR WALL FRAMING MEMBERS OR SUB-SHEATHING. |
| |
| 2014 FBC-B 602.3. 602.3 TYPE III. TYPE III CONSTRUCTION |
| IS THAT TYPE OF CONSTRUCTION IN WHICH THE EXTERIOR |
| WALLS ARE OF NONCOMBUSTIBLE MATERIALS AND THE INTERIOR |
| BUILDING ELEMENTS ARE OF ANY MATERIAL PERMITTED BY THIS |
| CODE. FIRE-RETARDANT-TREATED WOOD FRAMING COMPLYING |
| WITH SECTION 2303.2 SHALL BE PERMITTED WITHIN EXTERIOR |
| WALL ASSEMBLIES OF A 2-HOUR RATING OR LESS. |
| |
| 2) A SURVEY IS PROVIDED FOR THE LOT THIS BUILDING IS TO |
| BE BUILT UPON, BUT THERE IS NO PROPOSED BUILDING ON THE |
| SURVEY SHOWING THE DIMENSIONS FROM THE PROPERTY LINES |
| NOR THE REQUIRED SET BACKS. 2014 FBC-B TABLE 602 & |
| TABLE 705.8. |
| |
| 3) THE PROPOSED VALUE OF THE PROJECT IS EXTREMELY LOW |
| AT $75,000.00 IN VALUE. USING THE ICC BUILDING |
| VALUATION CHARTS FROM AUGUST 2015 FOR THE SQUARE |
| FOOTAGE OF : |
| A3/ III-B 937 SQ. FT. X $137.12 = $ 128,481.44 |
| B / III-B 1,631 SQ. FT. X $152.55 = $ 248,809.05 |
| $ 377,290.00 TOTAL VALUE FOR THE BUILDING |
| ONLY!!!!!!!!!! |
| |
| W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT |
| FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, |
| MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS |
| REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID |
| AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE |
| ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. |
| |
| 108.3* BUILDING PERMIT VALUATION. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| 4A) SHEET A4/ LIFE SAFETY SHEET DOES NOT SHOW THE |
| CORRIDOR AS A FIRE RATED CORRIDOR. PLEASE REVIEW TABLE |
| 1018.1 OF THE 2014 FBC-B. FOR BOTH ASSEMBLY AND |
| BUSINESS OCCUPANCCIES OF NON-FIRE SPRINKLERED BUILDINGS |
| WITH AN OCCUPANT LOAD GREATER THAN 30 A ONE HOUR FIRE |
| RATED CORRIDOR IS REQUIRED WITH REQUIRED OPENING |
| PROTECTIVES FOR DOORS IN COMPLIANCE OF TABLE 716.5. 20 |
| MINUTE FIRE RATED DOORS, SEE FOOTNOTE B. |
| |
| 4B) PLEASE SHOW HOW THE 1 HOUR FIRE RATED CORRIDOR IS |
| TO BE BUILT INCLUDING THE FIRE RATING OF WALLS TO THE |
| ROOF SHEATHING ON BOTH SIDES OF THE COORIDOR OR IS |
| THERE GOING TO BE A FIRE RATED CEILING ASSEMBLY? THE |
| MECHANICAL SHEET M1 DOES NOT SHOW EITHER THE DUCTS |
| PENETRATING THE CORRIDOR CEILING WITH FIRE DAMPERS. |
| DEPENDING WHERE THE MAIN TRUNK LINE IS PLACED IF ABOVE |
| IN THE ATTIC OR BELOW A RATED CORRIDOR CEILING EITHER |
| CEILING DAMPERS WILL BE REQUIRED OR FIRE DAMPERS IN THE |
| CORRIDOR WALLS. SEE FBC-B 717.5.4.1 CORRIDORS. A LISTED |
| SMOKE DAMPER DESIGNED TO RESIST THE PASSAGE OF SMOKE |
| SHALL BE PROVIDED AT EACH POINT A DUCT OR AIR TRANSFER |
| OPENING PENETRATES A CORRIDOR ENCLOSURE REQUIRED TO |
| HAVE SMOKE AND DRAFT CONTROL DOORS IN ACCORDANCE WITH |
| SECTION 716.5.3. |
| |
| 5) DISCREPANCY IN PLANS. THE COVERSHEET SHEET INDEX |
| LIST SHEETS A1-A6 WHERE AS IN THE SET OF DRAWINGS THERE |
| ARE 3 SHEETS LABELED A4, NO A5 OR A6. PLEASE CORRECT |
| THE DISCREPANCY (TYPO) IN PLANS. 107.2.1.3 |
| |
| 6) FOUNDATIONSHEET (A5) VERSES SHEET A3 DETAIL 14 CUT |
| SECTION OF EXTERIOR WALL AND FOUNDATION. SHEET A5 THE |
| PERIMTETER FOUNDATION IS INDICATED AS 18 IN. WIDE X |
| 16IN. DEEP. PLEASE SEE SHEET A3 DETAIL # 14. THE FINISH |
| FLOOR IS SHOWN AT ELE. 0-0 FT. THE BOTTOM SILL PLATE IS |
| RECESSED, THE DIMINSION NOT GIVEN. THE STUCCO SIDING |
| AND SUB-SHEATHING STOP ABOVE THE BOTTOM HALF OF THE |
| BOTTOM SILL PLATE NOT PROVIDING PROTECTION AGAINST THE |
| WEATHER AND PROMOTING ROT. THE 2012 ICC-B CODE |
| COMMENTARY 2304.11.2.6 ON THIS SECTION INDICATES THE |
| STUCCO AND SHEATHING SHOULD EXTEND AT LEAST 1 INCH |
| BELOW THE TOP OF THE FOUNDATION. THEN THE 6 INCH |
| CLEARANCE BETWEEN THE STUCCO AND SUB-SHEATHING TO |
| EXPOSED GRADE SHOLD OCCUR. SECTION 1809.4 OF THE 2014 |
| FBC-B REQUIRES THE FOUNDATION TO BE A MINIMUM OF 12 |
| INCHES BELOW GRADE TO THE BOTTOM OF THE FOUNDATION. THE |
| VERTICAL DIMENSION OF THE FOUNDATION NEEDS TO BE |
| INCREASED TO MEET ALL OF THESE CODE REQUIREMENTS. |
| |
| 7) SHEET A3 DETAIL 14 ALSO INDICATES THE USE OF STUCCO |
| AND THE USE OF WIRE LATH. PLEASE SHOW COMPLIANCE WITH |
| 2014 FBC-B 2510.6 WATER-RESISTIVE BARRIERS. |
| WATER-RESISTIVE BARRIERS SHALL BE INSTALLED AS REQUIRED |
| IN SECTION 1404.2 AND, WHERE APPLIED OVER WOOD-BASED |
| SHEATHING, SHALL INCLUDE A WATER-RESISTIVE |
| VAPOR-PERMEABLE BARRIER WITH A PERFORMANCE AT LEAST |
| EQUIVALENT TO TWO LAYERS OF GRADE D PAPER. THE |
| INDIVIDUAL LAYERS SHALL BE INSTALLED INDEPENDENTLY SUCH |
| THAT EACH LAYER PROVIDES A SEPARATE CONTINUOUS PLANE |
| AND ANY FLASHING (INSTALLED IN ACCORDANCE WITH SECTION |
| 1405.4) INTENDED TO DRAIN TO THE WATER-RESISTIVE |
| BARRIER IS DIRECTED BETWEEN THE LAYERS. |
| |
| 8) DISCREPANCY IN PLANS. SHEET A2.2 THE ELEVATIONS |
| SHOWS A 2FT OVERHANG FOR THE ROOF TRUSSES WHEREAS SHEET |
| A3 DETAIL 14 SHOWS ONLY A 1FT. 4 IN. OVERHANG. SHEET |
| A-6 (SHOWN AS A-4) THE TRUSS LAYOUT SHEET DOES NOT SHOW |
| ANY DIMENSION AS FAR AS WHAT THE OVERHANG SHOULD BE? |
| 107.2.1.3. |
| |
| 9) SHEET A-6 (SHOWN AS A-4) THE TRUSS LAYOUT SHEET |
| SHOWS WHAT APPEARS TO BE A 2 FT. OVERHANG ON THE GABLE |
| END WALLS, THIS DETAIL MAY BE REQUIRED TO BE A DROPPED |
| GABLE END. PLEASE NOTE THIS TYPE OF LATTER TYPE |
| OVERHANG IS USSUALLY FOUND ON TRUSS OVERHANGS OF 12 |
| INCHES. THE WOOD WOOD TRUSSES SHALL BE DESIGNED IN |
| ACCORDANCE WITH SECTION 2303.4. |
| |
| 2303.4.2 TRUSS PLACEMENT DIAGRAM. THE TRUSS |
| MANUFACTURER SHALL PROVIDE A TRUSS PLACEMENT DIAGRAM |
| THAT IDENTIFIES THE PROPOSED LOCATION FOR EACH |
| INDIVIDUALLY DESIGNATED TRUSS AND REFERENCES THE |
| CORRESPONDING TRUSS DESIGN DRAWING. THE TRUSS PLACEMENT |
| DIAGRAM SHALL BE PROVIDED AS PART OF THE TRUSS |
| SUBMITTAL PACKAGE, AND WITH THE SHIPMENT OF TRUSSES |
| DELIVERED TO THE JOB SITE. TRUSS PLACEMENT DIAGRAMS |
| THAT SERVE ONLY AS A GUIDE FOR INSTALLATION AND DO NOT |
| DEVIATE FROM THE PERMIT SUBMITTAL DRAWINGS SHALL NOT BE |
| REQUIRED TO BEAR THE SEAL OR SIGNATURE OF THE TRUSS |
| DESIGNER. |
| |
| 2303.4.3 TRUSS SUBMITTAL PACKAGE. THE TRUSS SUBMITTAL |
| PACKAGE PROVIDED BY THE TRUSS MANUFACTURER SHALL |
| CONSIST OF EACH INDIVIDUAL TRUSS DESIGN DRAWING, THE |
| TRUSS PLACEMENT DIAGRAM, THE PERMANENT INDIVIDUAL TRUSS |
| MEMBER RESTRAINT/BRACING METHOD AND DETAILS AND ANY |
| OTHER STRUCTURAL DETAILS GERMANE TO THE TRUSSES; AND, |
| AS APPLICABLE, THE COVER/TRUSS INDEX SHEET. |
| |
| 10) PLEASE NOTE SHEET A2.1 AND A4 BOTH SHOW THIS |
| STRUCTURE HAVING A GABLE END ON BOTH ENDS OF THE |
| BUILDING. THERE ARE NO DETAILS ON SHEET A4 FOR THE |
| GABLE END WALL BRACING OF THE TOP CORD, END TRUSS WALL |
| TO THE BOTTOM CORD OF TRUSSES BEING TRANSFERRED INTO |
| THE WOOD FRAME BEARING WALL. FBC-B 2308.3.2.2. WHERE |
| ROOF TRUSSES ARE USED AND ARE INSTALLED PERPENDICULAR |
| TO AN EXTERIOR BRACED WALL LINE, LATERAL FORCES SHALL |
| BE TRANSFERRED FROM THE ROOF DIAPHRAGM TO THE BRACED |
| WALL OVER THE FULL LENGTH OF THE BRACED WALL LINE BY |
| BLOCKING OF THE ENDS OF THE TRUSSES OR BY OTHER |
| APPROVED METHODS PROVIDING EQUIVALENT LATERAL FORCE |
| TRANSFER. BLOCKING SHALL BE MINIMUM 2 INCHES (51 MM) |
| NOMINAL THICKNESS AND SHALL EXTEND TO WITHIN 2 INCHES |
| (51 MM) FROM THE ROOF SHEATHING ABOVE AND SHALL BE |
| FASTENED TO THE BRACED WALL LINE TOP PLATE AS SPECIFIED |
| IN TABLE 2304.9.1, ITEM 11. NOTCHING OR DRILLING OF |
| HOLES IN BLOCKING IN ACCORDANCE WITH THE REQUIREMENTS |
| OF SECTION 2308.8.2 OR SECTION 2308.10.4.2 SHALL BE |
| PERMITTED. |
| |
| 11) DISCREPANCY IN PLANS SHEET A2.1 SHOWS WALL AND ROOF |
| ZONES PRESSURES FOR ZONES 1-5. THE CHART DOES NOT |
| INDICATE IF THERE PRESSURES ARE IN VULT OR VASD. PLEASE |
| ALSO REVIEW PRESSURES FOUND ON A-5 DETAIL 3 THE DETAIL |
| SHOWS A HIP ROOF NOT A GABLE ROOF. THE PRESSURES FOR |
| ZONES 2 AND 3 ARE THE SAME, THIS IS NOT TRUE FOR A |
| GABLE ROOF!!! 107.2.1.3 ADDITIONAL INFORMATION IS |
| REQUIRED. |
| |
| 12) SHEET A2 NOR A3 DETAIL 14 SHOW COMPLIANCE WITH: |
| PLEASE PROVIDE ATTIC VENTILATIONS CALCULATIONS IN |
| COMPLIANCE WITH 2308.10.11 ATTIC VENTILATION. FOR ATTIC |
| VENTILATION, SEE SECTION 1203.2. |
| |
| 13) SHEET A2.1 THE SOUTH ELEVATION SHOWS ARCHITECTURAL |
| DETAILS OF COLUMNS AND PEDIMENT PLEASE SHOW A CUR |
| THROUGH SECTION OF THIS AREA FOR A BETTER UNDERSTANDING |
| OF THE DEPTH OF THESE ELEMENTS. 107.2.1.3 ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 14) ROOFING: NOTICE: EFFECTIVE APRIL 1/2016 THE |
| REFERENCED MIAMI-DADE COUNTY ELECTROGALVANIZED |
| FASTENERS LISTINGS ARE SUSPENDED: |
| 11--1019.02 & 11-1019.03 BLUELINX CORP. |
| 12-0423.06 CONTINENAL MATERIALS, INC. |
| 15-1123.04 PRIME SOURCE BUILDING PRODUCTS, INC. |
| 13-0530.01 SPECIALTY FASTENING SYSTEM |
| 12-0423.03 & 12-0423.04 SUMMIT CONGLOMERATE, LLC |
| 12-1205.11, 12-1205.13 & 13-05 & 13-0514.05 WEATHERPRO, |
| LLC |
| |
| 15) PLEASE SHOW COMPLIANCE WITH THE 2014 ENERGY CODE: |
| C401.2 APPLICATION. |
| COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE |
| FOLLOWING: |
| |
| 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1. |
| |
| 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND |
| C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY |
| WITH EITHER SECTION C406.2, C406.3 OR C406.4. |
| |
| 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2, |
| C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE |
| BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 |
| PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING. |
| |
| 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |