Plan Review Stops For Permit 16040559 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2016-05-04 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-05-04 |
Time |
12:14 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-05-04 |
Time |
12:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2016-04-29 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-04-29 |
Time |
15:00 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-04-29 |
Time |
14:12 |
Sent To |
|
|
Notes |
2016-04-29 15:08:20 | 1ST REVIEW: FBC 2014 5TH ED | | CHRISTOPHER S. THROOP, C.B.O. | | BLDG. PLANS EXAMINER ? PX3169 | | (561) 805-6718 | | [email protected] | | | | 1. PROVIDE TOP PLATE CONNECTION DETAIL FOR NEW INTERIOR | | WALLS. | | 2. PROVIDE DOOR SCHEDULE FOR NEW DOORS. | | 3. PROVIDE REPAIR DETAIL FOR SAW CUT AREAS OF EXISTING | | SLAB. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2016-05-04 |
|
|
Cont ID |
|
Sent By |
vperez |
Date |
2016-05-04 |
Time |
07:55 |
Rev Time |
0.00 |
Received By |
vperez |
Date |
2016-05-04 |
Time |
07:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2016-04-15 |
|
|
Cont ID |
|
Sent By |
vperez |
Date |
2016-04-15 |
Time |
13:20 |
Rev Time |
0.00 |
Received By |
vperez |
Date |
2016-04-15 |
Time |
13:20 |
Sent To |
|
|
Notes |
2016-04-15 13:20:31 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 NEC | | COMMENTS: | | | | 1. PLEASE LABEL RECEPTACLES IN THE UTILITY, RESTROOMS | | AND DRINKING FOUNTAIN TO BE GFCI PROTECTED. NEC | | 210.8B(2) AND (5) AND NEC 422.52 | | 2. SIGNATURE IS REQUIRED ON DRAWINGS BY AOR. | | 3. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | QUESTIONS REGARDING THIS PROJECT. | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2016-05-04 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2016-05-04 |
Time |
14:36 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2016-05-03 |
Time |
14:36 |
Sent To |
|
|
Notes |
2016-05-04 14:36:54 | REVIEW BY WESELY JOLIN. PLANS STAMPED BY WJ. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2016-04-13 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2016-04-13 |
Time |
15:50 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2016-04-13 |
Time |
15:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2016-05-04 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2016-05-04 |
Time |
14:37 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2016-05-03 |
Time |
10:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-04-29 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-04-29 |
Time |
15:08 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-04-11 |
Time |
14:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2016-05-03 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2016-05-03 |
Time |
16:44 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2016-05-03 |
Time |
16:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2016-04-13 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2016-04-13 |
Time |
08:33 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2016-04-13 |
Time |
08:21 |
Sent To |
|
|
Notes |
2016-04-13 09:06:14 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #16040559 | | 4/13/16 | | | | 1) PROVIDE VENTILATION FOR THE UTILITY ROOM PER TABLE | | 403.3 FBC-14 MECHANICAL. | | 2) SHEET 2.1: CORRECT THE NOTE IN THE LEGEND INDICATING | | A KITCHEN EXHAUST FAN: THE FAN SYMBOL IN THE DRAWING IS | | IN THE TOILET ROOM. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2016-05-03 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2016-05-03 |
Time |
14:17 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2016-05-03 |
Time |
14:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2016-04-21 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2016-04-21 |
Time |
17:02 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2016-04-21 |
Time |
17:48 |
Sent To |
|
|
Notes |
2016-04-21 17:42:43 | PLUMBING COMMENTS: | | | | 1.THE FLOOR SINK AND SERVICE SINK ARE NOT VENTED, THE | | VENT ON 6IN BUILDING DOES NOT COMPLY, THE BRANCH DRAIN | | FOR FLOOR SINK AND SERVICE SINK HAS TO BE VENTED | | INDIVIDUALLY VENTED | | SHALL COMPLY WITH FBC PL SEC. 901.2.1 | | | | 2. SIZE SERVICE SINK DRAIN AND NEW VENT PIPING. PER WPB | | AMEND. SEC. 107.2.1 | | | | 3.PROVIDE WATER RISER DIAGRAM. PER WPB | | AMEND.107.3.5.13(13) | | | | 4. HOT WATER IS REQUIRED FOR ALL FIXTURES FBC PL 607.1 | | | | 5. INCLUDE LETTER FROM ARCHITECT STATING THAT ALL FOOD | | ITEM ARE PRE PACKED AND NOTHING IS COOKED OR PRE PAIR. | | IF NOT A GREASE INTERCEPTOR WILL BE REQUIRED | | PER WPB AMEND. SEC. 107.2.1 | | | | 6. PLACE MAILING ADDRESS IN TITLE BLOCK ON EACH SHEET. | | PER WPB AMEND. SEC. 107.2.1 | | | | 7. PLANS NEED TO BE SIGNED BY ARCHITECT DIGITAL DOES | | NOT COMPLY | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | PREVIOUSLY REVIEWED SHEETS | | DO TO PLANS BEING INCOMPLETE OR UNCLEAR, A | | COMPREHENSIVE PLAN REVIEW CANNOT BE DONE AT THIS TIME, | | THERE MAYBE ADDITIONAL COMMENTS ON RESUBMITTAL OF | | PLANS. | | | | | | 1ST REVIEW: FBC 2014 | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2016-05-04 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2016-05-04 |
Time |
13:51 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2016-05-04 |
Time |
13:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2016-04-15 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2016-04-15 |
Time |
18:01 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2016-04-15 |
Time |
18:01 |
Sent To |
|
|
Notes |
|
|