Plan Review Details - Permit 16040559
Plan Review Stops For Permit 16040559
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-05-04 Cont ID  
Sent By cthroop Date 2016-05-04 Time 12:14 Rev Time 0.00
Received By cthroop Date 2016-05-04 Time 12:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-04-29 Cont ID  
Sent By cthroop Date 2016-04-29 Time 15:00 Rev Time 0.00
Received By cthroop Date 2016-04-29 Time 14:12 Sent To  
Notes
2016-04-29 15:08:201ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 1. PROVIDE TOP PLATE CONNECTION DETAIL FOR NEW INTERIOR
 WALLS.
 2. PROVIDE DOOR SCHEDULE FOR NEW DOORS.
 3. PROVIDE REPAIR DETAIL FOR SAW CUT AREAS OF EXISTING
 SLAB.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-05-04 Cont ID  
Sent By vperez Date 2016-05-04 Time 07:55 Rev Time 0.00
Received By vperez Date 2016-05-04 Time 07:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-04-15 Cont ID  
Sent By vperez Date 2016-04-15 Time 13:20 Rev Time 0.00
Received By vperez Date 2016-04-15 Time 13:20 Sent To  
Notes
2016-04-15 13:20:31INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE LABEL RECEPTACLES IN THE UTILITY, RESTROOMS
 AND DRINKING FOUNTAIN TO BE GFCI PROTECTED. NEC
 210.8B(2) AND (5) AND NEC 422.52
 2. SIGNATURE IS REQUIRED ON DRAWINGS BY AOR.
 3. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-05-04 Cont ID  
Sent By skennedy Date 2016-05-04 Time 14:36 Rev Time 0.00
Received By skennedy Date 2016-05-03 Time 14:36 Sent To  
Notes
2016-05-04 14:36:54REVIEW BY WESELY JOLIN. PLANS STAMPED BY WJ.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-04-13 Cont ID  
Sent By wjolin Date 2016-04-13 Time 15:50 Rev Time 0.00
Received By wjolin Date 2016-04-13 Time 15:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-04 Cont ID  
Sent By skennedy Date 2016-05-04 Time 14:37 Rev Time 0.00
Received By skennedy Date 2016-05-03 Time 10:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-29 Cont ID  
Sent By cthroop Date 2016-04-29 Time 15:08 Rev Time 0.00
Received By cthroop Date 2016-04-11 Time 14:07 Sent To  
Notes
2016-04-11 14:09:54B21

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-05-03 Cont ID  
Sent By ccole Date 2016-05-03 Time 16:44 Rev Time 0.00
Received By ccole Date 2016-05-03 Time 16:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-04-13 Cont ID  
Sent By ccole Date 2016-04-13 Time 08:33 Rev Time 0.00
Received By ccole Date 2016-04-13 Time 08:21 Sent To  
Notes
2016-04-13 09:06:141ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16040559
 4/13/16
  
 1) PROVIDE VENTILATION FOR THE UTILITY ROOM PER TABLE
 403.3 FBC-14 MECHANICAL.
 2) SHEET 2.1: CORRECT THE NOTE IN THE LEGEND INDICATING
 A KITCHEN EXHAUST FAN: THE FAN SYMBOL IN THE DRAWING IS
 IN THE TOILET ROOM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-05-03 Cont ID  
Sent By gjohnson Date 2016-05-03 Time 14:17 Rev Time 0.00
Received By gjohnson Date 2016-05-03 Time 14:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-04-21 Cont ID  
Sent By gjohnson Date 2016-04-21 Time 17:02 Rev Time 0.00
Received By gjohnson Date 2016-04-21 Time 17:48 Sent To  
Notes
2016-04-21 17:42:43PLUMBING COMMENTS:
  
 1.THE FLOOR SINK AND SERVICE SINK ARE NOT VENTED, THE
 VENT ON 6IN BUILDING DOES NOT COMPLY, THE BRANCH DRAIN
 FOR FLOOR SINK AND SERVICE SINK HAS TO BE VENTED
 INDIVIDUALLY VENTED
 SHALL COMPLY WITH FBC PL SEC. 901.2.1
  
 2. SIZE SERVICE SINK DRAIN AND NEW VENT PIPING. PER WPB
 AMEND. SEC. 107.2.1
  
 3.PROVIDE WATER RISER DIAGRAM. PER WPB
 AMEND.107.3.5.13(13)
  
 4. HOT WATER IS REQUIRED FOR ALL FIXTURES FBC PL 607.1
  
 5. INCLUDE LETTER FROM ARCHITECT STATING THAT ALL FOOD
 ITEM ARE PRE PACKED AND NOTHING IS COOKED OR PRE PAIR.
 IF NOT A GREASE INTERCEPTOR WILL BE REQUIRED
 PER WPB AMEND. SEC. 107.2.1
  
 6. PLACE MAILING ADDRESS IN TITLE BLOCK ON EACH SHEET.
 PER WPB AMEND. SEC. 107.2.1
  
 7. PLANS NEED TO BE SIGNED BY ARCHITECT DIGITAL DOES
 NOT COMPLY
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS
 DO TO PLANS BEING INCOMPLETE OR UNCLEAR, A
 COMPREHENSIVE PLAN REVIEW CANNOT BE DONE AT THIS TIME,
 THERE MAYBE ADDITIONAL COMMENTS ON RESUBMITTAL OF
 PLANS.
  
  
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2016-05-04 Cont ID  
Sent By eschneid Date 2016-05-04 Time 13:51 Rev Time 0.25
Received By eschneid Date 2016-05-04 Time 13:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-04-15 Cont ID  
Sent By eschneid Date 2016-04-15 Time 18:01 Rev Time 0.25
Received By eschneid Date 2016-04-15 Time 18:01 Sent To  
Notes
***NONE***