2016-08-08 13:06:38 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| NUMEROUS COMMENTS WERE NOT PROVIDED WITH ANY NARRATIVE, |
| NOTE OR REVISION CLOUD. PER NPFA 1 |
| |
| 1.14 PLAN REVIEW. |
| |
| 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION |
| DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND |
| SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE |
| CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD |
| CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS. |
| |
| |
| PREVIOUS COMMENTS: |
| |
| 1) SHEET FP 110 A - COMPLIED WITH LETTER. |
| |
| 2) SHEET FP 110 A - COMPLIED WITH LETTER. |
| |
| 3) SHEET FP 110 C - REMOTE AREA # 1 INDICATES |
| 0.100GPM/FT2 AND THE CLACULATIONS SHEETS INDICATES |
| 0.15GPM/FT2. PLEASE CORRECT AND CLARIFY WHICH IS |
| CORRECT. |
| |
| REMOTE AREA # 1 INDICATION HAS BEEN REMOVED FROM THAT |
| SHEET WITH NO REVISION CLOUD OR OTHER INDICATION OF THE |
| REMOTE AREA. |
| |
| 4) SHEET FP 110 C - REMOTE AREA # 1 LAYOUT IS DIFFICULT |
| TO DETERMINE AS THERE APPEARS TO BE TWO SETS OF BRANCH |
| LINES IN THE SAME AREA. PLEASE CLARIFY OR SHOW |
| ELEVATIONS. |
| |
| REMOTE AREA # 1 INDICATION HAS BEEN REMOVED FROM THAT |
| SHEET WITH NO REVISION CLOUD OR OTHER INDICATION OF |
| CLARITY. |
| |
| 5) SHEET FP 110 C - PLEASE PROVIDE AND INDICATE EXACT |
| DIMENSIONS AND SQUARE FOOTAGE OF ACTUAL REMOTE AREA # |
| 1. NO DIMENSIONS ARE INDICATED AND THE AREA IS NOT |
| CLEARLY MARKED. |
| |
| REMOTE AREA # 1 INDICATION HAS BEEN REMOVED FROM THAT |
| SHEET WITH NO REVISION CLOUD OR OTHER INDICATION OF |
| CLARITY. |
| |
| 6) SHEET FP 120 A - ALL THE ROOMS ARE NOT LABELED. ALL |
| ROOMS SHALL BE LABELED OR INDICATED. THERE ARE TWO |
| ROOMS WITH 1 SPRINKLER HEAD ONLY THAT APPEAR TO BE FOR |
| ORDINARY HAZARD GROUP 1. WERE THE CALCULATION DEMANDS |
| OF THESE HEADS CONSIDERED. PLEASE EXPLAIN OR PROVIDE A |
| BRIEF NARRATIVE. |
| |
| NO REVISION CLOUD OR OTHER INDICATIONS OF CLARITY |
| PROVIDED. |
| |
| 7) SHEET FP 120 A - FLEXIBLE PIPING IS INDICATED. |
| FLEXIBLE PIPING IS NOT INDICATED ON THE CALCULATIONS |
| FOR REMOTE AREA # 2. |
| |
| NO REVISION CLOUD OR OTHER INDICATIONS OF CLARITY |
| PROVIDED. |
| |
| 8) SHEET FP 120 A - FLEXIBLE PIPING IS INDICATED. SHEET |
| 501 DOES NOT INDICATE SPECIFICATIONS FOR FLEXIBLE PIPE |
| AND NO SPEC SHEETS ARE PROVIDED. PLEASE INDICATE ON |
| SHEET 501 AND PROVIDE SPEC SHEETS. |
| |
| NO REVISION CLOUD OR OTHER INDICATIONS OF CLARITY |
| PROVIDED. |
| |
| 9) SHEET FP 120 B - COMPLIED WITH NEW SHEET, NO |
| REVISION CLOUD PROVIDED. |
| |
| 10) SHEET FP 160 A - COMPLIED WITH LETTER. |
| |
| 11) SHEET FP 160 C - COMPLIED WITH NEW SHEET, NO |
| REVISION CLOUD PROVIDED. |
| |
| 12 ) SHEET FP 501 - COMPLIED WITH NEW PRESSURE TEST, NO |
| REVISION CLOUD PROVIDED. |
| |
| 13) SHEET FP 501 - NOTE # 1 - THERE IS NO TRANSFER |
| SWITCH INDICATED ON THE CONTROLLER. EMERGENCY POWER IS |
| REQUIRED AND SHALL BE PROVIDED. PROVIDE A TRANSFER |
| SWITCH AND APPLICBALE SPEC SHEETS. |
| |
| APPEARS TO COMPLY, NO REVISON CLOUD PROVIDED. |
| |
| 14) SHEET FP 501 - NOTE # 15 - A 175PSI REGUALTING |
| VALVE IS INDICATED. NFPA 20 DOES NOT PERMIT FOR A |
| REGULATING VALVE/DEVICE WITHIN THE FIRE PUMP SUCTION OR |
| DISCHARGE PIPING. THE REGULATING VALVE/DEVICES ARE |
| PERMITED BY NFPA 14 IN THE STANDPIPE SYSTEM. PLEASE |
| CORRECT AND PROVIDE APPLICABLE SPECS FOR EACH FLOOR |
| LOCATION |
| |
| NO REVISION CLOUD OR OTHER INDICATIONS OF CLARITY |
| PROVIDED. |
| |
| 15) SHEET FP 501 - ROOF MANIFOLD DRAWINGS OR SPEC ARE |
| NOT PROVIDED OR INDICATED. PLEASE PROVIDE. |
| |
| NO REVISION CLOUD OR OTHER INDICATIONS OF CLARITY |
| PROVIDED. |
| |
| |
| PLEASE PROVIDE REVSION CLOUDS OR OTHER INDICATIONS ON |
| EACH SHEET OF THE CHANGES MADE. |
| |
| |
| ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL |
| OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |
| |
| |
| |
| |
| |