Plan Review Details - Permit 16040539
Plan Review Stops For Permit 16040539
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-08-19 Cont ID  
Sent By hmoser Date 2016-08-30 Time 14:45 Rev Time 0.00
Received By pleduc Date 2016-08-19 Time 08:32 Sent To M
Notes
2016-08-19 12:46:17THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET FP 501 - THERE IS NO INDICATIONS THAT ELBOWS
 AND T'S ARE GREATER THAN 10 THE SUCTION PIPE DIAMETER.
  
  
 4.14.6.3 ELBOWS AND TEES.
 4.14.6.3.1 UNLESS THE REQUIREMENTS OF 4.14.6.3.2 ARE
 MET, ELBOWS AND TEES WITH A CENTERLINE PLANE PARALLEL
 TO A HORIZONTAL SPLIT-CASE PUMP SHAFT SHALL NOT BE
 PERMITTED. (SEE FIGURE A.4.14.6.)
 4.14.6.3.2 THE REQUIREMENTS OF 4.14.6.3.1 SHALL NOT
 APPLY TO ELBOWS AND TEES WITH A CENTERLINE PLANE
 PARALLEL TO A HORIZONTAL SPLIT-CASE PUMP SHAFT WHERE
 THE DISTANCE BETWEEN THE FLANGES OF THE PUMP SUCTION
 INTAKE AND THE ELBOW AND TEE IS GREATER THAN 10 TIMES
 THE SUCTION PIPE DIAMETER.
 4.14.6.3.3 ELBOWS WITH A CENTERLINE PLANE PERPENDICULAR
 TO THE HORIZONTAL SPLIT-CASE PUMP SHAFT SHALL BE
 PERMITTED AT ANY LOCATION IN THE PUMP SUCTION INTAKE.
  
  
 PLEASE ENSURE COMPLIANCE ON INSTALLATION. FIRE
 INSPECTOR WILL VERIFY ON INSPECTION.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2016-08-08 Cont ID  
Sent By pleduc Date 2016-08-08 Time   Rev Time 0.00
Received By pleduc Date 2016-08-08 Time 13:03 Sent To M
Notes
2016-08-08 13:06:38THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 NUMEROUS COMMENTS WERE NOT PROVIDED WITH ANY NARRATIVE,
 NOTE OR REVISION CLOUD. PER NPFA 1
  
 1.14 PLAN REVIEW.
  
 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION
 DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND
 SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE
 CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD
 CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS.
  
  
 PREVIOUS COMMENTS:
  
 1) SHEET FP 110 A - COMPLIED WITH LETTER.
  
 2) SHEET FP 110 A - COMPLIED WITH LETTER.
  
 3) SHEET FP 110 C - REMOTE AREA # 1 INDICATES
 0.100GPM/FT2 AND THE CLACULATIONS SHEETS INDICATES
 0.15GPM/FT2. PLEASE CORRECT AND CLARIFY WHICH IS
 CORRECT.
  
 REMOTE AREA # 1 INDICATION HAS BEEN REMOVED FROM THAT
 SHEET WITH NO REVISION CLOUD OR OTHER INDICATION OF THE
 REMOTE AREA.
  
 4) SHEET FP 110 C - REMOTE AREA # 1 LAYOUT IS DIFFICULT
 TO DETERMINE AS THERE APPEARS TO BE TWO SETS OF BRANCH
 LINES IN THE SAME AREA. PLEASE CLARIFY OR SHOW
 ELEVATIONS.
  
 REMOTE AREA # 1 INDICATION HAS BEEN REMOVED FROM THAT
 SHEET WITH NO REVISION CLOUD OR OTHER INDICATION OF
 CLARITY.
  
 5) SHEET FP 110 C - PLEASE PROVIDE AND INDICATE EXACT
 DIMENSIONS AND SQUARE FOOTAGE OF ACTUAL REMOTE AREA #
 1. NO DIMENSIONS ARE INDICATED AND THE AREA IS NOT
 CLEARLY MARKED.
  
 REMOTE AREA # 1 INDICATION HAS BEEN REMOVED FROM THAT
 SHEET WITH NO REVISION CLOUD OR OTHER INDICATION OF
 CLARITY.
  
 6) SHEET FP 120 A - ALL THE ROOMS ARE NOT LABELED. ALL
 ROOMS SHALL BE LABELED OR INDICATED. THERE ARE TWO
 ROOMS WITH 1 SPRINKLER HEAD ONLY THAT APPEAR TO BE FOR
 ORDINARY HAZARD GROUP 1. WERE THE CALCULATION DEMANDS
 OF THESE HEADS CONSIDERED. PLEASE EXPLAIN OR PROVIDE A
 BRIEF NARRATIVE.
  
 NO REVISION CLOUD OR OTHER INDICATIONS OF CLARITY
 PROVIDED.
  
 7) SHEET FP 120 A - FLEXIBLE PIPING IS INDICATED.
 FLEXIBLE PIPING IS NOT INDICATED ON THE CALCULATIONS
 FOR REMOTE AREA # 2.
  
 NO REVISION CLOUD OR OTHER INDICATIONS OF CLARITY
 PROVIDED.
  
 8) SHEET FP 120 A - FLEXIBLE PIPING IS INDICATED. SHEET
 501 DOES NOT INDICATE SPECIFICATIONS FOR FLEXIBLE PIPE
 AND NO SPEC SHEETS ARE PROVIDED. PLEASE INDICATE ON
 SHEET 501 AND PROVIDE SPEC SHEETS.
  
 NO REVISION CLOUD OR OTHER INDICATIONS OF CLARITY
 PROVIDED.
  
 9) SHEET FP 120 B - COMPLIED WITH NEW SHEET, NO
 REVISION CLOUD PROVIDED.
  
 10) SHEET FP 160 A - COMPLIED WITH LETTER.
  
 11) SHEET FP 160 C - COMPLIED WITH NEW SHEET, NO
 REVISION CLOUD PROVIDED.
  
 12 ) SHEET FP 501 - COMPLIED WITH NEW PRESSURE TEST, NO
 REVISION CLOUD PROVIDED.
  
 13) SHEET FP 501 - NOTE # 1 - THERE IS NO TRANSFER
 SWITCH INDICATED ON THE CONTROLLER. EMERGENCY POWER IS
 REQUIRED AND SHALL BE PROVIDED. PROVIDE A TRANSFER
 SWITCH AND APPLICBALE SPEC SHEETS.
  
 APPEARS TO COMPLY, NO REVISON CLOUD PROVIDED.
  
 14) SHEET FP 501 - NOTE # 15 - A 175PSI REGUALTING
 VALVE IS INDICATED. NFPA 20 DOES NOT PERMIT FOR A
 REGULATING VALVE/DEVICE WITHIN THE FIRE PUMP SUCTION OR
 DISCHARGE PIPING. THE REGULATING VALVE/DEVICES ARE
 PERMITED BY NFPA 14 IN THE STANDPIPE SYSTEM. PLEASE
 CORRECT AND PROVIDE APPLICABLE SPECS FOR EACH FLOOR
 LOCATION
  
 NO REVISION CLOUD OR OTHER INDICATIONS OF CLARITY
 PROVIDED.
  
 15) SHEET FP 501 - ROOF MANIFOLD DRAWINGS OR SPEC ARE
 NOT PROVIDED OR INDICATED. PLEASE PROVIDE.
  
 NO REVISION CLOUD OR OTHER INDICATIONS OF CLARITY
 PROVIDED.
  
  
 PLEASE PROVIDE REVSION CLOUDS OR OTHER INDICATIONS ON
 EACH SHEET OF THE CHANGES MADE.
  
  
 ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL
 OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-04-19 Cont ID  
Sent By pleduc Date 2016-04-19 Time   Rev Time 0.00
Received By pleduc Date 2016-04-14 Time 13:32 Sent To M
Notes
2016-04-19 13:16:04THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET FP 110 A - THE SUBMITTED PLANS INDICATED AN
 ENGINEER'S STAMP THAT DOES NOT MATCH THE ENGINEER OF
 RECORD WHICH IS INCONSISTENT WITH FLORIDA
 ADMINISTRATIVE CODE SECTION 61G15. THERE CAN BE ONLY
 ONE ENGINEER OF RECORD.
  
 2) SHEET FP 110 A - THE DESIGN SHOWS SEVERAL CHANGES
 FROM THE ORIGNAL ENGINNER OF RECORD SUBMITTAL. THE
 ENGINEER OF RECORD SHALL APPROVE BY STAMP OR LETTER THE
 SHOP DRAWINGS IN COMPLIANCE WITH FLORIDA ADMINISTRATIVE
 CODE SECTION 61G15.
  
 3) SHEET FP 110 C - REMOTE AREA # 1 INDICATES
 0.100GPM/FT2 AND THE CLACULATIONS SHEETS INDICATES
 0.15GPM/FT2. PLEASE CORRECT AND CLARIFY WHICH IS
 CORRECT.
  
 4) SHEET FP 110 C - REMOTE AREA # 1 LAYOUT IS DIFFICULT
 TO DETERMINE AS THERE APPEARS TO BE TWO SETS OF BRANCH
 LINES IN THE SAME AREA. PLEASE CLARIFY OR SHOW
 ELEVATIONS.
  
 5) SHEET FP 110 C - PLEASE PROVIDE AND INDICATE EXACT
 DIMENSIONS AND SQUARE FOOTAGE OF ACTUAL REMOTE AREA #
 1. NO DIMENSIONS ARE INDICATED AND THE AREA IS NOT
 CLEARLY MARKED.
  
 6) SHEET FP 120 A - ALL THE ROOMS ARE NOT LABELED. ALL
 ROOMS SHALL BE LABELED OR INDICATED. THERE ARE TWO
 ROOMS WITH 1 SPRINKLER HEAD ONLY THAT APPEAR TO BE FOR
 ORDINARY HAZARD GROUP 1. WERE THE CALCULATION DEMANDS
 OF THESE HEADS CONSIDERED. PLEASE EXPLAIN OR PROVIDE A
 BRIEF NARRATIVE.
  
 7) SHEET FP 120 A - FLEXIBLE PIPING IS INDICATED.
 FLEXIBLE PIPING IS NOT INDICATED ON THE CALCULATIONS
 FOR REMOTE AREA # 2.
  
 8) SHEET FP 120 A - FLEXIBLE PIPING IS INDICATED. SHEET
 501 DOES NOT INDICATE SPECIFICATIONS FOR FLEXIBLE PIPE
 AND NO SPEC SHEETS ARE PROVIDED. PLEASE INDICATE ON
 SHEET 501 AND PROVIDE SPEC SHEETS.
  
 9) SHEET FP 120 B - THERE IS NO SHEET FP 120 B; A
 DUPLICATE SHEET FP 110 B IS IN ITS PLACE. PROVIDE
 PROPER SHEET.
  
 10) SHEET FP 160 A - A NOTE INDICATES REMOVED CANOPY
 FIRE PROTECTION. PLEASE PROVIDE EXPLANATION OR
 JUSTIFICATION FOR THIS NOTE WITH THE APPROVAL FROM THE
 ENGINEER OF RECORD.
  
 11) SHEET FP 160 C - THERE ARE TWO SHEETS INDICATED AS
 FP 160 C; SHEET FP 160 D IS MISSING. PLEASE PROVIDE
 CORRECT SHEET.
  
 12 ) SHEET FP 501 - A NOTE INDICATES A WATER FLOW TEST
 DATE OF 2014. PER NFPA 13, CHAPTER 22, 22.2 WATER
 SUPPLY INFORMATION, 22.2.1.1* WHERE A WATER FLOW TEST
 IS USED FOR THE PURPOSES OF SYSTEM DESIGN, THE TEST
 SHALL BE CONDUCTED NO MORE THAN 12 MONTHS PRIOR TO
 WORKING PLAN SUBMITTAL. PLEASE PROVIDE UPDATE
 INFORMATION.
  
 13) SHEET FP 501 - NOTE # 1 - THERE IS NO TRANSFER
 SWITCH INDICATED ON THE CONTROLLER. EMERGENCY POWER IS
 REQUIRED AND SHALL BE PROVIDED. PROVIDE A TRANSFER
 SWITCH AND APPLICBALE SPEC SHEETS.
  
 14) SHEET FP 501 - NOTE # 15 - A 175PSI REGUALTING
 VALVE IS INDICATED. NFPA 20 DOES NOT PERMIT FOR A
 REGULATING VALVE/DEVICE WITHIN THE FIRE PUMP SUCTION OR
 DISCHARGE PIPING. THE REGULATING VALVE/DEVICES ARE
 PERMITED BY NFPA 14 IN THE STANDPIPE SYSTEM. PLEASE
 CORRECT AND PROVIDE APPLICABLE SPECS FOR EACH FLOOR
 LOCATION
  
 15) SHEET FP 501 - ROOF MANIFOLD DRAWINGS OR SPEC ARE
 NOT PROVIDED OR INDICATED. PLEASE PROVIDE.
  
 16) ADDITIONAL COMMENTS MAY BE PROVIDED BASED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-08-30 Cont ID  
Sent By hmoser Date 2016-08-30 Time 14:45 Rev Time 0.00
Received By hmoser Date 2016-08-17 Time 09:00 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-16 Cont ID  
Sent By hmoser Date 2016-08-16 Time 09:36 Rev Time 0.00
Received By hmoser Date 2016-08-04 Time 12:52 Sent To  
Notes
2016-08-05 12:52:52RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-20 Cont ID  
Sent By hmoser Date 2016-04-20 Time 09:42 Rev Time 0.00
Received By hmoser Date 2016-04-11 Time 13:12 Sent To  
Notes
2016-04-11 13:13:25FIRE SPRINKLER BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-08-30 Cont ID  
Sent By hmoser Date 2016-08-30 Time 14:45 Rev Time 0.00
Received By hmoser Date 2016-08-30 Time 13:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-08-16 Cont ID  
Sent By hmoser Date 2016-08-16 Time 09:34 Rev Time 0.00
Received By hmoser Date 2016-08-16 Time 09:34 Sent To  
Notes
2016-08-16 09:35:56REFER TO FIRE COMMENTS
 PLAN REVIEW BY HM.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-04-20 Cont ID  
Sent By hmoser Date 2016-04-20 Time 09:38 Rev Time 0.00
Received By hmoser Date 2016-04-20 Time 09:38 Sent To  
Notes
2016-04-20 09:41:25PLAN DENIED
 REFER TO FIRE COMMENTS