Plan Review Details - Permit 16040524
Plan Review Stops For Permit 16040524
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jwitmer Date 2017-02-28 Time 16:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-05-06 Cont ID  
Sent By jwitmer Date 2016-05-06 Time 14:28 Rev Time 0.00
Received By jwitmer Date 2016-05-06 Time 14:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-05-06 Cont ID  
Sent By mvaldes Date 2016-04-20 Time 15:12 Rev Time 0.00
Received By jwitmer Date 2016-04-20 Time 14:20 Sent To  
Notes
2016-04-20 15:14:17JOB PERMIT NUMBER: 16040524
 JOB ADDRESS: 701 S ROSEMARY AVE
 WEST PALM BEACH FLORIDA
 DATE: APRIL 20 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - ALL ELECTRICAL BOXES IN DEMISING WALL SHALL COMPLY
 WITH NEC 300.21 & FBC-B SECTION 714. ANY FIRE RATED
 STRUCTURE OR SURFACE THAT IS COMPROMISED SHALL BE
 RETURNED TO ITS ORIGINAL FIRE-RATING WITH APPROVED FIRE
 SEALING MATERIALS.
 - NEC 300.3 C ON THE SLAB ?? CONDUIT MAKE A NOTE THAT
 DIFFERENT RACEWAYS WILL BE USED FOR LOW VOLTAGE AND
 POWER CONDUCTORS UNLESS RATED WITH THE SAME INSULATION.
 - NEC 110.26A & 110.24 ARC-FLASH HAZARD WARNING LABEL
 AND AVAILABLE FAULT CURRENT MARKING IS MISSING FROM
 ELECTRICAL GENERAL NOTES.
 - FOLLOW UP FIRE COMMENTS IN ADDING EXIT SIGNS AND
 EMERGENCY LIGHTING FBC- 1006, 1011
 - NEC 700.12 (F) (4) - EMERGENCY LIGHTING SHALL BE FED
 BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR MORE
 LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY BE ON
 OWN CIRCUIT.
 - NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, PANELBOARDS.
 - PROVIDE ON PANEL SCHEDULE THE AIC RATING OF EQUIPMENT
 AND AMPERE RATING OF THE BUS BAR. WPBA 107, NEC 110.9 ,
 110.10
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-02-27 Cont ID  
Sent By pleduc Date 2017-02-27 Time   Rev Time 0.00
Received By pleduc Date 2017-02-24 Time 15:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-04-13 Cont ID  
Sent By pleduc Date 2016-04-13 Time   Rev Time 0.00
Received By pleduc Date 2016-04-13 Time 10:25 Sent To  
Notes
2016-04-13 10:43:57THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1. SHEET A 2.1 - ANY AND ALL WORK ON THE FIRE ALARM AND
 FIRE SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE
 SHOP DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 2. SHEET E 1.1 - EXISTING EXITSIGNS AND EMERGENCY
 LIGHTS SHALL BE CONFIRMED ON FIRE INSPECTION.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2017-02-21 Time 15:05 Sent To  
Notes
2017-02-22 15:05:34C16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-06 Cont ID  
Sent By jwitmer Date 2016-05-06 Time 14:28 Rev Time 0.00
Received By jwitmer Date 2016-04-11 Time 11:05 Sent To  
Notes
2016-04-11 11:06:50C16

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By gjohnson Date 2017-02-28 Time 10:05 Sent To  
Notes
2017-02-28 13:47:361ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SINK IN BRAKE-ROOM SHALL COMPLY WITH FBC ACC 606.3
 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 606.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop Z ZONING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-04-15 Cont ID  
Sent By eschneid Date 2016-04-15 Time 18:13 Rev Time 0.50
Received By eschneid Date 2016-04-15 Time 18:13 Sent To  
Notes
***NONE***