2016-04-12 12:35:34 | ELECTRICAL REVIEW COMMENTS |
| REVIEWED FOR COMPLIANCE WITH: |
| 2010 FLORIDA BLDG. CODES; 2008 NEC |
| |
| CORRECTIONS REQUIRED FOR THE SUBMITTED AS-BUILT |
| DRAWINGS AS INDICATED BELOW. WHERE THREE AND FOUR WAY |
| SWITCHING IS MENTIONED PLEASE NOTE THAT THIS IS ONLY A |
| SUGGESTION IN THE INTEREST OF ENERGY CONSERVATION, LIFE |
| SAFETY AND USER CONVENIENCE AND THEY DO NOT HAVE TO BE |
| INSTALLED. |
| 1. NEC 250.94 MISSING THE INTER SYSTEM BONDING TERMINAL |
| REQUIRED. |
| 2. NEC 110.12 & NEC 408.4 THE AS-BUILT DRAWINGS PANEL |
| SCHEDULES SHOULD INDICATE THE PANEL?S MANUFACTURER NAME |
| BRAND. |
| 3. NEC 220 PART III ADJUST THE LOADS AND CALCS AS |
| INSTRUCTED BY NEC. I WORKED THE LOAD CALCS AND CAME UP |
| WITH A MUCH LOWER NUMBER. |
| 4. REVISE THE SWITCH SYMBOL ON THE DRAWINGS TO MATCH |
| THE LEGEND |
| 5. NEC 210.70(A)(1) PROVIDE A WALL SWITCH FOR THE LIGHT |
| IN ROOM 100. |
| 6. NEC 210.70(A)(1) PROVIDE THE REQUIRED LIGHT AND WALL |
| SWITCH IN ROOMS 113, 105 & 109. |
| 7. NEC 210.52(A)(1) OUTLET SPACING IN ROOM 213 IS NOT |
| TO CODE. |
| 8. NEC 210.70(A)(1) THERE SHALL BE A LIGHT CONTROLLED |
| BY A WALL SWITCH IN THE ROOM BETWEEN ROOMS 211 & 213. |
| PREFERABLY THIS LIGHT SHOULD HAVE A 3 WAY SWITCH. |
| 9. ADD AN ADDITIONAL SWITCH FOR THE HALL 201 AND |
| VESTIBULE 211 AS IT EXITS INTO ROOM 213. THIS WOULD BE |
| A 4 WAY SWITCH. |
| 10. NEC 210.52(E)(3) A GFI PROTECTED OUTLET IS REQUIRED |
| IN THE BALCONY OUTSIDE OF ROOM 202. |
| 11. A 3 WAY SWITCH TO CONTROL HALL WAY 207 LIGHTS AS IT |
| EXITS INTO ROOM 209 IS SUGGESTED. |
| 12. NEC 406.8 ALL RECEPTACLES IN DAMP OR WET LOCATIONS |
| SHALL BE LISTED WEATHER-RESISTANT IN ADDITION TO HAVING |
| AN IN-USE TYPE COVER. |
| 13. FBC-E SECTION 404.1 A MINIMUM OF 50% OF THE LAMPS |
| IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE |
| HIGH-EFFICACY LAMPS. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |
| PH: 561-805-6746 |
| EMAIL: [email protected] |
| |