Plan Review Details - Permit 16040512
Plan Review Stops For Permit 16040512
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-05-02 Cont ID  
Sent By skennedy Date 2016-05-02 Time 17:20 Rev Time 0.00
Received By skennedy Date 2016-05-02 Time 17:20 Sent To  
Notes
2016-05-02 17:21:45IT IS NOTED THAT SOME INFORMATION FROM THE PERMIT SET
 OF PLAN HAS BEEN OMITTED FROM SHEETS E-1 & E-2. SUCH
 INFOMATION STILL APPLIES.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-04-27 Cont ID  
Sent By albarran Date 2016-04-27 Time 19:14 Rev Time 0.00
Received By albarran Date 2016-04-27 Time 16:52 Sent To M
Notes
2016-04-27 19:14:47ELECTRICAL REVIEW COMMENTS
  
 CORRECTIONS REQUIRED:
 1. THERE ARE SEVERAL ITEMS THAT MAY NOT BE TO CODE BUT
 WERE INITIALLY MISSED BY BOTH MYSELF AND LATER THE
 INSPECTOR.
 2. PROVIDE MANUFACTURER SPECS FOR BOTH, THE RANGE/OVEN
 AND HVAC TO CONFIRM THAT THE OCPD AND WIRING AS
 INDICATED ON YOUR PANEL SCHEDULES IS ACCEPTABLE,
 OTHERWISE CORRECT THE PANEL SCHEDULE AND LOAD CALCS
 ACCORDINGLY.
 3. FBC-R303.9 REQUIRE THAT YOU PROVIDE HEAT ENOUGH TO
 MAINTAIN 68 DEGREES WITHIN 3? OF THE FLOOR IN EVERY
 HABITABLE ROOM. THE HVAC LOADS INDICATED DO NOT REFLECT
 THAT.
 4. CORRECTION TO THE SMOKE DETECTOR NOTE. SMOKE
 DETECTORS MAY NOT BE WITHIN 20? OF THE RANGE UNLESS IT
 CAN BE SILENCED.
 5. IF ROOM 100 IS AN EXTERIOR ROOM IT BECOMES A PORCH
 BY CODE STANDARDS AND AS PER NEC 210.52(E)(3), IT
 REQUIRES AN OUTLET.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-04-12 Cont ID  
Sent By albarran Date 2016-04-12 Time 12:35 Rev Time 0.00
Received By albarran Date 2016-04-12 Time 08:35 Sent To I
Notes
2016-04-12 12:35:34ELECTRICAL REVIEW COMMENTS
 REVIEWED FOR COMPLIANCE WITH:
 2010 FLORIDA BLDG. CODES; 2008 NEC
  
 CORRECTIONS REQUIRED FOR THE SUBMITTED AS-BUILT
 DRAWINGS AS INDICATED BELOW. WHERE THREE AND FOUR WAY
 SWITCHING IS MENTIONED PLEASE NOTE THAT THIS IS ONLY A
 SUGGESTION IN THE INTEREST OF ENERGY CONSERVATION, LIFE
 SAFETY AND USER CONVENIENCE AND THEY DO NOT HAVE TO BE
 INSTALLED.
 1. NEC 250.94 MISSING THE INTER SYSTEM BONDING TERMINAL
 REQUIRED.
 2. NEC 110.12 & NEC 408.4 THE AS-BUILT DRAWINGS PANEL
 SCHEDULES SHOULD INDICATE THE PANEL?S MANUFACTURER NAME
 BRAND.
 3. NEC 220 PART III ADJUST THE LOADS AND CALCS AS
 INSTRUCTED BY NEC. I WORKED THE LOAD CALCS AND CAME UP
 WITH A MUCH LOWER NUMBER.
 4. REVISE THE SWITCH SYMBOL ON THE DRAWINGS TO MATCH
 THE LEGEND
 5. NEC 210.70(A)(1) PROVIDE A WALL SWITCH FOR THE LIGHT
 IN ROOM 100.
 6. NEC 210.70(A)(1) PROVIDE THE REQUIRED LIGHT AND WALL
 SWITCH IN ROOMS 113, 105 & 109.
 7. NEC 210.52(A)(1) OUTLET SPACING IN ROOM 213 IS NOT
 TO CODE.
 8. NEC 210.70(A)(1) THERE SHALL BE A LIGHT CONTROLLED
 BY A WALL SWITCH IN THE ROOM BETWEEN ROOMS 211 & 213.
 PREFERABLY THIS LIGHT SHOULD HAVE A 3 WAY SWITCH.
 9. ADD AN ADDITIONAL SWITCH FOR THE HALL 201 AND
 VESTIBULE 211 AS IT EXITS INTO ROOM 213. THIS WOULD BE
 A 4 WAY SWITCH.
 10. NEC 210.52(E)(3) A GFI PROTECTED OUTLET IS REQUIRED
 IN THE BALCONY OUTSIDE OF ROOM 202.
 11. A 3 WAY SWITCH TO CONTROL HALL WAY 207 LIGHTS AS IT
 EXITS INTO ROOM 209 IS SUGGESTED.
 12. NEC 406.8 ALL RECEPTACLES IN DAMP OR WET LOCATIONS
 SHALL BE LISTED WEATHER-RESISTANT IN ADDITION TO HAVING
 AN IN-USE TYPE COVER.
 13. FBC-E SECTION 404.1 A MINIMUM OF 50% OF THE LAMPS
 IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-28 Cont ID  
Sent By ccole Date 2016-04-28 Time 11:01 Rev Time 0.00
Received By ccole Date 2016-04-26 Time 09:16 Sent To  
Notes
2016-04-27 09:16:47RESUB ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-12 Cont ID  
Sent By albarran Date 2016-04-12 Time 12:35 Rev Time 0.00
Received By albarran Date 2016-04-11 Time 10:31 Sent To  
Notes
2016-04-12 12:38:214/12/16 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT FILE TO SMALL DENIED BIN "C".
 MA
2016-04-11 10:31:41CCOLE'S DESK

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-04-28 Cont ID  
Sent By ccole Date 2016-04-28 Time 11:00 Rev Time 0.00
Received By ccole Date 2016-04-28 Time 11:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-04-12 Cont ID  
Sent By ccole Date 2016-04-12 Time 07:15 Rev Time 0.00
Received By ccole Date 2016-04-12 Time 07:15 Sent To  
Notes
2016-04-12 07:36:331ST REVIEW: FBC 2010 RESIDENTIAL, MECHANICAL
 REVISION PERMIT #16040512
 MASTER #15050486
 4/12/16
  
 1) THE 6" FLEX DUCTS SUPPLYING 240 CFMS EACH TO THE
 FUTURE BONUS ROOM ARE UNDERSIZED PER ACCA MANUAL D
 CALCULATIONS. PLEASE INCREASE THE SIZES TO MINIMUIM
 10".
 2) THE 12" FLEX TRUNK LINE SUPPLYING 600 CFMS TO
 BEDROOMS 2 & 3 IS UNDERSIZED AND SHOULD INCREASE TO
 MINIMUM 14" PER ACCA MANUAL D.
 3) REVISE THE AIR HANDLER CLOSET DETAIL TO INDICATE THE
 TOTAL WIDTH OF THE ENCLOSING SPACE SHALL BE MINIMUM 12"
 WIDER THAN THE AIR HANDLER- SECTION 1305.1.1 FBC-10
 RESIDENTIAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  