Plan Review Stops For Permit 16040430 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2016-11-16 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-11-16 |
Time |
07:11 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-11-15 |
Time |
14:36 |
Sent To |
|
|
Notes |
2016-11-16 06:56:37 | APPROVED WITH EXCEPTIONS | | BUILDING PROVISO | | 1) SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117 | | ENHANCED FASTENING CALCULATIONS FOR THE POLYGLASS | | MODIFIED ROOFING SYSTEM. (THE ROOF DESIGN UPLIFT | | PRESSURES ON SHEET S-3 SHOULD USE 10 SQUARE FT. RATHER | | THAN 20 SQUARE FOR THE EFFECTIVE WIND AREA WHICH | | RESULTS IN GREATER UPLIFT PRESSURES THAN THE ONES THAT | | ARE LISTED.) | | 2) SUBMIT TWO SETS DETAILS AND INSTALLATION | | INSTRUCTIONS FOR THE ELEVATOR SHAFT, THE ELEVATOR AND | | THE ELEVATOR EQUIPMENT. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2016-10-20 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-10-20 |
Time |
18:14 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-10-20 |
Time |
16:07 |
Sent To |
|
|
Notes |
2016-10-20 18:14:09 | PLAN | | REVIEW COMMENTS | | | | 3RD REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SHOW COMPLIANCE WITH FBC R401.3 SURFACE WATER | | DRAINAGE ON THE SITE PLAN. SURFACE DRAINAGE SHALL BE | | DIVERTED TO A STORM SEWER CONVEYANCE OR OTHER APPROVED | | POINT OF COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS | | SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM | | FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 | | INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048 MM). | | WHERE LOT LINES, WALLS, SLOPES OR OTHER PHYSICAL | | BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL WITHIN 10 | | FEET (3048 MM), DRAINS OR SWALES SHALL BE CONSTRUCTED | | TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. IMPERVIOUS | | SURFACES WITHIN 10 FEET (3048 MM) OF THE BUILDING | | FOUNDATION SHALL BE SLOPED A MINIMUM OF 2 PERCENT AWAY | | FROM THE BUILDING. SUBMIT TWO COPIES OF A SURFACE WATER | | DRAINAGE PLAN THAT SHOWS THE FLOW OF THE SURFACE WATER. | | | | 3) SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117 | | CALCULATIONS FOR THE ENHANCED FASTENING OF THE TAMKO | | MODIFIED ROOFING SYSTEM OVER WOOD DECKS (NOA NO. | | 12-1003.05). SEE LIMITATION NUMBER 7 ON THE NOA. THE | | MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT | | ASSEMBLIES LISTED IN THE PRODUCT APPROVAL ARE TYPICALLY | | FOR ROOF ZONE ONE AND REQUIRE ENHANCED FASTENING FOR | | THE PERIMETER (ZONE 2) AND CORNER ZONES(ROOF ZONE 3). | | PLEASE INDICATE THE APPROVED ASSEMBLY AND THE DESIGN | | PRESSURE FROM THE PRODUCT APPROVAL THAT WILL BE USED | | AND SUBMIT THE RAS 117 ENHANCED FASTENING CALCULATIONS. | | | | 4) SPECIFY THE APPROVED ASSEMBLY AND THE DESIGN | | PRESSURES FOR THE TAMKO MODIFIED ROOFING SYSTEM OVER | | CONCRETE DECK THAT WILL BE USED. CIRCLE THE APPROPRIATE | | INFORMATION ON THE PRODUCT APPROVAL. FBC 107.2.1 | | | | 5) THIS WILL BE NOTED ON THE PLANS. ENGINEERED SHOP | | DRAWINGS FOR THE GLASS BALCONY GUARDS ARE REQUIRED TO | | BE SUBMITTED AND APPROVED PRIOR TO INSTALLATION. FBC | | R312, R308.4.4 & FBC107.3.4.2 | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2016-08-04 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-08-04 |
Time |
19:14 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-08-04 |
Time |
09:09 |
Sent To |
M |
|
Notes |
2016-08-04 19:12:16 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD | | AREA ( A5 ). THE MINIMUM FINISH FLOOR ELEVATION | | INCLUDING THE 6" FREE BOARD REQUIRED BY THE CITY OF | | WEST PALM BEACH IS 7.5' NGVD. THE GARAGE FLOOR AND THE | | EQUIPMENT PADS ARE ALSO REQUIRED TO BE AT OR ABOVE 7.5' | | NGVD. SPECIFY THE PROPOSED FINISH FLOOR ELEVATIONS ON | | THE PLANS. FBC-R 322.1 THE ELEVATIONS OF THE ATTACHED | | GARAGE AND THE EQUIPMENT PADS WERE NOT SPECIFIED ON THE | | PLANS. | | | | 2) SHOW COMPLIANCE WITH FBC R401.3 SURFACE WATER | | DRAINAGE ON THE SITE PLAN. SURFACE DRAINAGE SHALL BE | | DIVERTED TO A STORM SEWER CONVEYANCE OR OTHER APPROVED | | POINT OF COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS | | SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM | | FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 | | INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048 MM). | | | | 3) PROVIDE STRUCTURAL AND FASTENING DETAILS FOR THE | | STEEL ANGLE LEDGE THAT WILL BE USED TO SUPPORT THE | | STONE WALL VENEER. FBC R703.7.2.1 & R703.7.2.2 | | | | 4) SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117 | | CALCULATIONS FOR THE ENHANCED FASTENING OF THE TAMKO | | MODIFIED ROOFING SYSTEM OVER WOOD DECKS (NOA NO. | | 12-1003.05). SEE LIMITATION NUMBER 7 ON THE NOA. | | | | 5) SUBMIT PRODUCT APPROVALS FOR THE ROOFING SYSTEM THAT | | WILL BE USED OVER THE CONCRETE DECKS. DCA RULE 9N-3 THE | | PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND | | APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | 6) THE PRODUCT APPROVALS FOR THE TAMKO ROOFING SYSTEMS | | HAVE SEVERAL DIFFERENT APPROVED ASSEMBLIES WITH | | DIFFERENT DESIGN PRESSURES, SPECIFY THE ASSEMBLY AND | | THE DESIGN PRESSURES THAT WILL BE INSTALLED. IF THE | | PRODUCT'S DESIGN PRESSURES ARE NOT ADEQUATE FOR THE | | INCREASED PRESSURES AT THE PERIMETER AND CORNER AREAS, | | THEN SIGNED AND SEALED RAS 117 CALCULATIONS ARE | | REQUIRED TO BE SUBMITTED IN ACCORDANCE WITH LIMITATION | | #7 ON THE LAST PAGE OF THE NOA. | | | | 7) SUBMIT ENGINEERED SHOP DRAWINGS FOR THE GLASS | | BALCONY GUARDS FOR REVIEW PRIOR TO INSTALLATION. FBC | | R312, R308.4.4 & FBC107.3.4.2 | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2016-05-16 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-05-16 |
Time |
18:25 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-05-11 |
Time |
18:14 |
Sent To |
|
|
Notes |
2016-05-16 16:46:01 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD | | AREA ( A5 ). THE MINIMUM FINISH FLOOR ELEVATION | | INCLUDING THE 6" FREE BOARD REQUIRED BY THE CITY OF | | WEST PALM BEACH IS 7.5' NGVD. THE GARAGE FLOOR AND THE | | EQUIPMENT PADS ARE ALSO REQUIRED TO BE AT OR ABOVE 7.5' | | NGVD. SPECIFY THE PROPOSED FINISH FLOOR ELEVATIONS ON | | THE PLANS. FBC-R 322.1 | | | | 2) SUBMIT TWO SETS OF A PRE-CONSTRUCTION ELEVATION | | CERTIFICATE THAT SHOWS COMPLIANCE WITH THE CITY'S FLOOD | | ORDINANCE. | | | | 3) SUBMIT TWO SETS OF A SIGNED AND SEALED SUB-SURFACE | | SOIL INVESTIGATION REPORT. FBC-R401.4 | | | | 4) SUBMIT TWO SETS OF A SURVEY/SITE PLAN THAT SHOWS THE | | LOCATION OF THE PROPOSED STRUCTURES AND THE DISTANCES | | TO PROPERTY LINES. FBC-R302.1 | | | | 5) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE | | ENERGY COMPLIANCE FORM R405. FBC ENERGY R103.1.1.2 | | | | 6) SHOW COMPLIANCE WITH FBC-R302.1.2 DRAFTSTOPPING. THE | | CONCEALED SPACE IN THE FLOOR/CEILING ASSEMBLY BETWEEN | | THE FIRST AND SECOND FLOOR CAN NOT EXCEED 1,000 SQUARE | | FEET AND IS REQUIRED TO BE DIVIDED INTO TWO | | APPROXIMATELY EQUAL AREAS. | | | | 7) THE FIRST FLOOR PLAN ON SHEET A-2 SPECIFIES A | | BEDROOM NUMBER 4 AND IT APPEARS THAT THIS DWELLING ONLY | | HAS 3 BED ROOMS. THE STUDY/EXERCISE ROOM DOES NOT HAVE | | A CLOSET AND IS NOT CONSIDERED A BEDROOM. FBC 107.2.1 | | | | 8) ON SHEET A-2 THE ENGINEERING CRITERIA HAS THE | | OCCUPANCY TYPE AS R2 AND SINGLE FAMILY DWELLINGS ARE | | R3. | | | | 9) THE FOUNDATION NOTES ON S-1 LIST THE WRONG EDITIONS | | OF THE REFERENCE STANDARDS. THESE ARE THE CORRECT ONES: | | ACI 530/530.1-11, ASCE 5-11 AND ASCE 6-11. FBC-R | | CHAPTER 46 | | | | 10) THE NOTES ON A-1 LIST THE WRONG EDITIONS OF THE | | REFERENCE STANDARDS. THESE ARE THE CORRECT ONES: ASTM | | C94-09, ACI 318-11, ACI 332-10, ACI 53-11 AND ACI | | 530.1-11. FBC-R CHAPTER 46 | | | | 11) ON SHEET A-8 THE ROOF NOTE FOR WOOD FRAMING AND THE | | PLYWOOD DECKING HAS AN ARROW THAT POINTS TO THE | | CONCRETE DECK. FBC 107.2.1 | | | | 12) SUBMIT PRODUCT APPROVALS FOR THE STONE WALL VENEER. | | DCA RULE 9N-3 | | | | 13) SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117 | | CALCULATIONS FOR THE ENHANCED FASTENING OF THE TAMKO | | MODIFIED ROOFING SYSTEM OVER WOOD DECKS (NOA NO. | | 12-1003.05). SEE LIMITATION NUMBER 7 ON THE NOA. | | | | 14) SUBMIT PRODUCT APPROVALS FOR THE ROOFING SYSTEM | | THAT WILL BE USED OVER THE CONCRETE DECKS. DCA RULE | | 9N-3 | | | | | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2016-11-16 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-11-16 |
Time |
08:21 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-11-15 |
Time |
19:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2016-10-13 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2016-10-13 |
Time |
15:48 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2016-10-13 |
Time |
11:40 |
Sent To |
|
|
Notes |
2016-10-13 15:50:23 | NEW SHEETS WERE ADDED WITHOUT ANY INDICATION OF A | | NARRATIVE CREATING THE NEED FOR A COMPLETE ELECTRICAL | | REVIEW. | | | | 2ND ELECTRICAL REVIEW NOTES | | REVIEWED FOR COMPLIANCE WITH: | | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) | | | | | | JOB ADDRESS: 2900 N. FLAGLER DR. | | DESCRIPTION: NEW SINGLE FAMILY RESIDENCE | | MASTER PERMIT: 16040430 | | | | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. | | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF | | SUBMITTED CORRECTIONS. ITEMS 2 & 3 BELOW CAN BE | | ADDRESSED WITH A BLOCK NOTE ADDED TO THE PLANS. | | | | 1. MARK ON THE PLANS THE LOCATION OF ALL HVAC EQUIPMENT | | AS WELL AS THE WASHER AND DRYERS. | | 2. FBC-R4002.9 NEC 406.9(B) RECEPTACLES IN WET | | LOCATIONS. 15 AND 20 AMPERE, 125 AND 250 VOLT | | RECEPTACLES INSTALLED IN A WET LOCATION SHALL HAVE AN | | ENCLOSURE THAT IS WEATHERPROOF WHETHER OR NOT THE | | ATTACHMENT PLUG CAP IS INSERTED. ALL 15 AND 20 AMPERE, | | 125 AND 250 VOLT NONLOCKING RECEPTACLES SHALL BE LISTED | | WEATHER-RESISTANT TYPE ?WR?. | | 3. FBC-ER404.1: A MINIMUM OF 75% OF THE LAMPS IN | | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE | | HIGH-EFFICACY LAMPS OR A MINIMUM OF 75% OF THE | | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN | | ONLY HIGH EFFICIENCY LAMPS. | | 4. THERE DOES NOT APPEAR TO BE SUFFICIENT LIGHT IN THE | | ELEVATOR LOBBY AREA OF THE 2ND FLOOR. | | 5. CLARIFY THE AHU 1 & 2 VS. A/C 1-3 AND INCLUDE THEM | | ALL IN THE ELECTRICAL LOAD CALCS. | | 6. FBC-RE3901.4.4/NEC 210.52(C)(4) SEPARATE SPACES: | | COUNTERTOP SPACES SEPARATED BY RANGE TOPS, | | REFRIGERATORS, OR SINKS SHALL BE CONSIDERED AS SEPARATE | | COUNTERTOP SPACES IN APPLYING THE REQUIREMENTS OF THE | | CODE. WHERE A RANGE, COUNTER-MOUNTED COOKING UNIT, OR | | SINK IS INSTALLED IN AN ISLAND OR PENINSULAR COUNTERTOP | | AND THE DEPTH OF THE COUNTERTOP BEHIND THE RANGE, | | COUNTER-MOUNTED COOKING UNIT, OR SINK IS LESS THAN 12 | | INCHES (305 MM), THE RANGE, COUNTER-MOUNTED COOKING | | UNIT, OR SINK HAS DIVIDED THE COUNTERTOP SPACE INTO TWO | | SEPARATE COUNTERTOP SPACES AS DEFINED IN SECTION | | E3901.4.4. EACH SEPARATE COUNTERTOP SPACE SHALL COMPLY | | WITH THE APPLICABLE REQUIREMENTS OF THIS SECTION. | | THEREFORE AN OUTLET IS MISSING IN THE SUMMER KITCHEN | | ISLAND ON THE OTHER SIDE OF THE SINK. | | 7. FBC-RE3901.2.1/NEC 210.52 (A)(1) SPACING. | | RECEPTACLES SHALL BE INSTALLED SUCH THAT NO POINT | | MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL | | SPACE IS MORE THAN 6 FT. FROM A RECEPTACLE OUTLET. THIS | | INCLUDES THE DISTANCE FROM THE EDGE OF THE WALL. | | THEREFORE, YOU SHALL ADD OR RELOCATE THE EXISTING | | OUTLETS IN THE MASTER BEDROOM, GREAT ROOM ADJACENT TO | | THE SLIDING GLASS DOORS TO COMPLY. ADD MISSING OUTLET | | IN BOTH THE STUDY AND DINNING TO COMPLY. | | 8. FBC-RE3901.6/NEC 210.52(D) BATHROOMS. IN DWELLING | | UNITS, AT LEAST ONE RECEPTACLE OUTLET SHALL BE | | INSTALLED IN BATHROOMS WITHIN 3 FT. OF THE OUTSIDE EDGE | | OF EACH BASIN. RELOCATE THE MARKED OR ADD A NEW OUTLET | | IN HER BATH TO COMPLY. | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER | | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER | | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE | | GREATLY APPRECIATED. | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | CONTACT ME DIRECTLY. | | | | THANK YOU, | | MIKE ALBARRAN | | ELECTRICAL PLANS EXAMINER | | PH: 561-805-6746 | | EMAIL: [email protected] | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2016-07-15 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2016-07-15 |
Time |
13:12 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2016-07-15 |
Time |
11:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2016-04-14 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2016-04-14 |
Time |
15:50 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2016-04-14 |
Time |
11:02 |
Sent To |
|
|
Notes |
2016-04-14 15:51:49 | 1ST ELECTRICAL REVIEW COMMENTS | | REVIEWED FOR COMPLIANCE WITH: | | 5TH EDITION OF THE FBC 2014 & NFPA 70 (NEC) 2011 | | EDITION | | | | CORRECTIONS REQUIRED: | | 1. ISSUES ON THE ELECTRICAL NOTES OF PAGES E-1 & E-2 | | A) NOTE 2, STATES THE CURRENT CODE. YOU SHALL INDICATE | | THE ACTUAL CODE TO WHICH THE PROJECT IS DESIGNED. IN | | THIS CASE THE APPLICABLE ELECTRICAL CODE IS THE 2011 | | EDITION OF THE NEC. | | B) NOTE 7, THE WORD ?ROMEX? AS USED IN THIS NOTE IS TO | | IDENTIFY A TYPE OF CABLE. ROMEX IS A BRAND NAME AND NOT | | A TYPE OF CABLE, REFER TO CABLE TYPES ?NM?, ?NMC? OR | | ?NMS?. | | C) NOTE 8, AS ABOVE, THE APPLICABLE CODE IS NOT THE | | LATEST, BUT THE 2011 EDITION. | | 2. NEC 404.4. WHERE SWITCHES CONTROLLING LIGHTING LOADS | | SUPPLIED BY A GROUNDED BRANCH CIRCUIT, THE GROUNDED | | BRANCH CIRCUIT CONDUCTOR FOR THE CONTROLLED LIGHTING | | CIRCUIT SHALL BE PROVIDED AT THE SWITCH. | | 3. NEC 314.27(D) PADDLE FANS. BOXES USED FOR THE SOLE | | SUPPORT OF CEILING FANS SHALL BE MARKED BY THE | | MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND INDICATE | | THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT | | PADDLE FANS HEAVIER THAN 70 LBS. | | 4. SHOW HVAC EQUIPMENT AND ITS RESPECTIVE DISCONNECT ON | | THE ELECTRICAL FLOOR PLANS. | | 5. NEC 210.52(E)(3) BALCONIES. BALCONIES GREATER THAN | | 20 SQ. FT. SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET | | INSTALLED WITHIN THE PERIMETER OF THE BALCONY. AN | | OUTLET IS REQUIRED WITHIN THE PERIMETER OF THE SUN | | DECK. | | 6. THE SUBMITTED RISER DIAGRAM HAS PANELS A, B, C & | | POOL PANEL. PANELS ARE NOT IDENTIFIED ON THE ELECTRICAL | | FLOOR PLAN. SHOW ALL PANELS ON THE ELECTRICAL FLOOR | | PLANS. | | 7. NEC 230.72 GROUPING OF DISCONNECTS. (A) GENERAL. THE | | TWO TO SIX DISCONNECTS AS PERMITTED IN 230.71 SHALL BE | | GROUPED. EACH DISCONNECT SHALL BE MARKED TO INDICATE | | THE LOAD SERVED. | | 8. THE POOL EQUIPMENT SHALL BE IDENTIFIED IF IT IS A | | PART OF THE SCOPE, OTHERWISE MARK IT AS FUTURE. | | 9. EVERY ROOM ON THE FLOOR PLAN SHALL BE LABELED TO | | ASCERTAIN MINIMUM ELECTRICAL REQUIREMENTS IF | | APPLICABLE. | | 10. NEC 310.15(B)(7) PERMITS #3 CU FOR 110 AMP | | RESIDENTIAL SERVICES. PANELS ?C? & POOL ARE SAID TO BE | | 100 AMP ON THE LABEL YET THE SPECS INDICATE A 200 AMP | | BUS RATING AND MAIN BREAKER FED WITH 3 #3AWG. CORRECT | | ACCORDINGLY. | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER | | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER | | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE | | GREATLY APPRECIATED. | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | CONTACT ME DIRECTLY. | | | | THANK YOU, | | MIKE ALBARRAN | | ELECTRICAL PLANS EXAMINER | | PH: 561-805-6746 | | EMAIL: [email protected] | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
N |
Date |
2016-10-15 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-10-15 |
Time |
06:57 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-10-15 |
Time |
06:57 |
Sent To |
|
|
Notes |
2016-10-15 06:57:57 | A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | THIS TIME. A GAS PERMIT IS REQUIRED FOR A CONTRACTOR TO | | PERFORM THE RELATED WORK. PROVIDE COMPLETE PLANS THAT | | REFLECT THE ENTIRE SCOPE OF GAS WORK TO BE DONE. WPB | | AMEND. TO FBC SEC.107.2.1. | | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE | | FBC-R, SEC. G2404.3. | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL | | GAS SEC. 301.3. | | | | A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2016-11-16 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-11-16 |
Time |
08:33 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-11-10 |
Time |
16:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2016-11-10 |
|
|
Cont ID |
|
Sent By |
spalmer |
Date |
2016-11-10 |
Time |
14:31 |
Rev Time |
0.00 |
Received By |
spalmer |
Date |
2016-09-22 |
Time |
10:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2016-08-11 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2016-08-11 |
Time |
11:05 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2016-07-06 |
Time |
14:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-05-16 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-05-16 |
Time |
18:25 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-04-07 |
Time |
09:18 |
Sent To |
|
|
Notes |
2016-04-19 10:06:27 | | | | 2016-04-08 09:18:25 | R15 |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
3 |
Status |
P |
Date |
2016-11-17 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-11-17 |
Time |
09:51 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-11-17 |
Time |
09:51 |
Sent To |
|
|
Notes |
2016-11-17 09:51:53 | MU-2016-28360, NO FEES WERE DUE. |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
F |
Date |
2016-08-04 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-08-04 |
Time |
09:12 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-08-04 |
Time |
09:12 |
Sent To |
|
|
Notes |
2016-08-04 09:12:23 | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. | | | | |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2016-05-11 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-05-11 |
Time |
18:14 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-05-11 |
Time |
18:14 |
Sent To |
|
|
Notes |
2016-05-11 18:15:09 | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2016-11-09 |
|
|
Cont ID |
|
Sent By |
jvalido |
Date |
2016-11-09 |
Time |
17:29 |
Rev Time |
0.00 |
Received By |
jvalido |
Date |
2016-11-09 |
Time |
16:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2016-08-11 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2016-08-11 |
Time |
11:05 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2016-08-10 |
Time |
08:54 |
Sent To |
|
|
Notes |
2016-08-11 11:05:00 | PLAN DENIED | | 1) REFER TO SECTION M1302.1 LISTED AND LABELED. FOR | | KITCHEN HOOD.2014 RESIDENTIAL CODE | | 2) REFER TO TABLE M1507.4 BATHROOM EXHAUST 2014 | | RESIDENTIAL CODE | | 3) REFER TO SECTION M1602.4 BALANCED RETURN AIR | | 2014 RESIDENTIAL CODE | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2016-04-19 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2016-04-19 |
Time |
10:07 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2016-04-18 |
Time |
13:45 |
Sent To |
|
|
Notes |
2016-04-19 10:19:53 | PLAN DENIED | | 1) PROVIDE BATHROOM EXHAUST FOR GUEST AND | | MASTER BATHROOM. PER TABLE M1507.4 | | RESIDENTIAL CODE 2014 | | 2) PROVIDE MANUFACTURER'S INSTALLATION INSTRUCTIONS | | FOR THE CLOTHES DRYER AND AIR CONDITIONING EQUIPMENT | | WITH THE PLAN. PER SECTION M1502 CLOTHES DRYER EXHAUST. | | 3) PROVIDE MANUFACTURER'S INSTALLATION INSTRUCTIONS | | ON THE KITCHEN HOOD WITH THE PLAN | | PER SECTION M1503.4 MAKE UP AIR REQUIRED. | | 4) REFER TO SECTION M1602.4 BALANCED RETURN AIR | | EXCEPTION # 2 | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 | | | | | | |
|
|
Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
Rev No |
2 |
Status |
F |
Date |
2016-08-04 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-08-04 |
Time |
09:49 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-08-04 |
Time |
09:49 |
Sent To |
|
|
Notes |
2016-08-04 10:26:54 | EMAIL SAMANTHA HILL WHEN PERMIT IS READY TO BE PRINTED. | | PRE-CONSTRUCTION ELEVATION CERTIFICATE DEFECIENCIES. | | 1) THE SQUARE FOOTAGE OF THE ATTACHED GARAGE WAS NOT | | PROVIDED ON THE LINE FOR PART A9 (A). | | 2) THE LOWEST ELEVATION OF THE EQUIPMENT SERVICING THE | | BUILDING WAS NOT PROVIDED ON THE LINE FOR PART C2 (E). | | |
|
|
Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
Rev No |
1 |
Status |
N |
Date |
2016-05-11 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-05-11 |
Time |
16:58 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-05-11 |
Time |
16:57 |
Sent To |
|
|
Notes |
2016-05-11 16:59:27 | EMAIL SAMANTHA HILL WHEN PERMIT IS READY TO BE PRINTED. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2016-10-15 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-10-15 |
Time |
06:56 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-10-15 |
Time |
06:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2016-07-23 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-07-23 |
Time |
12:07 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-07-23 |
Time |
11:38 |
Sent To |
|
|
Notes |
2016-07-23 12:03:07 | 1) SECONDARY (EMERGENCY) ROOF DRAINS OR SCUPPERS ARE | | REQUIRED PER 2014 FPC SEC. 1108. IF SCUPPERS ARE | | SUPPLIED, COMPLY WITH TABLE 1106.7 OF THE FPC. | | 2) WASHING MACHINE DRAIN IS UNDERSIZED & NOT VENTED. | | 2014 FBCR SEC. P3201.7, P3101.2. | | 3) SHOWER IN CABANA BATH NOT PROPERLY VENTED. 2014 FBCR | | SEC. P3201.7, P3101.2. | | 4) SHOWER IN HIS BATH NOT PROPERLY VENTED. 2014 FBCR | | SEC. P3201.7, P3101.2. | | 5) WET VENT FOR HER BATH IS UNDERSIZED. 2014 FBCR SEC. | | P3108.3. | | 6) SIZE ALL VENTS ON THE SANITARY RISER. | | 7) SINK IN SUMMER KITCHEN NOT ON SANITARY RISER. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2016-04-26 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2016-04-26 |
Time |
09:45 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2016-04-26 |
Time |
09:20 |
Sent To |
|
|
Notes |
2016-04-26 09:55:07 | | | 1ST REVIEW: FBC 2014 | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: | | | | 1. EMERGENCY / SECONDARY ROOF DRAINS ARE REQUIRED AND | | SHALL COMPLY WITH FBC PL SEC. 1108 | | | | 2. A CLEANOUT SHALL BE PROVIDED AT THE BASE OF EACH | | WASTE OR SOIL STACK. PER FBC RES. SEC. P3005.2.6 | | | | 3. THE MORNING BAR IS MISSING ON THE SANITARY RISER | | DIAGRAM PLEASE PERVIDE PER WPB AMEND. TO FBC SEC. | | 107.2.1 | | | | 4.IS THE ELEVATOR HYDRAULIC OR TRACK TYPE .PER WPB | | AMEND. TO FBC SEC. 107.2.1 | | | | 5. A SEPARATE PERMIT IS REQUIRED FOR FUEL GAS PIPING. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
P |
Date |
2016-11-15 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-11-15 |
Time |
16:00 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-11-15 |
Time |
16:00 |
Sent To |
|
|
Notes |
2016-11-15 17:30:23 | FL 16429-R5 POLYGLASS MODIFIED BITUMEN ROOF SYSTEM | | NUMBER W-48 AND SC-24. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
|
|
|
Cont ID |
|
Sent By |
awooten |
Date |
2016-11-02 |
Time |
|
Rev Time |
0.00 |
Received By |
awooten |
Date |
2016-11-02 |
Time |
11:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2016-07-08 |
|
|
Cont ID |
|
Sent By |
llouie |
Date |
2016-07-08 |
Time |
|
Rev Time |
0.00 |
Received By |
llouie |
Date |
2016-07-08 |
Time |
|
Sent To |
|
|
Notes |
2016-07-08 15:26:59 | ** FAILED ** | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | APPLICABLE: | | | | 1.) THE SITE PLAN IS MISSING FROM THE PERMIT | | APPLICATION. THE SITE PLAN SHALL PROVIDE THE FOLLOWING | | INFORMATION: NORTH ARROW AND A GRAPHIC SCALE; VICINITY | | MAP SHOWING THE PROPERTY IN RELATIONSHIP TO THE | | SURROUNDING AREA; BUILDING FOOTPRINT(S) OF ALL NEW AND | | EXISTING STRUCTURES SHOWING SETBACK DIMENSIONS IN | | RELATIONSHIP TO THE PROPERTY LINES; DRIVEWAYS AND CURB | | CUTS AND MEANS OF VEHICULAR AND PEDESTRIAN ACCESS TO | | AND FROM THE SITE; LOCATION AND DIMENSIONS OF ALL | | PERIMETER TREATMENT (I.E. SIDEWALKS, FENCES, WALLS, | | ETC.); DATA TABLE WITH THE FOLLOWING INFORMATION: | | EXISTING/PROPOSED LAND USE; TOTAL ACRES OF THE PROJECT; | | GROSS BUILDING SQUARE FOOTAGE; PERCENT OF OPEN SPACE, | | LANDSCAPING, BUILDING COVERAGE AND IMPERMEABLE | | SURFACES; PARKING COMPUTATIONS; SETBACK REQUIREMENTS | | (REQUIRED AND PROPOSED). [REPEAT COMMENT FROM 4/12/16] | | | | 2.) STRUCTURAL OVERHANGS, INCLUDING BUT NOT LIMITED TO | | BALCONIES, EAVES AND ROOF OVERHANG PROJECTIONS SHALL | | NOT EXTEND FARTHER THAN 3 FT. INTO ANY SETBACK. [ZLDR | | S.94-305(B)(2)], [REPEAT COMMENT FROM 4/12/16: | | COMPLIANCE WITH STRUCTURAL OVERHANGS CANNOT BE | | DETERMINED WITHOUT A SITE PLAN SHOWING DIMENSIONS.] | | | | 3.) MECHANICAL EQUIPMENT, INCLUDING POOL EQUIPMENT, A/C | | UNITS, ETC., SHALL NOT PROJECT MORE THAN 4 FT. INTO A | | SETBACK. [ZLDR S.94-305(B)(4)], [REPEAT COMMENT FROM | | 4/12/16: COMPLIANCE WITH SETBACKS CANNOT BE DETERMINED | | WITHOUT A SITE PLAN SHOWING DIMENSIONS] | | | | 4.) A SEPARATE LANDSCAPE PERMIT SUBMITTAL AND REVIEW IS | | REQUIRED FOR THE PROJECT. PLEASE SUBMIT A LANDSCAPE | | PERMIT CONCURRENTLY WITH THIS PERMIT APPLICATION. | | [REPEAT COMMENT FROM 4/12/16] | | | | REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL | | COMMENTS. PLEASE CONTACT LINDA LOUIE @ (561) 822-1458 | | IF THERE ARE QUESTIONS. | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2016-04-12 |
|
|
Cont ID |
|
Sent By |
llouie |
Date |
2016-04-12 |
Time |
11:08 |
Rev Time |
0.00 |
Received By |
llouie |
Date |
2016-04-11 |
Time |
15:28 |
Sent To |
|
|
Notes |
2016-04-12 11:10:24 | ** FAILED ** | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS IN WRITING OR ON | | THE PLANS WHERE APPLICABLE: | | | | 1.) THE SITE PLAN IS MISSING FROM THE PERMIT | | APPLICATION. THE SITE PLAN SHALL PROVIDE THE FOLLOWING | | INFORMATION: NORTH ARROW AND A GRAPHIC SCALE; VICINITY | | MAP SHOWING THE PROPERTY IN RELATIONSHIP TO THE | | SURROUNDING AREA; BUILDING FOOTPRINT(S) OF ALL NEW AND | | EXISTING STRUCTURES SHOWING SETBACK DIMENSIONS IN | | RELATIONSHIP TO THE PROPERTY LINES; DRIVEWAYS AND CURB | | CUTS AND MEANS OF VEHICULAR AND PEDESTRIAN ACCESS TO | | AND FROM THE SITE; LOCATION AND DIMENSIONS OF ALL | | PERIMETER TREATMENT (I.E. SIDEWALKS, FENCES, WALLS, | | ETC.); DATA TABLE WITH THE FOLLOWING INFORMATION: | | EXISTING/PROPOSED LAND USE; TOTAL ACRES OF THE PROJECT; | | GROSS BUILDING SQUARE FOOTAGE; PERCENT OF OPEN SPACE, | | LANDSCAPING, BUILDING COVERAGE AND IMPERMEABLE | | SURFACES; PARKING COMPUTATIONS; SETBACK REQUIREMENTS | | (REQUIRED AND PROPOSED). | | | | 2.) STRUCTURAL OVERHANGS, INCLUDING BUT NOT LIMITED TO | | BALCONIES, EAVES AND ROOF OVERHANG PROJECTIONS SHALL | | NOT EXTEND FARTHER THAN 3 FT. INTO ANY SETBACK. [ZLDR | | S.94-305(B)(2)] | | | | 3.) MECHANICAL EQUIPMENT, INCLUDING POOL EQUIPMENT, A/C | | UNITS, ETC., SHALL NOT PROJECT MORE THAN 4 FT. INTO A | | SETBACK. [ZLDR S.94-305(B)(4)] | | | | 4.) A SEPARATE LANDSCAPE PERMIT SUBMITTAL AND REVIEW IS | | REQUIRED FOR THE PROJECT. PLEASE SUBMIT A LANDSCAPE | | PERMIT CONCURRENTLY WITH THIS PERMIT APPLICATION. | | | | REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL | | COMMENTS. PLEASE CONTACT LINDA LOUIE @ (561) 822-1458 | | IF THERE ARE QUESTIONS. | | |
|
|