Plan Review Details - Permit 16040415
Plan Review Stops For Permit 16040415
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2017-03-30 Cont ID  
Sent By shill Date 2017-03-30 Time 14:34 Rev Time 0.00
Received By shill Date 2017-03-30 Time 14:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-01-10 Cont ID  
Sent By jwitmer Date 2017-01-10 Time 12:18 Rev Time 0.00
Received By jwitmer Date 2017-01-10 Time 10:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-12-06 Cont ID  
Sent By jwitmer Date 2016-12-06 Time 09:16 Rev Time 0.00
Received By jwitmer Date 2016-12-06 Time 09:09 Sent To  
Notes
2016-12-06 09:16:32PLANS WILL BE STAMPED ONCE COMMENTS FROM PERMIT
 16040412 ARE APPROVED. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-08-12 Cont ID  
Sent By jwitmer Date 2016-08-12 Time 16:12 Rev Time 0.00
Received By jwitmer Date 2016-08-11 Time 16:09 Sent To  
Notes
2016-08-12 16:11:57BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16040415
 ADD: 1522 N DIXIE HWY.
 CONT: TBD/ TO BE DETERMINED
 TEL: (561)662-1927
 E-MAIL:[email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. AUGUST 12/2016
 ACTION: DENIED
  
 1) COMPLIED.
  
 2)PLEASE NOTE THE SITE PLAN IS REQUIED FOR SHOWING THE
 ACCESSIBLE ROUTE TO THE PUBLIC WAY AS WELL AS FOR
 SHOWING A CODE COMPLIANT ACCESSIBLE PARKING. PLEASE
 NOTE THAT THE PARKING LOT STRIPPING WILL REQUIRE A
 SEPARATE PERMIT AND PLANS. THANK YOU.
  
 2A) SEMI COMPLIED.SHEET A-1.0. 2014 FBC-B 1027.5 ACCESS
 TO A PUBLIC WAY. THE EXIT DISCHARGE SHALL PROVIDE A
 DIRECT AND UNOBSTRUCTED ACCESS TO A PUBLIC WAY. THE NEW
 ENTRY DOOR IS SHOWN TO BE ON AN ACCESSIBLE ROUTE
 (LANDINGS AND RAMP) WITH AN ACCESS AISLE MARKED TO THE
 CITY SIDEWALK. WHAT THEN SHOWS IS AN ACCESS AISLE INTO
 THE STREET AND WHAT APPEARS TO BE DESIGNATED DROP OFF
 ZONE IN THE CITY RIGHT OF WAY. PLEASE EXPLAIN.
  
 2B) COMPLIED. 2014 FBC-ACCESSIBILITY CODE 206.2.4
 SPACES AND ELEMENTS. AT LEAST ONE ACCESSIBLE ROUTE
 SHALL CONNECT ACCESSIBLE BUILDING OR FACILITY ENTRANCES
 WITH ALL ACCESSIBLE SPACES AND ELEMENTS WITHIN THE
 BUILDING OR FACILITY WHICH ARE OTHERWISE CONNECTED BY A
 CIRCULATION PATH TO THE PUBLIC WAY..
  
 2C) SEMI-COMPLIED. SHEET A-1.0 THE NEW PARKING PLAN FOR
 1522 N. DIXIE NOW SHOWS AN ACCESSIBLE PARKING PLACE ON
 THE NORTH SIDE OF THE PARKING LOT. THERE IS A SPACE TO
 THE WEST NOT DESIGNATED AS PARKING, NO CAR STOP IN THE
 SPACE, IT IS UNCLEAR WHAT THIS SPACE IS TO BE USED FOR.
 IF THE PARKING SPACE IS GOING TO BE FOR PARKING OR FOR
 DELIVERY DROP-OFF IT WOULD STILL COMPEL THE USER OF THE
 ACCESSIBLE PARKING SPACE TO WHEEL BEHIND PARKED
 VEHICLES. IF THE ACCESSIBLE PARKING SPACE WERE THE
 FURTHEST WET IN THE PARKING LOT AND THE ACCESS AISLE TO
 BE ON THE WEST SIDE OF THE ACCESSIBLE SPACE THIS ACCESS
 AISLE WOULD OR COULD BE CONTINUED TO THE ACCESS AISLE
 TO THE SOUTH.
 2014 FBC-ACCESSIBILITY 208.3.1 WHERE IN THE ACCESSIBLE
 PARKING SPACE AND ACCESS AISLE THE PATRON IS NOT
 COMPELLED TO WALK OR WHEEL BEHIND PARKED CARS.
  
 3) COMPLIED.
  
 4) 2ND REQUEST. LS-1.0B SHOWS A NEW EXTERIOR DOOR # 29.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 5) 2ND REQUEST. 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-04-29 Cont ID  
Sent By gearl Date 2016-05-04 Time 13:25 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2016-05-04 15:10:07BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16040415
 ADD: 1522 N DIXIE HWY.
 CONT: TBD/ TO BE DETERMINED
 TEL: (561)662-1927
 E-MAIL:[email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MAY 04/2016
 ACTION: DENIED
  
 1A) THE COVER SHEET INDICATES THE PLANS WERE DEVELOPED
 TO THE 2010 FBC CODE. STATEWIDE JUNE 30/2015 THE 2014
 FBC-B/ 5TH EDITION WAS ADOPTED STATEWIDE.
  
 1B) THE COVERSHEET THE INDEX IS MISSING (4) SHEETS THAT
 ARE IN THE PLAN SET. SHEET D-2.0, A-1.0, A-2.1 & A-7.1.
  
 2) SHEET A-1.0 INDICATES THE PROPOSED SITE PLAN. THIS
 IS AN UNUSUAL BUILDING SINCE NONE OF THE TENANT SPACE
 (1600 N DIXIE) HAVE DOORWAYS THAT EXIT ONTO A PUBLIC
 RIGHT OF WAY. PLEASE PROVIDE A SITE PLAN SHOWING
 COMPLIANCE WITH:
  
 2A) 2014 FBC-B 1027.5 ACCESS TO A PUBLIC WAY. THE EXIT
 DISCHARGE SHALL PROVIDE A DIRECT AND UNOBSTRUCTED
 ACCESS TO A PUBLIC WAY.
  
 2B) 2014 FBC-ACCESSIBILITY CODE 206.2.4 SPACES AND
 ELEMENTS. AT LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT
 ACCESSIBLE BUILDING OR FACILITY ENTRANCES WITH ALL
 ACCESSIBLE SPACES AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY WHICH ARE OTHERWISE CONNECTED BY A CIRCULATION
 PATH TO THE PUBLIC WAY, UNLESS EXEMPTED BY 206.2.3
 EXCEPTIONS 1 THROUGH 7.
  
 2C) 2014 FBC-ACCESSIBILITY 208.3.1 WHERE IN THE
 ACCESSIBLE PARKING SPACE AND ACCESS AISLE THE PATRON IS
 NOT COMPELLED TO WALK OR WHEEL BEHIND PARKED CARS.
  
 3) SHEET LS-1.0B INDICATES THE USE OF A 2 HOUR WALL,
 WALL TYPE ?D?. . PLEASE PROVIDE THE UL DETAIL FOR THE
 INSPECTOR WILL BE ABLE TO IDENTIFY THE VARIOUS
 COMPONENTS OF THE WALL ASSEMBLY. 2014 FBC-B 707.3 FIRE
 ?RESISTANCE RATINGS. 107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED.
  
 4) LS-1.0B SHOWS A NEW EXTERIOR DOOR # 29. 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 5) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 6) PLEASE PROVIDE THE PRESSURES BOTH POSITIVE AND
 NEGATIVE FOR THESE DOORS IN VASD. 2014 FBC-B 1603.1.4
 WIND DESIGN DATA.
  
 7) ) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 THE REVIEWS FOR THIS PROJECT ARE COMPLETE. TO VIEW
 COMMENTS FROM ALL DISCIPLINES:
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2017-03-28 Cont ID  
Sent By rlecky Date 2017-03-28 Time 11:53 Rev Time 0.00
Received By rlecky Date 2017-03-28 Time 11:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2017-01-25 Cont ID  
Sent By vperez Date 2017-01-25 Time 09:38 Rev Time 0.00
Received By vperez Date 2017-01-25 Time 09:38 Sent To  
Notes
2017-01-25 09:38:50ROBERT LECKY APPROVED/ DID NOT SIGNOUT

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2016-12-14 Cont ID  
Sent By mvaldes Date 2016-12-14 Time 15:50 Rev Time 0.00
Received By mvaldes Date 2016-12-14 Time 15:50 Sent To  
Notes
2016-12-14 15:51:10JOB PERMIT NUMBER: 1640412 & 16040415
 JOB ADDRESS: 1600 & 1522 N DIXIE HWY
 WEST PALM BEACH FLORIDA 33401
 DATE: DECEMBER 14, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 - THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED.
  
 1] BUILDING 1600 N DIXIE HIGHWAY RISER DIAGRAM REFLECTS
 THE EQUIPMENT GROUNDING CONDUCTOR FOR PANEL "DP" IN
 PARALLEL WHICH IS IN VIOLATION OF NEC 310.10(H) &
 250.122(F).
  
 2] BY MODIFICATIONS DONE TO THE ELECTRICAL SYSTEM,
 USING THE EXISTING AVAILABLE FAULT CURRENT PLEASE SHOW
 AIC CALCULATIONS TO VERIFY SHORT CIRCUIT RATING OF NEW
 ELECTRICAL EQUIPMENT. NEC 110.24, 110.10, 110.9.
  
 3] IN ADDITION TO THE SERVICE PERMANENT PLAQUE REQUIRED
 BY NEC 230.2(E) PLEASE PROVIDE A SHUNT TRIP DEVICE AT
 EACH SERVICE LOCATION TO FACILITATE FIRST RESPONDERS,
 THE DEVICE SHALL BE INSTALLED AT A READILY ACCESSIBLE
 LOCATION PER NEC 230.70(A)(3).
  
 - PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME
 DIRECTLY.
  
 3RD REVIEW FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-08-04 Cont ID  
Sent By albarran Date 2016-08-04 Time 10:35 Rev Time 0.00
Received By albarran Date 2016-08-04 Time 08:56 Sent To  
Notes
2016-08-04 10:36:09ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: FRESENIUS MEDICAL CARE ADDITION
 JOB ADDRESS: 1522 & 1600 N. DIXIE HWY.
 DESCRIPTION: RENOVATION OF EXISTING SPACE
 MASTER PERMIT:16040415
 REVISION: (THIS PACKET IS RUNNING TOGETHER WITH PERMIT
 16040412)
  
 THE BELOW MENTIONED COMMENTS WILL RELATE TO BOTH
 PERMITS AS THEY ARE SHARING A SUBMITTAL
 1. THERE ARE TWO SEPARATE PERMITS AND THEREFORE THERE
 SHOULD BE TWO SEPARATE PLAN SETS. IF NOT AT A MINIMUM
 THREE SETS SO THAT ONE CAN BE STORED ON RECORD FOR EACH
 PERMIT NUMBER EVEN IF THEY WILL BE SHARING THE JOB
 COPY. AT PRESENT THERE IS ONLY ONE SET OF DRAWINGS
 ATTACHED TO EACH PERMIT AND THEY DO NOT MATCH. THE
 SHEET INDEX OF T1.0 FOR EACH SET MENTIONS 11
 INDIVIDUALLY NUMBERED ELECTRICAL SHEETS. THE SET OF
 PERMIT 16040415 IS MISSING SHEET E2.0A AND SHEET E2.2
 IS REPLACED W/SHEET E2.2A. THE SET OF PERMIT 16040412
 DOES INCLUDE SHEET E2.0A BUT ALSO HAS A SHEET E2.2A
 RATHER THAN AN E2.2. CORRECT THAT ACCORDINGLY.
 2. YOU DID NOT RESPOND TO MY COMMENT #3 WHICH ADDRESSES
 THE DAYLIGHT ZONE ISSUE. I INADVERTENTLY CALLED OUT
 SHEET E2.1 WHICH OBVIOUSLY DOES NOT INCLUDE THE
 LIGHTING. IT IS SHEET E2.0A THAT ADDRESSES THE LIGHTING
 AND NOTHING HAS BEEN DONE TO ADDRESS THE DAYLIGHT
 LIGHTING ZONE CONTROL. PLEASE CORRECT THAT ACCORDINGLY.
 3. WITH REGARDS TO MY COMMENT #4, THE FACT THAT THESE
 TWO BUILDINGS ARE TO BE CONNECTED WILL POSE A LIFE
 SAFETY HAZARD BY HAVING TWO SERVICES. THEREFORE, RATHER
 THAN HAVING SHUNT TRIP CAPABILITIES YOU SHALL PLACE A
 WARNING PLACARD AT EACH SERVICE INFORMING EMERGENCY
 PERSONNEL OF THE OTHER SERVICE AND THE LOCATION OF THE
 DISCONNECT.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-04-13 Cont ID  
Sent By albarran Date 2016-04-13 Time 19:08 Rev Time 0.00
Received By albarran Date 2016-04-13 Time 11:04 Sent To  
Notes
2016-04-13 18:56:05THIS PERMIT IS RIDING ALONG WITH16040412 AND ARE
 SHARING THE PLANS, THEREFORE THE COMMENTS ARE COMMON TO
 BOTH PERMIT.
  
 ELECTRICAL REVIEW COMMENTS
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION OF THE FBC 2014 & NFPA 70 (NEC) 2011
 EDITION
  
 CORRECTIONS REQUIRED:
 BLDG. DEPT. NOTES ON COVER SHEET
 1. A) INDICATE THAT THE PLANS WERE DESIGNED TO MEET THE
 REQUIREMENTS OF THE 2008 NEC. D) REFERS TO THE LATEST
 CODE. THE 2011 EDITION OF THE NEC IS THE ONE CURRENTLY
 ADOPTED BUT IT IS NOT THE LATEST EDITION.
 SHEET E2.0A
 1. NOTE 14 AGAIN REFERS TO AN OLD CODE. THOUGH THE
 VERBIAGE OF THE OLD CODE DIDN'T VARY WITH THE NEW ONE
 THE REFERENCE IS INCORRECT.
 2. FROM THIS DRAWING IT IS VERY DIFFICULT TO RECOGNIZE
 WHAT AND WHERE WOULD THE DAYLIGHT ZONE BE FOR
 COMPLIANCE WITH THE FBC-EC402 & 405
 SHEET E2.1A
 1. NEC 225.34 RESTRICTS THE NUMBER OF DISCONNECTS AND
 REQUIRES THAT THEY BE GROUPED.
 SHEET E2.1B
 1. PANELS LA & LB DO NOT COMPLY WITH NEC 110.26
 SHEET E2.2A
 1. SEPARATE PERMIT AND SUBMITTAL REQUIRED FOR THE FIRE
 ALARM.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-04-04 Cont ID  
Sent By scaldero Date 2017-04-04 Time 10:37 Rev Time 0.00
Received By scaldero Date 2017-04-04 Time 10:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-08-08 Cont ID  
Sent By scaldero Date 2016-08-08 Time 11:36 Rev Time 0.00
Received By scaldero Date 2016-08-08 Time 11:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-04-11 Cont ID  
Sent By scaldero Date 2016-04-11 Time 14:44 Rev Time 0.00
Received By scaldero Date 2016-04-11 Time 14:44 Sent To  
Notes
2016-04-11 14:44:33PERMIT #16040415
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 2) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 3) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2017-05-15 Cont ID  
Sent By shill Date 2017-05-08 Time 11:18 Rev Time 0.00
Received By shill Date 2017-03-24 Time 15:09 Sent To  
Notes
2017-03-27 15:09:11B29
 *TRAVELLING WITH 16040412*

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2017-02-01 Cont ID  
Sent By ccole Date 2017-02-01 Time 09:14 Rev Time 0.00
Received By ccole Date 2017-01-30 Time 11:39 Sent To  
Notes
2017-01-31 11:39:27RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-01-25 Cont ID  
Sent By vperez Date 2017-01-25 Time 09:39 Rev Time 0.00
Received By vperez Date 2017-01-25 Time 09:38 Sent To  
Notes
2016-12-30 09:37:17B29

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-12-14 Cont ID  
Sent By mvaldes Date 2016-12-14 Time 15:51 Rev Time 0.00
Received By mvaldes Date 2016-11-21 Time 13:33 Sent To  
Notes
2016-11-22 13:33:22B29 **TRAVELLING WITH 16040412**

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-25 Cont ID  
Sent By eschneid Date 2016-08-25 Time 09:37 Rev Time 0.00
Received By eschneid Date 2016-07-29 Time 10:47 Sent To  
Notes
2016-08-01 10:47:28B29
 *TRAVELLING WITH 16040412*

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-24 Cont ID  
Sent By eschneid Date 2016-05-24 Time 13:20 Rev Time 0.00
Received By eschneid Date 2016-04-07 Time 09:00 Sent To  
Notes
2016-04-08 09:00:16B29 TRAVELLING WITH 16040412

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-05-04 Cont ID  
Sent By jwitmer Date 2016-05-04 Time 15:10 Rev Time 0.00
Received By jwitmer Date 2016-05-04 Time 15:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2017-02-01 Cont ID  
Sent By ccole Date 2017-02-01 Time 09:15 Rev Time 0.00
Received By ccole Date 2017-02-01 Time 09:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2017-01-13 Cont ID  
Sent By ccole Date 2017-01-13 Time 17:14 Rev Time 0.00
Received By ccole Date 2017-01-13 Time 17:14 Sent To  
Notes
2017-01-13 17:14:264TH REVIEW FBC-2014 MECHANICAL
 PERMIT #16040415
 1/5/17
  
 1) THE ENERGYGAUGE COMPLIANCE FORM IS INDICATING 17
 SEER FOR RTU'S 5-9, HOWEVER THE EQUIPMENT SCHEDULE ON
 THE PLANS LISTS THEM AT 13 SEER- PLEASE CORRECT.
  
 2) PROVIDE COMPLIANCE DATA ON THE ENERGYGAUGE FORM FOR
 OAU-1.
  
 2) AUTOMATIC SHUTOFF DAMPERS ARE REQUIRED FOR THE OAU
 DUCTS SUPPLYING THE RTU'S- SEE SECTION C403.2.4.4
 FBC-14 ENERGY CONSERVATION.
  
 3) PREVIOUS COMMENT #9 STILL EXISTS: PROVIDE A FIRE
 DAMPER FOR THE 8X6 O/A DUCT PENETRATING THE THE
 FIRE-RATED PD RECORDS WALL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-12-02 Cont ID  
Sent By ccole Date 2016-12-02 Time 10:58 Rev Time 0.00
Received By ccole Date 2016-12-02 Time 10:58 Sent To  
Notes
2016-12-02 10:58:233RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16040415
 12/2/16
  
 1) SHEETS M-1 & M-2.1: IT APPEARS THAT THE RTU
 SCHEDULE, AND THE ENERGY AND AC CALCULATIONS ARE
 INDICATING NEW UNITS ARE BEING INSTALLED. PLEASE
 CORRECT THE MECHANICAL ROOF PLAN INDICATING EXISTING.
  
 2) CLARIFY IF THE DUCT HEATERS ARE NEW OR EXISTING AND
 LABEL THEM ACCORDINGLY. IF NEW UNITS ARE BEING
 PROVIDED, PLEASE PROVIDE AN EQUIPMENT SCHEDULE.
  
 3) M-1, FAN SCHEDULE: PROVIDE THE CONTROL SEQUENCE FOR
 EF-7.
  
 4) M-1 & M-2.0A: THE EXHAUST CALCULATION IS SPECIFYING
 EXHAUST RATES BASED ON SECTION 502.8.1.1 FBC-14
 MECHANICAL. PLEASE REVIEW AND SHOW COMPLIANCE WITH
 ITEMS #1-7 UNDER 502.8.1.1, AND ALSO REFER TO SECTION
 510.8 FOR EXHAUST DUCT REQUIREMENTS AND SHOW DETAILS ON
 THE PLAN.
  
 5) PLEASE REFER TO TABLE 7-1 ASHRAE 170- 2008 AND
 PROVIDE THE DESIGN PARAMETERS FOR THE SOILED UITILITY
 AND MEDICAL WASTE ROOMS. SHOW PRESSURE RELATIONSHIPS
 AND REQUIRED OUTDOOR AND TOTAL AIR CHANGES RO EACH
 ROOM.
  
 6) PROVIDE AIR BALANCE CALCULATIONS THAT INCLUDE THE
 NEW EXHAUST VENTILATION SYSTEMS.
  
 7) 2ND REQUEST FOR THE DEFINITION OF "HT" STORAGE ROOM
 AND WHAT MATERIALS ARE BEING STORED IN THE ROOM. AS
 PREVIOUSLY NOTED EXHAUST VENTILATION MAY BE REQUIRED
 AND RECIRCULATION IOF AIR PROHIBITED.
  
 8) M2.0A: SHOW THE DUCT DROP AND DUCT PLAN FOR OAU-1.
  
 9) M2.0A: THERE APPEARS TO BE A MISSING FIRE DAMPER
 WHERE THE 8X6 DUCT IS PENETRATING THE FIRE-RATED PD
 RECORDS ROOM WALL.
  
 10 ) A RESPONSE NARRATIVE WAS NOT SUBMITTED WITH THE
 CORRECTED PLANS. PLEASE PROVIDE A RESPONSE NARRATIVE
 ADDRESSING THESE REVIEW COMMENTS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-08-05 Cont ID  
Sent By ccole Date 2016-08-05 Time 16:16 Rev Time 0.00
Received By ccole Date 2016-08-05 Time 16:16 Sent To  
Notes
2016-08-05 16:24:002ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16040412
 8/4/16
  
 1) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW: A)
 PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE SOILED
 UTILITY, MED WASTE, AND LAB ROOMS. B) PROVIDE AN
 EXHAUST SYSTEM IN THE LAB ROOM PER TABLE 403.3 AND
 ASHRAE 62.1-2010. PLEASE NOTE THAT RECIRCULATION OF AIR
 FROM THE SPACE IS PROHIBITED PER TABLE 403.3 FOOTNOTE G
  
 2) DEFINE "HT" AS IT APPLIES TO THE HT STORAGE ROOM.
 INDICATE WHAT MATERIALS AND/OR EQUIPMENT ARE BEING
 STORED IN THE ROOM. PLEASE NOTE THAT EXHAUST
 VENTILATIONS MAY BE REQUIRED.
  
 3) M-3.1: AS PREVIOUSLY REQUESTED PROVIDE COMPLETE
 ENGINEERED DETAILS FOR MOUNTING THE NEW RTU'S TO THE
 CURBS- SECTION 301.15. PLEASE INCLUDE THE WIND LOAD
 DESIGN CRITERIA FOR THE INSTALLATIONS AS OUTLINED IN
 SECTION 1609 FBC-14 BUILDING. CONTRARY TO THE RESPONSE
 NARRATIVE FROM JMM ENGINEERS, RTU'S 5, 6, 7, 8, &9 ARE
 NOT EXISTING AND WERE NEVER PERMITTED. BUILDING
 DEPARTMENT RECORDS INDICATE PERMIT #15070429 WAS ISSUED
 FOR INSTALLATION OF THE CURBS ONLY WITH CAPPING FOR
 FUTURE USE. WIND LOAD ENGINEERING IS ALSO REQUIRED
 INSTALLATION OF THE ROOFTOP FANS AND CURBS- EF-1, 2, 3,
 4, 5, & 6.
  
 4) SHEET M-2.1: AS PREVIOSULY REQUESTED, PROVIDE THE
 CLEARANCE DISTANCE MEASURERMENTS FROM THE EXHAUST FANS
 TO THE ROOF EDGES. ARE THERE PARAPETS THAT EXTEND AT
 LEAST 42" ABOVE THE FINISHED ROOF SURFACE?
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-04-14 Cont ID  
Sent By ccole Date 2016-04-14 Time 12:20 Rev Time 0.00
Received By ccole Date 2016-04-14 Time 12:20 Sent To  
Notes
2016-04-14 12:46:581ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16040415
 4/14/16
  
 1) SHEET M1.0: THE OUTSIDE AIR CALULATIONS ARE BASED ON
 THE OUTDATED FMC- 2010. THE CURRENT CODE IN EFFECT IS
 THE FBC- 2014 MECHANICAL: PLEASE REVIEW AND UPDATE.
 2) M1.0: PLEASE INDICATE THE OFFICE OR ROOM NUMBERS IN
 THE OUTSIDE AIR SCHEDULE AND INCLUDE CALULATIONS FOR
 ALL ROOMS AND SPACES INCLUDING THE EXAMINATION AND
 MEDICAL PROCEDURE ROOMS- SEE TABLE 403.3. PLEASE NOTE
 THAT THE "WATER TREATMENT STORAGE" ROOMS LISTED IN THE
 CALCULATIONS DO NOT APPEAR TO BE IN THE SCOPE OF WORK
 FOR THIS PROJECT: PLEASE CLARIFY.
 3) M1.0: PROVIDE EXHAUST VENTILATION CALCULATIONS FOR
 THE SOILED UTILITY, MED WASTE, AND LAB PREP ROOMS.
 PLEASE NOTE THAT NO EXHAUST HAS BEEN PROVIDED FOR THE
 LAB PREP ROOM- SEE TABLE 403.3 AND CLARIFY IF THERE IS
 LAB WORK OR CHEMICAL STORAGE IN THE THIS ROOM- SEE
 TABLE 6-4 ASHRAE 62.1-2010.
 4) D1.0: PLEASE PROVIDE A SCOPE OF WORK FOR MECHANICAL
 DEMOLITION WITH CORREPONDING DRAWINGS AND DETAILS.
 5) M-2.0A: THE 10" FLEX DUCTS SUPPLYING 405 CFMS EACH
 TO THE CONFERENCE ROOM ARE UNDERSIZED PER ACCA MANUAL D
 SIZING METHODS FOR LOW PRESSURE SYSTEMS.
 6) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS
 OF ALL ROOF TOP EQUIPMENT- RTU'S, EXHAUST FANS, AIR
 INTAKES ETC- SEE SECTIONS 401.5 AND 501.3.1 FOR
 REQUIRED CLEARANCE DISTANCES AND PLACE MEASUREMENTS ON
 THE PLAN TO VERIFY COMPLIANCE. SUBMIT NOA'S OR FL.
 PRODUCT APPROVALS FOR THE ROOF TOP FANS, AND FAN AND
 RTU CURBS REVIEWED AND APPROVED WITH SIGNATURE BY THE
 EOR. PLEASE NOTE THAT GUARDS WILL BE REQUIRED FOR ALL
 SERVICEABLE EQUIPMENT ON THE ROOF WITHIN 10' OF A ROOF
 EDGE I.E. EF-6.
 7) INDICATE THE USE OF EF-6 ON THE PLAN AND PROVIDE
 EXHAUST VENTILATION CALCULATIONS, MAKE-UP AIR, A
 VENTING DIAGRAM, AND MANUFACTURER'S SPECIFICATIONS FOR
 THE EXHAUST FAN AND DUCT WORK.
 8) M-3.1: REFER TO SECTRION 301.15 AND PROVIDE WIND
 LOAD DESIGN CRITERIA AND COMPLETE ENGINEERED DETAILS
 FOR TIE DOWN OF THE RTUS, FANS, AND CURBS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-04-04 Cont ID  
Sent By gjohnson Date 2017-04-04 Time 15:33 Rev Time 0.00
Received By gjohnson Date 2017-04-04 Time 15:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-04-29 Cont ID  
Sent By gearl Date 2016-04-29 Time 13:22 Rev Time 0.00
Received By gearl Date 2016-04-29 Time 13:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status F Date 2017-05-08 Cont ID  
Sent By eschneid Date 2017-05-08 Time 15:28 Rev Time 0.25
Received By eschneid Date 2017-05-08 Time 15:26 Sent To  
Notes
2017-05-08 15:32:04FAILED
  
 PROVIDE WRITTEN RESPONSES TO THE COMMENTS. PLEASE NOTE
 THAT THE SUBMITTAL OF THE REQUIRED ITEMS MAY RESULT IN
 ADDITIONAL COMMENTS.
  
 1) REPEAT COMMENT: THE PERMIT PACKAGE INCLUDES A
 PROPOSED SITE PLAN THAT RECONFIGURES THE EXISTING
 PARKING LOT. THE PARKING LOT WORK REQUIRES PARKING LOT
 PERMIT, WHICH SHALL BE SUBMITTED, WITH PLANS, TO THE
 BUILDING DEPARTMENT PRIOR TO ZONING APPROVAL OF THIS
 BUILDING PERMIT - NO PERMIT CURRENTLY SUBMITTED. PLEASE
 NOTE THAT THE CITY HAS NO PERMIT RECORD OF THE REMOVAL
 OF THE WALL AND THE CONNECTION BETWEEN THE TWO
 PROPERTIES, THUS IT APPEARS THAT THIS WAS DONE WITHOUT
 A PERMIT. A PERMIT FOR THIS WORK SHALL ALSO BE
 SUBMITTED, OR INCLUDED WITH THE PARKING LOT PERMIT.
  
 2) PRIOR TO THE FINAL (104) INSPECTION, THE PARKING
 SHALL BE RESTRIPED IN ACCORDANCE WITH CITY CODE
 REQUIREMENTS AND THE DUMPSTER SHALL BE LOCATED WITHIN
 AN ENCLOSURE. BOTH THE STRIPING AND DUMPSTER ENCLOSURE
 REQUIRE BUILDING PERMITS.
  
 3) THE BUILDING RENOVATION ITSELF COMPLIES WITH ZONING,
 BUT THIS PERMIT WILL NOT BE APPROVED UNTIL COMPLIANCE
 WITH ITEM 1.
  
 4) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR:
  
 A. PARKING LOT
 B. LANDSCAPE
 C. IRRIGATION
 D. DUMPSTER ENCLOSURE
 E. AWNINGS
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]
  

Review Stop Z ZONING
Rev No 4 Status F Date 2017-01-23 Cont ID  
Sent By eschneid Date 2017-01-23 Time 15:20 Rev Time 0.25
Received By eschneid Date 2017-01-23 Time 15:20 Sent To  
Notes
2017-01-23 15:34:04FAILED
  
 PROVIDE WRITTEN RESPONSES TO THE COMMENTS. PLEASE NOTE
 THAT THE SUBMITTAL OF THE REQUIRED ITEMS MAY RESULT IN
 ADDITIONAL COMMENTS.
  
 1) REPEAT COMMENT: THE PERMIT PACKAGE INCLUDES A
 PROPOSED SITE PLAN THAT RECONFIGURES THE EXISTING
 PARKING LOT. THE PARKING LOT WORK REQUIRES PARKING LOT
 PERMIT, WHICH SHALL BE SUBMITTED, WITH PLANS, TO THE
 BUILDING DEPARTMENT PRIOR TO ZONING APPROVAL OF THIS
 BUILDING PERMIT - NO PERMIT CURRENTLY SUBMITTED. PLEASE
 NOTE THAT THE CITY HAS NO PERMIT RECORD OF THE REMOVAL
 OF THE WALL AND THE CONNECTION BETWEEN THE TWO
 PROPERTIES, THUS IT APPEARS THAT THIS WAS DONE WITHOUT
 A PERMIT. A PERMIT FOR THIS WORK SHALL ALSO BE
 SUBMITTED, OR INCLUDED WITH THE PARKING LOT PERMIT.
  
 2) PRIOR TO THE FINAL (104) INSPECTION, THE PARKING
 SHALL BE RESTRIPED IN ACCORDANCE WITH CITY CODE
 REQUIREMENTS AND THE DUMPSTER SHALL BE LOCATED WITHIN
 AN ENCLOSURE. BOTH THE STRIPING AND DUMPSTER ENCLOSURE
 REQUIRE BUILDING PERMITS.
  
 3) THE BUILDING RENOVATION ITSELF COMPLIES WITH ZONING.
  
 4) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR:
  
 A. PARKING LOT
 B. LANDSCAPE
 C. IRRIGATION
 D. DUMPSTER ENCLOSURE
 E. AWNINGS
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 3 Status F Date 2016-12-12 Cont ID  
Sent By eschneid Date 2016-12-12 Time 16:14 Rev Time 2.00
Received By eschneid Date 2016-12-09 Time 14:22 Sent To  
Notes
2016-12-12 16:14:49FAILED
  
 PROVIDE WRITTEN RESPONSES TO THE COMMENTS. PLEASE NOTE
 THAT THE SUBMITTAL OF THE REQUIRED ITEMS MAY RESULT IN
 ADDITIONAL COMMENTS.
  
 1) REPEAT COMMENT: THE PERMIT PACKAGE INCLUDES A
 PROPOSED SITE PLAN THAT RECONFIGURES THE EXISTING
 PARKING LOT. THE PARKING LOT WORK REQUIRES PARKING LOT
 PERMIT, WHICH SHALL BE SUBMITTED, WITH PLANS, TO THE
 BUILDING DEPARTMENT PRIOR TO ZONING APPROVAL OF THIS
 BUILDING PERMIT - NO PERMIT CURRENTLY SUBMITTED. PLEASE
 NOTE THAT THE CITY HAS NO PERMIT RECORD OF THE REMOVAL
 OF THE WALL AND THE CONNECTION BETWEEN THE TWO
 PROPERTIES, THUS IT APPEARS THAT THIS WAS DONE WITHOUT
 A PERMIT. A PERMIT FOR THIS WORK SHALL ALSO BE
 SUBMITTED, OR INCLUDED WITH THE PARKING LOT PERMIT.
  
 2) PRIOR TO THE FINAL (104) INSPECTION, THE PARKING
 SHALL BE RESTRIPED IN ACCORDANCE WITH CITY CODE
 REQUIREMENTS AND THE DUMPSTER SHALL BE LOCATED WITHIN
 AN ENCLOSURE. BOTH THE STRIPING AND DUMPSTER ENCLOSURE
 REQUIRE BUILDING PERMITS.
  
 3) REVISED COMMENT: THE DEMOLITION PLAN AND THE
 PROPOSED SITE PLAN DO NOT SHOW ACCURATE EXISTING AND
 PROPOSED CONDITIONS ON THE EAST SIDE OF THE BUILDING
 WHERE THE ELECTRIC METER AND OTHER EQUIPMENT ARE. THE
 PLANS SHOW THESE AREAS AS LANDSCAPING; HOWEVER, THE
 ACTUAL EQUIPMENT IS ALMOST THE FULL DEPTH OF THE CURBED
 AREA AND SITS ON TWO CONCRETE PADS (SHOWN ON THE
 SURVEY) WHICH LEAVES NO SPACE FOR FOUNDATION PLANTING.
 THIS AREA SHALL NOT BE LABELED AS EXISTING OR FUTURE
 FOUNDATION PLANTING AREA. THE NEW PLANS DO PROVIDE MORE
 FOUNDATION PLANTING THAN WAS REMOVED. 42 SF REMOVED -
 80 SF INSTALLED.
  
 4) REVISED COMMENT: THE EXISTING SITE PLAN INCORRECTLY
 SHOWS THE AREA OF EXISTING BUFFER LANDSCAPE ALONG THE
 NORTH PROPERTY LINE. THE BUFFER EXTENDS TO THE SHED
 (SURVEY AND SITE CONDITION). THE EXISTING AND PROPOSED
 SITE PLANS INCORRECTLY SHOW THE AREA WHERE THE ELECTRIC
 METER AND OTHER EQUIPMENT ARE LOCATED AS LANDSCAPE
 AREA. THE PLANS SHALL REFLECT ACCURATE CONDITIONS. THE
 NEW PLANS DO PROVIDE MORE SITE LANDSCAPE THAN WAS
 REMOVED. 53 SF REMOVED - 80 SF INSTALLED.
  
 5) THE BUILDING RENOVATION ITSELF COMPLIES WITH ZONING.
  
 6) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR:
  
 A. PARKING LOT
 B. LANDSCAPE
 C. IRRIGATION
 D. DUMPSTER ENCLOSURE
 E. AWNINGS
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2016-08-24 Cont ID  
Sent By eschneid Date 2016-08-24 Time 15:32 Rev Time 1.00
Received By eschneid Date 2016-08-24 Time 14:41 Sent To  
Notes
2016-08-24 15:33:25FAILED
  
 PROVIDE WRITTEN RESPONSES TO THE COMMENTS. PLEASE NOTE
 THAT THE SUBMITTAL OF THE REQUIRED ITEMS MAY RESULT IN
 ADDITIONAL COMMENTS.
  
 1) REVISED COMMENT: THE CONNECTION BETWEEN THE TWO
 BUILDINGS EXTENDS INTO THE REQUIRED FIVE (5) FOOT SIDE
 SETBACK, WHICH IS NOT PERMITTED. IN ORDER TO CONNECT
 THE TWO BUILDINGS, A RECORDED UNITY OF TITLE IS
 REQUIRED TO REMOVE THE PROPERTY LINE AND THUS THE
 REQUIRED SETBACK ALONG WHAT IS CURRENTLY THE SHARED
 PROPERTY LINE. YOU WILL NEED TO PROVIDE A RECORDED COPY
 OF THE COMPLETED UNITY OF TITLE PRIOR TO ZONING
 APPROVAL OF THIS PERMIT.
  
 2) REVISED COMMENT: THE PERMIT PACKAGE INCLUDES A
 PROPOSED SITE PLAN THAT RECONFIGURES THE EXISTING
 PARKING LOT. THE PARKING LOT WORK REQUIRES PARKING LOT
 PERMIT, WHICH SHALL BE SUBMITTED, WITH PLANS, FOR TO
 THE BUILDING DEPARTMENT PRIOR TO ZONING APPROVAL OF
 THIS BUILDING PERMIT - NO PERMIT CURRENTLY SUBMITTED.
 PLEASE NOTE THAT THE CITY HAS NOT PERMIT RECORD OF THE
 REMOVAL OF THE WALL AND THE CONNECTION BETWEEN THE TWO
 PROPERTIES, THUS IT APPEARS THAT THIS WAS DONE WITHOUT
 A PERMIT. A PERMIT FOR THIS WORK SHALL BE SUBMITTED.
  
 3) PRIOR TO THE FINAL (104) INSPECTION, THE PARKING
 SHALL BE RESTRIPED IN ACCORDANCE WITH CITY CODE
 REQUIREMENTS AND THE DUMPSTER SHALL BE LOCATED WITHIN
 AN ENCLOSURE. BOTH THE STRIPING AND DUMPSTER ENCLOSURE
 REQUIRE BUILDING PERMITS.
  
 4) REVISED COMMENT: THE DEMOLITION PLAN SHOWS THE
 PLANTER WITH EXISTING FOUNDATION LANDSCAPE PLANTING
 BEING REMOVED. SINCE THE BUILDING IS CURRENTLY
 DEFICIENT IN THE AMOUNT OF REQUIRED FOUNDATION
 LANDSCAPE PLANTING, IT MAY NOT BE REMOVED UNLESS THE
 SAME, OR MORE, FOUNDATION LANDSCAPE PLANTING IS
 REPLACED. FOUNDATION PLANTINGS SHALL BE ADJACENT TO THE
 BUILDING. THE MAJORITY OF THE 63 SQUARE FEET OF
 REPLACEMENT LANDSCAPE IS NOT ADJACENT TO THE BUILDING
 AND THUS MAY NOT BE COUNTED TOWARD REPLACING THE
 FOUNDATION PLANTING.
  
 5) THE ENTIRE SITE IS DEFICIENT OF LANDSCAPE SO
 CALCULATIONS SHALL BE PROVIDED THAT THE REMOVAL OF THE
 LANDSCAPE ADJACENT TO THE BUILDING, PLUS THE LANDSCAPE
 REMOVED AT THE WALL PASS THROUGH IN THE PARKING LOT
 HAVE BEEN REPLACED WITH THE SAME OR MORE LANDSCAPE ON
 THE SITE.
  
 6) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR:
  
 A. PARKING LOT
 B. LANDSCAPE
 C. IRRIGATION
 D. DUMPSTER ENCLOSURE
 E. AWNINGS
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-05-24 Cont ID  
Sent By eschneid Date 2016-05-24 Time 13:08 Rev Time 2.00
Received By eschneid Date 2016-05-24 Time 09:51 Sent To  
Notes
2016-05-24 13:20:08FAILED
  
 PROVIDE WRITTEN RESPONSES TO THE COMMENTS. PLEASE NOTE
 THAT THE SUBMITTAL OF THE REQUIRED ITEMS MAY RESULT IN
 ADDITIONAL COMMENTS.
  
 1) PROVIDE TWO COPIES OF A SURVEY, LESS THAN ONE YEAR
 OLD, WHICH SHOWS ALL IMPROVEMENTS, DIMENSIONS FROM
 PROPERTY LINES AND EASEMENTS.
  
 2) THE CONNECTION BETWEEN THE TWO BUILDINGS EXTENDS
 INTO THE REQUIRED FIVE (5) FOOT SIDE SETBACK, WHICH IS
 NOT PERMITTED. IN ORDER TO CONNECT THE TWO BUILDINGS, A
 RECORDED UNITY OF TITLE IS REQUIRED TO REMOVE THE
 REQUIRED SETBACK ALONG WHAT IS CURRENTLY THE SHARED
 PROPERTY LINE. PLEASE CONTACT VINCE NOEL, CITY
 SURVEYOR, AT (561) 494-1096 TO BEGIN THE CITY'S UNITY
 OF TITLE APPLICATION PROCESS.
  
 3) THE PERMIT PACKAGE INCLUDES A PROPOSED SITE PLAN
 THAT RECONFIGURES THE EXISTING PARKING LOT AND JOINS IT
 WITH THE PARKING LOT TO THE NORTH. THE PROPOSED PLAN
 INCLUDES THE REMOVAL OF THE ADA PARKING SPACE AND THE
 DUMPSTER THAT ARE SHOWN ON THE EXISTING PLAN FOR THE
 PROPERTY AT 1522 N. DIXIE HIGHWAY. THIS CREATES A
 DEFICIENCY OF ONE (1) PARKING SPACE FOR THE USE. IN
 ORDER TO VERIFY THAT THE NEW ENLARGED PARKING LOT HAS
 SUFFICIENT PARKING TO ACCOMMODATE BOTH THIS BUILDING
 AND THE BUILDING TO THE NORTH, A PARKING LOT PERMIT,
 WITH PLANS, SHALL BE SUBMITTED FOR REVIEW PRIOR TO
 STAFF'S APPROVAL OF THIS BUILDING PERMIT.
  
 4) PRIOR TO THE FINAL (104) INSPECTION, THE PARKING
 SHALL BE RESTRIPED IN ACCORDANCE WITH CITY CODE
 REQUIREMENTS AND THE DUMPSTER SHALL BE LOCATED WITHIN
 AN ENCLOSURE. BOTH THE STRIPING AND DUMPSTER ENCLOSURE
 REQUIRE BUILDING PERMITS. THIS MAY BE DONE EITHER IN
 THE STAND ALONE CURRENT CONFIGURATION OR THE PROPOSED
 SITE PLAN. PLEASE NOTE THAT THE CONDITIONS SHOWN ON THE
 PROPOSED SITE PLAN DO NOT MATCH THE PROPOSED NEW
 DOORWAY ON THE EAST SIDE OF THE BUILDING SHOWN ON THE
 PROPOSED FLOOR PLANS.
  
 5) THE DEMOLITION PLAN SHOWS THE PLANTER WITH EXISTING
 FOUNDATION LANDSCAPE PLANTING BEING REMOVED. SINCE THE
 BUILDING IS CURRENTLY DEFICIENT IN THE AMOUNT OF
 REQUIRED FOUNDATION LANDSCAPE PLANTING, IT MAY NOT BE
 REMOVED UNLESS THE SAME, OR MORE, FOUNDATION LANDSCAPE
 PLANTING IS REPLACED. THE REPLACEMENT FOUNDATION
 LANDSCAPE, WITH SQUARE FOOTAGE VERIFICATION, SHALL BE
 CLEARLY SHOWN ON THE PLANS.
  
 6) STAFF SUGGESTS REVIEWING THE OPTION OF REMOVING THE
 POWER POLES AND BURYING THE UTILITY LINES AS THIS WILL
 IMPROVE THE AESTHETICS OF THE SITE. IT APPEARS EACH
 POLE ONLY SERVES ONE OF THE BUILDINGS. ANOTHER OPTION
 MAY BE TO CONSOLIDATE THE SERVICES ON ONE POLE.
  
 7) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR:
  
 A. PARKING LOT
 B. LANDSCAPE
 C. IRRIGATION
 D. DUMPSTER ENCLOSURE
 E. AWNINGS
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  