Plan Review Details - Permit 16040412
Plan Review Stops For Permit 16040412 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2017-03-30 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2017-03-30 |
Time |
14:34 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2017-03-30 |
Time |
14:34 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2017-01-10 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2017-01-10 |
Time |
12:19 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2017-01-10 |
Time |
10:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2016-12-06 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2016-12-06 |
Time |
09:07 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2016-12-06 |
Time |
09:07 |
Sent To |
|
|
Notes |
2016-12-06 09:07:24 | BUILDING PLAN REVIEW | | W. P. B. PERMIT: 16040412 | | ADD: 1600 N DIXIE HWY. | | CONT: TBD/ TO BE DETERMINED | | TEL: (561)662-1927 | | E-MAIL:[email protected] | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | FLORIDA BUILDING CODE, BUILDING. | | | | 3RD REVIEW | | DATE: TUES. DEC. 06/2016 | | ACTION: DENIED | | | | 4X FEE NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) | | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? | | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN | | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING | | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS | | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO | | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY | | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, | | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. | | | | | | 1) 3RD REQUEST. THE MECHANICAL SHEET M-3.1 SHOWS THE | | ROOF TOP UNITS BEING ATTACHED TO THE ROOF TOP CURBS. | | PLEASE NOTE THAT RTU CURBS WERE REVIEWED AND INSPECTED | | UNDER PERMIT # 15100589. PLEASE NOTE THE WIND DESIGN | | FOR THE ANCHORING OF THE RTU UNIT TO CURB IS 150 MPH. | | PLEASE CORRECT THE WIND DESIGN AND CALCULATIONS FOR | | ANCHORING OF THE RTU TO CURB. THIS IS A 170 VULT MPH | | WIND ZONE FOR BUILDINGS WITH AN BUILDING RISK CATEGORY | | II. SEE 2014 FBC-B FIGURE 1609A. | | | | | | 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL | | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY | | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT | | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY | | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. | | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE | | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES | | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND | | LOADS? | | | | 2) NOTICE THE PARKING LOT STRIPPING WILL BE UNDER A | | AEPARATE PERMIT. THE SITE PLAN PARKING IS FOR SHOWING | | THE ACCESSIBLE EGRESS ROUTE FROM THE BUILDING. NO | | ACCTION NEED TO BE TAKEN. | | | | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | THE REVIEWS FOR THIS PROJECT ARE COMPLETE. TO VIEW | | COMMENTS FROM ALL DISCIPLINES: | | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT | | US.ASPX. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION | | DEVELOPMENT SERVICES DEPARTMENT | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2016-08-12 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2016-08-12 |
Time |
15:34 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2016-08-12 |
Time |
15:02 |
Sent To |
|
|
Notes |
2016-08-12 15:34:17 | BUILDING PLAN REVIEW | | W. P. B. PERMIT: 16040412 | | ADD: 1600 N DIXIE HWY. | | CONT: TBD/ TO BE DETERMINED | | TEL: (561)662-1927 | | E-MAIL:[email protected] | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | FLORIDA BUILDING CODE, BUILDING. | | | | 3RD REVIEW | | DATE: AUGUST 12/2016 | | ACTION: DENIED | | | | | | | | | | 1) 2ND REQUEST. THE MECHANICAL SHEET M-3.1 SHOWS THE | | ROOF TOP UNITS BEING ATTACHED TO THE ROOF TOP CURBS. | | PLEASE NOTE THAT RTU CURBS WERE REVIEWED AND INSPECTED | | UNDER PERMIT # 15100589. PLEASE NOTE THE WIND DESIGN | | FOR THE ANCHORING OF THE RTU UNIT TO CURB IS 150 MPH. | | PLEASE CORRECT THE WIND DESIGN AND CALCULATIONS FOR | | ANCHORING OF THE RTU TO CURB. THIS IS A 170 VULT MPH | | WIND ZONE FOR BUILDINGS WITH AN BUILDING RISK CATEGORY | | II. SEE 2014 FBC-B FIGURE 1609A. | | | | | | 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL | | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY | | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT | | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY | | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. | | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE | | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES | | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND | | LOADS? | | | | 2) NOTICE THE PARKING LOT STRIPPING WILL BE UNDER A | | AEPARATE PERMIT. THE SITE PLAN PARKING IS FOR SHOWING | | THE ACCESSIBLE EGRESS ROUTE FROM THE BUILDING. NO | | ACCTION NEED TO BE TAKEN. | | | | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | THE REVIEWS FOR THIS PROJECT ARE COMPLETE. TO VIEW | | COMMENTS FROM ALL DISCIPLINES: | | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT | | US.ASPX. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION | | DEVELOPMENT SERVICES DEPARTMENT | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2016-05-04 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2016-05-04 |
Time |
15:08 |
Rev Time |
|
Received By |
jwitmer |
Date |
2016-05-04 |
Time |
07:45 |
Sent To |
|
|
Notes |
2016-05-04 15:08:13 | BUILDING PLAN REVIEW | | W. P. B. PERMIT: 16040412 | | ADD: 1600 N DIXIE HWY. | | CONT: TBD/ TO BE DETERMINED | | TEL: (561)662-1927 | | E-MAIL:[email protected] | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | FLORIDA BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | DATE: WED. MAY 04/2016 | | ACTION: DENIED | | | | 1A) THE COVER SHEET INDICATES THE PLANS WERE DEVELOPED | | TO THE 2010 FBC CODE. STATEWIDE JUNE 30/2015 THE 2014 | | FBC-B/ 5TH EDITION WAS ADOPTED STATEWIDE. | | | | 1B) THE COVERSHEET THE INDEX IS MISSING (4) SHEETS THAT | | ARE IN THE PLAN SET. SHEET D-2.0, A-1.0, A-2.1 & A-7.1. | | | | 1C) THE COVERSHEET INDIATES THIS FACILITY CURRENTLY | | DOES NOT HAVE FIRE SPRINKLERS, THIS IS A CHANGE OF | | OCCUPANCY FROM A LOUNGE A2 TO A B OCCUPANCY/ AMBULATORY | | CARE FACILITY. | | 2014 EXIST. BLDG. CODE SECTION 1004 FIRE PROTECTION. | | 1004.1. FIRE PROTECTION REQUIREMENTS OF SECTION 1012 | | SHALL APPLY WHERE A BUILDING OR PORTIONS THEREOF | | UNDERGO A CHANGE OF OCCUPANCY CLASSIFICATION. | | | | 2014 EXISTING BLDG CODE. 1012.1.1 COMPLIANCE WITH | | CHAPTER 9. THE REQUIREMENTS OF CHAPTER 9 SHALL BE | | APPLICABLE THROUGHOUT THE BUILDING FOR THE NEW | | OCCUPANCY CLASSIFICATION BASED ON THE SEPARATION | | CONDITIONS SET FORTH IN SECTIONS 1012.1.1.1 AND | | 1012.1.1.2. | | | | 2014 EXISTING BLDG CODE. 1012.2.1 FIRE SPRINKLER | | SYSTEM. WHERE A CHANGE IN OCCUPANCY CLASSIFICATION | | OCCURS THAT REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM | | TO BE PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE | | WITH CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, | | SUCH SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE | | THE CHANGE OF OCCUPANCY OCCURS. | | | | 2014 FBC-B [F] 903.2.2 AMBULATORY CARE FACILITIES. AN | | AUTOMATIC SPRINKLER SYSTEM SHALL BE INSTALLED | | THROUGHOUT THE ENTIRE FLOOR CONTAINING AN AMBULATORY | | CARE FACILITY WHERE EITHER OF THE FOLLOWING CONDITIONS | | EXIST AT ANY TIME: | | | | 1. FOUR OR MORE CARE RECIPIENTS ARE INCAPABLE OF SELF | | PRESERVATION, WHETHER RENDERED INCAPABLE BY STAFF OR | | STAFF HAS ACCEPTED RESPONSIBILITY FOR CARE RECIPIENTS | | ALREADY INCAPABLE. | | | | 2. ONE OR MORE CARE RECIPIENTS THAT ARE INCAPABLE OF | | SELF-PRESERVATION ARE LOCATED AT OTHER THAN THE LEVEL | | OF EXIT DISCHARGE SERVING SUCH A FACILITY. | | | | 2) SHEET A-1.0 INDICATES THE PROPOSED SITE PLAN. THIS | | IS AN UNUSUAL BUILDING SINCE NONE OF THE TENANT SPACE | | (1600 N DIXIE) HAVE DOORWAYS THAT EXIT ONTO A PUBLIC | | RIGHT OF WAY. PLEASE PROVIDE A SITE PLAN SHOWING | | COMPLIANCE WITH: | | 2A) 2014 FBC-B 1027.5 ACCESS TO A PUBLIC WAY. THE EXIT | | DISCHARGE SHALL PROVIDE A DIRECT AND UNOBSTRUCTED | | ACCESS TO A PUBLIC WAY. | | 2B) 2014 FBC-ACCESSIBILITY CODE 206.2.4 SPACES AND | | ELEMENTS. AT LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT | | ACCESSIBLE BUILDING OR FACILITY ENTRANCES WITH ALL | | ACCESSIBLE SPACES AND ELEMENTS WITHIN THE BUILDING OR | | FACILITY WHICH ARE OTHERWISE CONNECTED BY A CIRCULATION | | PATH TO THE PUBLIC WAY, UNLESS EXEMPTED BY 206.2.3 | | EXCEPTIONS 1 THROUGH 7. | | 2C) 2014 FBC-ACCESSIBILITY 208.3.1 WHERE IN THE | | ACCESSIBLE PARKING SPACE AND ACCESS AISLE THE PATRON IS | | NOT COMPELLED TO WALK OR WHEEL BEHIND PARKED CARS. | | 3) SHEET LS-1.0A SHOWS (2) 1 HOUR FIRE SEPARATION WALLS | | LOCATED AT THE PROPERTY LINE. THERE ARE 2 LLC | | CORPORATIONS THAT OWN THE BUILDING AT 1600 N. DIXIE AND | | 1522 N. DIXIE. NO UNITY OF TITLE CAN OCCUR FOR THIS | | SITE WITH DIFFERENT OWNERS. THE ISSUE WITH THE DOORWAY | | BEING CUT INTO THE PROPERTY LINE WALL THESE ARE | | CONSIDERED AS BOTH BEING 1 HOUR FIRE RATED WALLS. SINCE | | THERE IS ONLY ONE COMMON WALL SEPARATING THE 2 | | PROPERTIES, THIS PORTION OF WALL WILL NEED TO BE | | CONSIDERED A PARTY WALL SEE 2014 FBC-B 706.1.1 & TABLE | | 706.4. ( 3 HOURS) & TABLE 716.5 OPENINGS IN FIRE WALLS | | ( 3 HOURS). | | 4) SHEET LS-1.0A DOES THE DOORS 30, 31 & ER HAVE AN | | ACCESSIBLE ENTRY/ EXIT , LEVEL WITH GRADE? 2014 | | FBC-ACCESS. CODE 206.2.4 SPACES AND ELEMENTS. AT LEAST | | ONE ACCESSIBLE ROUTE SHALL CONNECT ACCESSIBLE BUILDING | | OR FACILITY ENTRANCES WITH ALL ACCESSIBLE SPACES AND | | ELEMENTS WITHIN THE BUILDING OR FACILITY WHICH ARE | | OTHERWISE CONNECTED BY A CIRCULATION PATH UNLESS | | EXEMPTED BY 206.2.3 EXCEPTIONS 1 THROUGH 7. | | 5) SHEET LS-1A THE OCCUPANT LOADS OF BUSINESS 23.24, | | STORAGE 1.03 & CONFERENCE ROOM 52.86 OCCUPANTS. IN EACH | | CASE THE OCCUPANT LOAD IS ROUNDED DOWN. PLEASE NOTE YOU | | ALWAYS ROUND UP TO THE NEXT WHOLE NUMBER. FLORIDA | | BUILDING CODE INFORMAL INTERPRETATION REPORT # 5479. | | DATE: TUE DEC 18 2007 | | REPORT #: 5479 | | CODE: BUILDING | | SECTION: 1004.1.2 | | QUESTION: | | IS IT THE INTENT OF SECTION 1004.1.2 TO ALLOW THE | | LARGEST NUMBER COMPUTED IN ACCORDANCE WITH | | TABLE 1004.1.2 TO BE ROUNDED TO THE NEAREST WHOLE | | NUMBER? COMMENT: FOR EXAMPLE, A | | BUSINESS OCCUPANCY IN A BUILDING WITH 3215 GROSS SQUARE | | FEET, CALCULATED OCCUPANCY LOAD | | WOULD BE 32.15 WOULD I ROUND DOWN TO 32 OCCUPANTS OR | | WOULD I BE REQUIRED TO ROUND UP TO | | 33 OCCUPANTS | | ANSWER: | | ROUND UP TO 33 | | COMMENTARY: | | OCCUPANTS ONLY COME AS A WHOLE. | | | | 6) SHEET LS-1A SHOWS 1 HOUR RATED WALLS IN THE STORAGE | | ROOMS WITH THE WALL TYPE IDENTIFIED AS WALL TYPE F, A | | UL U-465 FIRE RATED WALL. PLEASE PROVIDE THE UL DETAIL | | FOR THE INSPECTOR WILL BE ABLE TO IDENTIFY THE VARIOUS | | COMPONENTS OF THE WALL ASSEMBLY. 2014 FBC-B 707.3 FIRE | | ?RESISTANCE RATINGS. 107.2.1.3 ADDITIONAL INFORMATION | | REQUIRED. | | | | 7) DOOR 31 & 32 ARE NEW EXTERIOR DOORS, WILL NEED TO | | COMPLY WITH: | | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) | | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT | | WILL REQUIRE PRODUCT APPROVALS: | | (31)(A) EXTERIOR DOORS. | | | | 8) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA | | RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY | | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | JURISDICTIONAL APPROVAL. | | | | 9) PLEASE PROVIDE THE PRESSURES BOTH POSITIVE AND | | NEGATIVE FOR THESE DOORS IN VASD. 2014 FBC-B 1603.1.4 | | WIND DESIGN DATA. | | | | 10) THE MECHANICAL SHEET M-3.1 SHOWS THE ROOF TOP UNITS | | BEING ATTACHED TO THE ROOF TOP CURBS. PLEASE NOTE THAT | | RTU CURBS WERE REVIEWED AND INSPECTED UNDER PERMIT # | | 15100589. PLEASE NOTE THE WIND DESIGN FOR THE ANCHORING | | OF THE RTU UNIT TO CURB IS 150 MPH. PLEASE CORRECT THE | | WIND DESIGN AND CALCULATIONS FOR ANCHORING OF THE RTU | | TO CURB. THIS IS A 170 VULT MPH WIND ZONE FOR BUILDINGS | | WITH AN BUILDING RISK CATEGORY II. SEE 2014 FBC-B | | FIGURE 1609A. | | | | | | 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL | | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY | | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT | | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY | | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. | | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE | | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES | | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND | | LOADS? | | | | 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES | | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | THE REVIEWS FOR THIS PROJECT ARE COMPLETE. TO VIEW | | COMMENTS FROM ALL DISCIPLINES: | | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT | | US.ASPX. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION | | DEVELOPMENT SERVICES DEPARTMENT | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2017-03-28 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2017-03-28 |
Time |
11:51 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2017-03-28 |
Time |
11:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2017-01-17 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2017-01-17 |
Time |
13:37 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2017-01-17 |
Time |
13:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2016-12-14 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-12-14 |
Time |
15:36 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-12-14 |
Time |
13:09 |
Sent To |
|
|
Notes |
2016-12-14 15:48:17 | JOB PERMIT NUMBER: 1640412 & 16040415 | | JOB ADDRESS: 1600 & 1522 N DIXIE HWY | | WEST PALM BEACH FLORIDA 33401 | | DATE: DECEMBER 14, 2016 | | ELECTRICAL PLAN REVIEW COMMENTS | | | | - THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC | | 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA | | BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH | | AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED. | | | | 1] BUILDING 1600 N DIXIE HIGHWAY RISER DIAGRAM REFLECTS | | THE EQUIPMENT GROUNDING CONDUCTOR FOR PANEL "DP" IN | | PARALLEL WHICH IS IN VIOLATION OF NEC 310.10(H) & | | 250.122(F). | | | | 2] BY MODIFICATIONS DONE TO THE ELECTRICAL SYSTEM, | | USING THE EXISTING AVAILABLE FAULT CURRENT PLEASE SHOW | | AIC CALCULATIONS TO VERIFY SHORT CIRCUIT RATING OF NEW | | ELECTRICAL EQUIPMENT. NEC 110.24, 110.10, 110.9. | | | | 3] IN ADDITION TO THE SERVICE PERMANENT PLAQUE REQUIRED | | BY NEC 230.2(E) PLEASE PROVIDE A SHUNT TRIP DEVICE AT | | EACH SERVICE LOCATION TO FACILITATE FIRST RESPONDERS, | | THE DEVICE SHALL BE INSTALLED AT A READILY ACCESSIBLE | | LOCATION PER NEC 230.70(A)(3). | | | | - PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE | | MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER | | RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER | | (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES | | WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER | | QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME | | DIRECTLY. | | | | 3RD REVIEW FBC 2014 5TH ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2016-08-04 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2016-08-04 |
Time |
10:26 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2016-08-04 |
Time |
09:36 |
Sent To |
|
|
Notes |
2016-08-04 10:28:34 | ELECTRICAL REVIEW NOTES | | REVIEWED FOR COMPLIANCE WITH: | | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) | | | | PROJECT NAME: FRESENIUS MEDICAL CARE ADDITION | | JOB ADDRESS: 1522 & 1600 N. DIXIE HWY. | | DESCRIPTION: RENOVATION OF EXISTING SPACE | | MASTER PERMIT:16040415 | | REVISION: (THIS PACKET IS RUNNING TOGETHER WITH PERMIT | | 16040412) | | | | THE BELOW MENTIONED COMMENTS WILL RELATE TO BOTH | | PERMITS AS THEY ARE SHARING A SUBMITTAL | | 1. THERE ARE TWO SEPARATE PERMITS AND THEREFORE THERE | | SHOULD BE TWO SEPARATE PLAN SETS. IF NOT AT A MINIMUM | | THREE SETS SO THAT ONE CAN BE STORED ON RECORD FOR EACH | | PERMIT NUMBER EVEN IF THEY WILL BE SHARING THE JOB | | COPY. AT PRESENT THERE IS ONLY ONE SET OF DRAWINGS | | ATTACHED TO EACH PERMIT AND THEY DO NOT MATCH. THE | | SHEET INDEX OF T1.0 FOR EACH SET MENTIONS 11 | | INDIVIDUALLY NUMBERED ELECTRICAL SHEETS. THE SET OF | | PERMIT 16040415 IS MISSING SHEET E2.0A AND SHEET E2.2 | | IS REPLACED W/SHEET E2.2A. THE SET OF PERMIT 16040412 | | DOES INCLUDE SHEET E2.0A BUT ALSO HAS A SHEET E2.2A | | RATHER THAN AN E2.2. CORRECT THAT ACCORDINGLY. | | 2. YOU DID NOT RESPOND TO MY COMMENT #3 WHICH ADDRESSES | | THE DAYLIGHT ZONE ISSUE. I INADVERTENTLY CALLED OUT | | SHEET E2.1 WHICH OBVIOUSLY DOES NOT INCLUDE THE | | LIGHTING. IT IS SHEET E2.0A THAT ADDRESSES THE LIGHTING | | AND NOTHING HAS BEEN DONE TO ADDRESS THE DAYLIGHT | | LIGHTING ZONE CONTROL. PLEASE CORRECT THAT ACCORDINGLY. | | 3. WITH REGARDS TO MY COMMENT #4, THE FACT THAT THESE | | TWO BUILDINGS ARE TO BE CONNECTED WILL POSE A LIFE | | SAFETY HAZARD BY HAVING TWO SERVICES. THEREFORE, RATHER | | THAN HAVING SHUNT TRIP CAPABILITIES YOU SHALL PLACE A | | WARNING PLACARD AT EACH SERVICE INFORMING EMERGENCY | | PERSONNEL OF THE OTHER SERVICE AND THE LOCATION OF THE | | DISCONNECT. | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER | | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER | | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE | | GREATLY APPRECIATED. | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | CONTACT ME DIRECTLY. | | | | THANK YOU, | | MIKE ALBARRAN | | ELECTRICAL PLANS EXAMINER | | PH: 561-805-6746 | | EMAIL: [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2016-04-13 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2016-04-13 |
Time |
17:07 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2016-04-13 |
Time |
11:04 |
Sent To |
|
|
Notes |
2016-04-13 18:52:32 | THIS PERMIT IS RIDING ALONG WITH16040415 AND ARE | | SHARING THE PLANS, THEREFORE THE COMMENTS ARE COMMON TO | | BOTH PERMIT. | | | | ELECTRICAL REVIEW COMMENTS | | REVIEWED FOR COMPLIANCE WITH: | | 5TH EDITION OF THE FBC 2014 & NFPA 70 (NEC) 2011 | | EDITION | | | | CORRECTIONS REQUIRED: | | BLDG. DEPT. NOTES ON COVER SHEET | | 1. A) INDICATE THAT THE PLANS WERE DESIGNED TO MEET THE | | REQUIREMENTS OF THE 2008 NEC. D) REFERS TO THE LATEST | | CODE. THE 2011 EDITION OF THE NEC IS THE ONE CURRENTLY | | ADOPTED BUT IT IS NOT THE LATEST EDITION. | | SHEET E2.0A | | 1. NOTE 14 AGAIN REFERS TO AN OLD CODE. THOUGH THE | | VERBIAGE OF THE OLD CODE DIDN'T VARY WITH THE NEW ONE | | THE REFERENCE IS INCORRECT. | | 2. FROM THIS DRAWING IT IS VERY DIFFICULT TO RECOGNIZE | | WHAT AND WHERE WOULD THE DAYLIGHT ZONE BE FOR | | COMPLIANCE WITH THE FBC-EC402 & 405 | | SHEET E2.1A | | 1. NEC 225.34 RESTRICTS THE NUMBER OF DISCONNECTS AND | | REQUIRES THAT THEY BE GROUPED. | | SHEET E2.1B | | 1. PANELS LA & LB DO NOT COMPLY WITH NEC 110.26 | | SHEET E2.2A | | 1. SEPARATE PERMIT AND SUBMITTAL REQUIRED FOR THE FIRE | | ALARM. | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER | | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER | | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE | | GREATLY APPRECIATED. | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | CONTACT ME DIRECTLY. | | | | THANK YOU, | | MIKE ALBARRAN | | ELECTRICAL PLANS EXAMINER | | PH: 561-805-6746 | | EMAIL: [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2017-04-04 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2017-04-04 |
Time |
10:38 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2017-04-04 |
Time |
10:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2016-08-08 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2016-08-08 |
Time |
11:32 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2016-08-08 |
Time |
11:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2016-04-11 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2016-04-11 |
Time |
14:44 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2016-04-11 |
Time |
14:31 |
Sent To |
|
|
Notes |
2016-04-11 14:43:55 | PERMIT #16040412 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | 1) UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF | | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE | | 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA | | AMENDMENTS. | | | | 2) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION | | SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND | | RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION | | SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A | | 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A | | FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED | | BY EMAIL ([email protected]) OR IN WRITING (FAX: | | 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE | | MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.? | | | | 3) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER | | SYSTEM AND/OR FIRE ALARM SYSTEM. | | | | SUE ELLEN CALDERON | | ASSISTANT FIRE MARSHAL | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 644-7326 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2017-05-08 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2017-05-08 |
Time |
15:19 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2017-03-24 |
Time |
15:09 |
Sent To |
|
|
Notes |
2017-03-27 15:10:04 | B29 | | *TRAVELLING WITH 16040415* |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2017-02-01 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-02-01 |
Time |
08:27 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-01-30 |
Time |
11:38 |
Sent To |
|
|
Notes |
2017-01-31 11:39:04 | RESUB ROUTED TO CCOLE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2017-01-23 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2017-01-23 |
Time |
15:03 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2016-12-28 |
Time |
09:38 |
Sent To |
|
|
Notes |
2017-01-23 15:40:18 | AWAITING ELECTRICAL REVIEW OF SISTER PERMIT 16040415 | 2016-12-30 09:38:31 | B29 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2016-12-14 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-12-14 |
Time |
15:49 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-11-21 |
Time |
13:31 |
Sent To |
|
|
Notes |
2016-11-22 13:32:10 | B29 **TRAVELLING WITH 16040415** |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2016-08-25 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2016-08-25 |
Time |
09:35 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2016-07-29 |
Time |
10:44 |
Sent To |
|
|
Notes |
2016-08-01 10:44:52 | B29 | | *TRAVELLING WITH 16040415** |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-05-24 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2016-05-24 |
Time |
14:59 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2016-04-07 |
Time |
08:59 |
Sent To |
|
|
Notes |
2016-04-08 08:59:43 | B29 TRAVELLING WITH 16040415 |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
N |
Date |
2016-05-04 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2016-05-04 |
Time |
15:08 |
Rev Time |
|
Received By |
jwitmer |
Date |
2016-05-04 |
Time |
07:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
P |
Date |
2017-02-01 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-02-01 |
Time |
08:27 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-02-01 |
Time |
07:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
F |
Date |
2017-01-05 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-01-05 |
Time |
10:47 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-01-05 |
Time |
10:47 |
Sent To |
|
|
Notes |
2017-01-05 10:57:35 | 4TH REVIEW FBC-2014 MECHANICAL | | PERMIT #16040412 | | 1/5/17 | | | | 1) THE ENERGYGAUGE COMPLIANCE FORM IS INDICATING 17 | | SEER FOR RTU'S 5-9, HOWEVER THE EQUIPMENT SCHEDULE ON | | THE PLANS LISTS THEM AT 13 SEER- PLEASE CORRECT. | | | | 2) PROVIDE COMPLIANCE DATA ON THE ENERGYGAUGE FORM FOR | | OAU-1. | | | | 2) AUTOMATIC SHUTOFF DAMPERS ARE REQUIRED FOR THE OAU | | DUCTS SUPPLYING THE RTU'S- SEE SECTION C403.2.4.4 | | FBC-14 ENERGY CONSERVATION. | | | | 3) PREVIOUS COMMENT #9 STILL EXISTS: PROVIDE A FIRE | | DAMPER FOR THE 8X6 O/A DUCT PENETRATING THE THE | | FIRE-RATED PD RECORDS WALL. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2016-12-02 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2016-12-02 |
Time |
10:15 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2016-12-02 |
Time |
07:56 |
Sent To |
|
|
Notes |
2016-12-02 10:48:56 | 3RD REVIEW FBC-2014 MECHANICAL | | PERMIT #16040415 | | 12/2/16 | | | | 1) SHEETS M-1 & M-2.1: IT APPEARS THAT THE RTU | | SCHEDULE, AND THE ENERGY AND AC CALCULATIONS ARE | | INDICATING NEW UNITS ARE BEING INSTALLED. PLEASE | | CORRECT THE MECHANICAL ROOF PLAN INDICATING EXISTING. | | | | 2) CLARIFY IF THE DUCT HEATERS ARE NEW OR EXISTING AND | | LABEL THEM ACCORDINGLY. IF NEW UNITS ARE BEING | | PROVIDED, PLEASE PROVIDE AN EQUIPMENT SCHEDULE. | | | | 3) M-1, FAN SCHEDULE: PROVIDE THE CONTROL SEQUENCE FOR | | EF-7. | | | | 4) M-1 & M-2.0A: THE EXHAUST CALCULATION IS SPECIFYING | | EXHAUST RATES BASED ON SECTION 502.8.1.1 FBC-14 | | MECHANICAL. PLEASE REVIEW AND SHOW COMPLIANCE WITH | | ITEMS #1-7 UNDER 502.8.1.1, AND ALSO REFER TO SECTION | | 510.8 FOR EXHAUST DUCT REQUIREMENTS AND SHOW DETAILS ON | | THE PLAN. | | | | 5) PLEASE REFER TO TABLE 7-1 ASHRAE 170- 2008 AND | | PROVIDE THE DESIGN PARAMETERS FOR THE SOILED UITILITY | | AND MEDICAL WASTE ROOMS. SHOW PRESSURE RELATIONSHIPS | | AND REQUIRED OUTDOOR AND TOTAL AIR CHANGES RO EACH | | ROOM. | | | | 6) PROVIDE AIR BALANCE CALCULATIONS THAT INCLUDE THE | | NEW EXHAUST VENTILATION SYSTEMS. | | | | 7) 2ND REQUEST FOR THE DEFINITION OF "HT" STORAGE ROOM | | AND WHAT MATERIALS ARE BEING STORED IN THE ROOM. AS | | PREVIOUSLY NOTED EXHAUST VENTILATION MAY BE REQUIRED | | AND RECIRCULATION IOF AIR PROHIBITED. | | | | 8) M2.0A: SHOW THE DUCT DROP AND DUCT PLAN FOR OAU-1. | | | | 9) M2.0A: THERE APPEARS TO BE A MISSING FIRE DAMPER | | WHERE THE 8X6 DUCT IS PENETRATING THE FIRE-RATED PD | | RECORDS ROOM WALL. | | | | 10 ) A RESPONSE NARRATIVE WAS NOT SUBMITTED WITH THE | | CORRECTED PLANS. PLEASE PROVIDE A RESPONSE NARRATIVE | | ADDRESSING THESE REVIEW COMMENTS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2016-08-04 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2016-08-04 |
Time |
13:56 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2016-08-04 |
Time |
13:56 |
Sent To |
|
|
Notes |
2016-08-04 14:44:28 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #16040412 | | 8/4/16 | | | | 1) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW: A) | | PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE SOILED | | UTILITY, MED WASTE, AND LAB ROOMS. B) PROVIDE AN | | EXHAUST SYSTEM IN THE LAB ROOM PER TABLE 403.3 AND | | ASHRAE 62.1-2010. PLEASE NOTE THAT RECIRCULATION OF AIR | | FROM THE SPACE IS PROHIBITED PER TABLE 403.3 FOOTNOTE G | | | | 2) DEFINE "HT" AS IT APPLIES TO THE HT STORAGE ROOM. | | INDICATE WHAT MATERIALS AND/OR EQUIPMENT ARE BEING | | STORED IN THE ROOM. PLEASE NOTE THAT EXHAUST | | VENTILATIONS MAY BE REQUIRED. | | | | 3) M-3.1: AS PREVIOUSLY REQUESTED PROVIDE COMPLETE | | ENGINEERED DETAILS FOR MOUNTING THE NEW RTU'S TO THE | | CURBS- SECTION 301.15. PLEASE INCLUDE THE WIND LOAD | | DESIGN CRITERIA FOR THE INSTALLATIONS AS OUTLINED IN | | SECTION 1609 FBC-14 BUILDING. CONTRARY TO THE RESPONSE | | NARRATIVE FROM JMM ENGINEERS, RTU'S 5, 6, 7, 8, &9 ARE | | NOT EXISTING AND WERE NEVER PERMITTED. BUILDING | | DEPARTMENT RECORDS INDICATE PERMIT #15070429 WAS ISSUED | | FOR INSTALLATION OF THE CURBS ONLY WITH CAPPING FOR | | FUTURE USE. WIND LOAD ENGINEERING IS ALSO REQUIRED | | INSTALLATION OF THE ROOFTOP FANS AND CURBS- EF-1, 2, 3, | | 4, 5, & 6. | | | | 4) SHEET M-2.1: AS PREVIOSULY REQUESTED, PROVIDE THE | | CLEARANCE DISTANCE MEASURERMENTS FROM THE EXHAUST FANS | | TO THE ROOF EDGES. ARE THERE PARAPETS THAT EXTEND AT | | LEAST 42" ABOVE THE FINISHED ROOF SURFACE? | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2016-04-14 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2016-04-14 |
Time |
13:57 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2016-04-14 |
Time |
13:57 |
Sent To |
|
|
Notes |
2016-04-14 13:57:23 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #16040412 | | 4/14/16 | | | | 1) SHEET M1.0: THE OUTSIDE AIR CALULATIONS ARE BASED ON | | THE OUTDATED FMC- 2010. THE CURRENT CODE IN EFFECT IS | | THE FBC- 2014 MECHANICAL: PLEASE REVIEW AND UPDATE. | | 2) M1.0: PLEASE INDICATE THE OFFICE OR ROOM NUMBERS IN | | THE OUTSIDE AIR SCHEDULE AND INCLUDE CALULATIONS FOR | | ALL ROOMS AND SPACES INCLUDING THE EXAMINATION AND | | MEDICAL PROCEDURE ROOMS- SEE TABLE 403.3. PLEASE NOTE | | THAT THE "WATER TREATMENT STORAGE" ROOMS LISTED IN THE | | CALCULATIONS DO NOT APPEAR TO BE IN THE SCOPE OF WORK | | FOR THIS PROJECT: PLEASE CLARIFY. | | 3) M1.0: PROVIDE EXHAUST VENTILATION CALCULATIONS FOR | | THE SOILED UTILITY, MED WASTE, AND LAB PREP ROOMS. | | PLEASE NOTE THAT NO EXHAUST HAS BEEN PROVIDED FOR THE | | LAB PREP ROOM- SEE TABLE 403.3 AND CLARIFY IF THERE IS | | LAB WORK OR CHEMICAL STORAGE IN THE THIS ROOM- SEE | | TABLE 6-4 ASHRAE 62.1-2010. | | 4) D1.0: PLEASE PROVIDE A SCOPE OF WORK FOR MECHANICAL | | DEMOLITION WITH CORREPONDING DRAWINGS AND DETAILS. | | 5) M-2.0A: THE 10" FLEX DUCTS SUPPLYING 405 CFMS EACH | | TO THE CONFERENCE ROOM ARE UNDERSIZED PER ACCA MANUAL D | | SIZING METHODS FOR LOW PRESSURE SYSTEMS. | | 6) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS | | OF ALL ROOF TOP EQUIPMENT- RTU'S, EXHAUST FANS, AIR | | INTAKES ETC- SEE SECTIONS 401.5 AND 501.3.1 FOR | | REQUIRED CLEARANCE DISTANCES AND PLACE MEASUREMENTS ON | | THE PLAN TO VERIFY COMPLIANCE. SUBMIT NOA'S OR FL. | | PRODUCT APPROVALS FOR THE ROOF TOP FANS, AND FAN AND | | RTU CURBS REVIEWED AND APPROVED WITH SIGNATURE BY THE | | EOR. PLEASE NOTE THAT GUARDS WILL BE REQUIRED FOR ALL | | SERVICEABLE EQUIPMENT ON THE ROOF WITHIN 10' OF A ROOF | | EDGE I.E. EF-6. | | 7) INDICATE THE USE OF EF-6 ON THE PLAN AND PROVIDE | | EXHAUST VENTILATION CALCULATIONS, MAKE-UP AIR, A | | VENTING DIAGRAM, AND MANUFACTURER'S SPECIFICATIONS FOR | | THE EXHAUST FAN AND DUCT WORK. | | 8) M-3.1: REFER TO SECTION 301.15 AND PROVIDE WIND LOAD | | DESIGN CRITERIA AND COMPLETE ENGINEERED DETAILS FOR TIE | | DOWN OF THE RTUS, FANS, AND CURBS TO THE ROOF | | STRUCTURE. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2017-04-04 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2017-04-04 |
Time |
15:39 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2017-04-04 |
Time |
13:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2016-04-29 |
|
|
Cont ID |
|
Sent By |
gearl |
Date |
2016-04-29 |
Time |
13:20 |
Rev Time |
0.00 |
Received By |
gearl |
Date |
2016-04-29 |
Time |
13:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
5 |
Status |
F |
Date |
2017-05-08 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2017-05-08 |
Time |
15:18 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2017-05-08 |
Time |
14:45 |
Sent To |
|
|
Notes |
2017-05-08 15:19:09 | FAILED | | | | PROVIDE WRITTEN RESPONSES TO THE COMMENTS. PLEASE NOTE | | THAT THE SUBMITTAL OF THE REQUIRED ITEMS MAY RESULT IN | | ADDITIONAL COMMENTS | | | | 1) REPEAT COMMENT: THE PERMIT PACKAGE INCLUDES A | | PROPOSED SITE PLAN THAT RECONFIGURES THE EXISTING | | PARKING LOT. THE PARKING LOT WORK REQUIRES PARKING LOT | | PERMIT, WHICH SHALL BE SUBMITTED, WITH PLANS, FOR TO | | THE BUILDING DEPARTMENT PRIOR TO ZONING APPROVAL OF | | THIS BUILDING PERMIT - NO PERMIT CURRENTLY SUBMITTED. | | | | 2) IN ACCORDANCE WITH THE PROVISOS APPROVED AS PART OF | | PERMIT NO. 15100589, THE CURBING AND STRIPING SHOWN ON | | THE ISSUED PARKING LOT PERMIT SHALL BE COMPLETED PRIOR | | TO THE FINAL (104) INSPECTION/CERTIFICATE OF COMPLETION | | OF THE VANILLA BOX PERMIT OR CERTIFICATE OF OCCUPANCY | | FOR THE SPACE, WHICHEVER FIRST OCCURS. | | | | 3) REPEAT COMMENT: THE VALUE OF THE CONSTRUCTION | | ($241,020) EXCEEDS 50% OF THE STRUCTURE'S VALUE | | ($339,394) ACCORDING TO THE P.B.C. PROPERTY APPRAISER'S | | OFFICE; THEREFORE, PURSUANT TO SECTION 94-441(C)(2) OF | | THE ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR), THE | | LANDSCAPE ON THE SITE SHALL BE IN COMPLIANCE WITH ALL | | APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF THE | | ZLDR. SINCE THE SITE DOES NOT CONFORM TO ARTICLE XIV, | | THEN PRIOR TO THE ZONING APPROVAL OF THIS PERMIT A | | SEPARATE LANDSCAPE PERMIT AND IRRIGATION PERMIT SHALL | | BE SUBMITTED SHOWING MATERIAL TO BRING THE SITE INTO | | CONFORMITY PRIOR TO THE ISSUANCE OF THIS PERMIT. THE | | LANDSCAPE WORK SHALL BE COMPLETED PRIOR TO A | | CERTIFICATE OF OCCUPANCY FOR THE BUILDING. NO LANDSCAPE | | PLAN HAS BEEN SUBMITTED. | | | | 4) STAFF SUGGESTS REVIEWING THE OPTION OF REMOVING THE | | POWER POLES AND BURYING THE UTILITY LINES AS THIS WILL | | IMPROVE THE AESTHETICS OF THE SITE. IT APPEARS EACH | | POLE ONLY SERVES ONE OF THE BUILDINGS. ANOTHER OPTION | | MAY BE TO CONSOLIDATE THE SERVICES ON ONE POLE. | | | | 5) THE BUILDING RENOVATION ITSELF COMPLIES WITH ZONING, | | BUT THIS PERMIT WILL NOT BE APPROVED UNTIL COMPLIANCE | | WITH ITEMS 1 AND 3. | | | | 6) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR: | | | | A. PARKING LOT | | B. LANDSCAPE | | C. IRRIGATION | | D. DUMPSTER ENCLOSURE | | E. AWNINGS | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
F |
Date |
2017-01-23 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2017-01-23 |
Time |
14:47 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2017-01-23 |
Time |
14:46 |
Sent To |
|
|
Notes |
2017-01-23 15:01:19 | FAILED | | | | PROVIDE WRITTEN RESPONSES TO THE COMMENTS. PLEASE NOTE | | THAT THE SUBMITTAL OF THE REQUIRED ITEMS MAY RESULT IN | | ADDITIONAL COMMENTS | | | | 1) REPEAT COMMENT: THE PERMIT PACKAGE INCLUDES A | | PROPOSED SITE PLAN THAT RECONFIGURES THE EXISTING | | PARKING LOT. THE PARKING LOT WORK REQUIRES PARKING LOT | | PERMIT, WHICH SHALL BE SUBMITTED, WITH PLANS, FOR TO | | THE BUILDING DEPARTMENT PRIOR TO ZONING APPROVAL OF | | THIS BUILDING PERMIT - NO PERMIT CURRENTLY SUBMITTED. | | | | 3) IN ACCORDANCE WITH THE PROVISOS APPROVED AS PART OF | | PERMIT NO. 15100589, THE CURBING AND STRIPING SHOWN ON | | THE ISSUED PARKING LOT PERMIT SHALL BE COMPLETED PRIOR | | TO THE FINAL (104) INSPECTION/CERTIFICATE OF COMPLETION | | OF THE VANILLA BOX PERMIT OR CERTIFICATE OF OCCUPANCY | | FOR THE SPACE, WHICHEVER FIRST OCCURS. | | | | 4) REPEAT COMMENT: THE VALUE OF THE CONSTRUCTION | | ($241,020) EXCEEDS 50% OF THE STRUCTURE'S VALUE | | ($339,394) ACCORDING TO THE P.B.C. PROPERTY APPRAISER'S | | OFFICE; THEREFORE, PURSUANT TO SECTION 94-441(C)(2) OF | | THE ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR), THE | | LANDSCAPE ON THE SITE SHALL BE IN COMPLIANCE WITH ALL | | APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF THE | | ZLDR. SINCE THE SITE DOES NOT CONFORM TO ARTICLE XIV, | | THEN PRIOR TO THE ZONING APPROVAL OF THIS PERMIT A | | SEPARATE LANDSCAPE PERMIT AND IRRIGATION PERMIT SHALL | | BE SUBMITTED SHOWING MATERIAL TO BRING THE SITE INTO | | CONFORMITY PRIOR TO THE ISSUANCE OF THIS PERMIT. THE | | LANDSCAPE WORK SHALL BE COMPLETED PRIOR TO A | | CERTIFICATE OF OCCUPANCY FOR THE BUILDING. NO LANDSCAPE | | PLAN HAS BEEN SUBMITTED. | | | | 5) STAFF SUGGESTS REVIEWING THE OPTION OF REMOVING THE | | POWER POLES AND BURYING THE UTILITY LINES AS THIS WILL | | IMPROVE THE AESTHETICS OF THE SITE. IT APPEARS EACH | | POLE ONLY SERVES ONE OF THE BUILDINGS. ANOTHER OPTION | | MAY BE TO CONSOLIDATE THE SERVICES ON ONE POLE. | | | | 6) THE BUILDING RENOVATION ITSELF COMPLIES WITH ZONING. | | | | 7) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR: | | | | A. PARKING LOT | | B. LANDSCAPE | | C. IRRIGATION | | D. DUMPSTER ENCLOSURE | | E. AWNINGS | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
F |
Date |
2016-12-14 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2016-12-14 |
Time |
11:37 |
Rev Time |
0.75 |
Received By |
eschneid |
Date |
2016-12-09 |
Time |
14:22 |
Sent To |
|
|
Notes |
2016-12-14 11:40:09 | FAILED | | | | PROVIDE WRITTEN RESPONSES TO THE COMMENTS. PLEASE NOTE | | THAT THE SUBMITTAL OF THE REQUIRED ITEMS MAY RESULT IN | | ADDITIONAL COMMENTS | | | | 1) REPEAT COMMENT: PROVIDE TWO COPIES OF A SURVEY, LESS | | THAN ONE YEAR OLD, WHICH SHOWS ALL IMPROVEMENTS AND | | EASEMENTS. A SURVEY WAS NOT PROVIDED FOR 1600 NORTH | | DIXIE. | | | | 2) REPEAT COMMENT: THE PERMIT PACKAGE INCLUDES A | | PROPOSED SITE PLAN THAT RECONFIGURES THE EXISTING | | PARKING LOT. THE PARKING LOT WORK REQUIRES PARKING LOT | | PERMIT, WHICH SHALL BE SUBMITTED, WITH PLANS, FOR TO | | THE BUILDING DEPARTMENT PRIOR TO ZONING APPROVAL OF | | THIS BUILDING PERMIT - NO PERMIT CURRENTLY SUBMITTED. | | | | 3) IN ACCORDANCE WITH THE PROVISOS APPROVED AS PART OF | | PERMIT NO. 15100589, THE CURBING AND STRIPING SHOWN ON | | THE ISSUED PARKING LOT PERMIT SHALL BE COMPLETED PRIOR | | TO THE FINAL (104) INSPECTION/CERTIFICATE OF COMPLETION | | OF THE VANILLA BOX PERMIT OR CERTIFICATE OF OCCUPANCY | | FOR THE SPACE, WHICHEVER FIRST OCCURS. | | | | 4) REPEAT COMMENT: THE VALUE OF THE CONSTRUCTION | | ($241,020) EXCEEDS 50% OF THE STRUCTURE'S VALUE | | ($339,394) ACCORDING TO THE P.B.C. PROPERTY APPRAISER'S | | OFFICE; THEREFORE, PURSUANT TO SECTION 94-441(C)(2) OF | | THE ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR), THE | | LANDSCAPE ON THE SITE SHALL BE IN COMPLIANCE WITH ALL | | APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF THE | | ZLDR. SINCE THE SITE DOES NOT CONFORM TO ARTICLE XIV, | | THEN PRIOR TO THE ZONING APPROVAL OF THIS PERMIT A | | SEPARATE LANDSCAPE PERMIT AND IRRIGATION PERMIT SHALL | | BE SUBMITTED SHOWING MATERIAL TO BRING THE SITE INTO | | CONFORMITY. THE LANDSCAPE WORK SHALL BE COMPLETED PRIOR | | TO A CERTIFICATE OF OCCUPANCY FOR THE BUILDING. NO | | LANDSCAPE PLAN HAS BEEN SUBMITTED. | | | | 5) STAFF SUGGESTS REVIEWING THE OPTION OF REMOVING THE | | POWER POLES AND BURYING THE UTILITY LINES AS THIS WILL | | IMPROVE THE AESTHETICS OF THE SITE. IT APPEARS EACH | | POLE ONLY SERVES ONE OF THE BUILDINGS. ANOTHER OPTION | | MAY BE TO CONSOLIDATE THE SERVICES ON ONE POLE. | | | | 6) THE BUILDING RENOVATION ITSELF COMPLIES WITH ZONING. | | | | 7) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR: | | | | A. PARKING LOT | | B. LANDSCAPE | | C. IRRIGATION | | D. DUMPSTER ENCLOSURE | | E. AWNINGS | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2016-08-25 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2016-08-25 |
Time |
09:34 |
Rev Time |
0.75 |
Received By |
eschneid |
Date |
2016-08-25 |
Time |
09:04 |
Sent To |
|
|
Notes |
2016-08-25 09:37:03 | FAILED | | | | PROVIDE WRITTEN RESPONSES TO THE COMMENTS. PLEASE NOTE | | THAT THE SUBMITTAL OF THE REQUIRED ITEMS MAY RESULT IN | | ADDITIONAL COMMENTS | | | | 1) REPEAT COMMENT: PROVIDE TWO COPIES OF A SURVEY, LESS | | THAN ONE YEAR OLD, WHICH SHOWS ALL IMPROVEMENTS AND | | EASEMENTS. A SURVEY WAS NOT PROVIDED FOR 1600 NORTH | | DIXIE. | | | | 2) REVISED COMMENT: THE CONNECTION BETWEEN THE TWO | | BUILDINGS EXTENDS INTO THE REQUIRED FIVE (5) FOOT SIDE | | SETBACK, WHICH IS NOT PERMITTED. IN ORDER TO CONNECT | | THE TWO BUILDINGS, A RECORDED UNITY OF TITLE IS | | REQUIRED TO REMOVE THE PROPERTY LINE AND THUS THE | | REQUIRED SETBACK ALONG WHAT IS CURRENTLY THE SHARED | | PROPERTY LINE. YOU WILL NEED TO PROVIDE A RECORDED COPY | | OF THE COMPLETED UNITY OF TITLE PRIOR TO ZONING | | APPROVAL OF THIS PERMIT. | | | | 3) REVISED COMMENT: THE PERMIT PACKAGE INCLUDES A | | PROPOSED SITE PLAN THAT RECONFIGURES THE EXISTING | | PARKING LOT. THE PARKING LOT WORK REQUIRES PARKING LOT | | PERMIT, WHICH SHALL BE SUBMITTED, WITH PLANS, FOR TO | | THE BUILDING DEPARTMENT PRIOR TO ZONING APPROVAL OF | | THIS BUILDING PERMIT - NO PERMIT CURRENTLY SUBMITTED. | | NOTE: THE PROPOSED PARKING LOT SHOWS ONE LESS PARKING | | SPACE THAN THE APPROVED PLAN FOR THE BUILDING. SINCE | | THE APPROVED PARKING IS DEFICIENT FOR A MEDICAL OFFICE | | BUILDING, NO ADDITIONAL PARKING REDUCTIONS ARE | | PERMITTED. | | | | 4) IN ACCORDANCE WITH THE PROVISOS APPROVED AS PART OF | | PERMIT NO. 15100589, THE CURBING AND STRIPING SHOWN ON | | THE ISSUED PARKING LOT PERMIT SHALL BE COMPLETED PRIOR | | TO THE FINAL (104) INSPECTION/CERTIFICATE OF COMPLETION | | OF THE VANILLA BOX PERMIT OR CERTIFICATE OF OCCUPANCY | | FOR THE SPACE, WHICHEVER FIRST OCCURS. | | | | 5) REPEAT COMMENT: THE VALUE OF THE CONSTRUCTION | | ($241,020) EXCEEDS 50% OF THE STRUCTURE'S VALUE | | ($339,394) ACCORDING TO THE P.B.C. PROPERTY APPRAISER'S | | OFFICE; THEREFORE, PURSUANT TO SECTION 94-441(C)(2) OF | | THE ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR), THE | | LANDSCAPE ON THE SITE SHALL BE IN COMPLIANCE WITH ALL | | APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF THE | | ZLDR. SINCE THE SITE DOES NOT CONFORM TO ARTICLE XIV, | | THEN PRIOR TO THE ZONING APPROVAL OF THIS PERMIT A | | SEPARATE LANDSCAPE PERMIT AND IRRIGATION PERMIT SHALL | | BE SUBMITTED SHOWING MATERIAL TO BRING THE SITE INTO | | CONFORMITY. THE LANDSCAPE WORK SHALL BE COMPLETED PRIOR | | TO A CERTIFICATE OF OCCUPANCY FOR THE BUILDING. NO | | LANDSCAPE PLAN HAS BEEN SUBMITTED. | | | | 6) STAFF SUGGESTS REVIEWING THE OPTION OF REMOVING THE | | POWER POLES AND BURYING THE UTILITY LINES AS THIS WILL | | IMPROVE THE AESTHETICS OF THE SITE. IT APPEARS EACH | | POLE ONLY SERVES ONE OF THE BUILDINGS. ANOTHER OPTION | | MAY BE TO CONSOLIDATE THE SERVICES ON ONE POLE. | | | | 7) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR: | | | | A. PARKING LOT | | B. LANDSCAPE | | C. IRRIGATION | | D. DUMPSTER ENCLOSURE | | E. AWNINGS | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2016-05-24 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2016-05-24 |
Time |
13:28 |
Rev Time |
0.50 |
Received By |
eschneid |
Date |
2016-05-24 |
Time |
13:28 |
Sent To |
|
|
Notes |
2016-05-24 14:58:22 | FAILED | | | | 1) PROVIDE WRITTEN RESPONSES TO THE COMMENTS. PLEASE | | NOTE THAT THE SUBMITTAL OF THE REQUIRED ITEMS MAY | | RESULT IN ADDITIONAL COMMENTS | | | | 2) PROVIDE TWO COPIES OF A SURVEY, LESS THAN ONE YEAR | | OLD, WHICH SHOWS ALL IMPROVEMENTS AND EASEMENTS. | | | | 3) THE CONNECTION BETWEEN THE TWO BUILDINGS EXTENDS | | INTO THE REQUIRED FIVE (5) FOOT SIDE SETBACK, WHICH IS | | NOT PERMITTED. IN ORDER TO CONNECT THE TWO BUILDINGS, A | | RECORDED UNITY OF TITLE IS REQUIRED TO REMOVE THE | | REQUIRED SETBACK ALONG WHAT IS CURRENTLY THE SHARED | | PROPERTY LINE. PLEASE CONTACT VINCE NOEL, CITY | | SURVEYOR, AT (561) 494-1096 TO BEGIN THE CITY'S UNITY | | OF TITLE APPLICATION PROCESS. | | | | 4) THE PERMIT PACKAGE INCLUDES A PROPOSED SITE PLAN | | THAT RECONFIGURES THE EXISTING PARKING LOT AND JOINS IT | | WITH THE PARKING LOT TO THE SOUTH. IN ORDER TO VERIFY | | THAT THE NEW ENLARGED PARKING LOT HAS SUFFICIENT | | PARKING TO ACCOMMODATE BOTH THIS BUILDING AND THE | | BUILDING TO THE NORTH, A PARKING LOT PERMIT, WITH | | PLANS, SHALL BE SUBMITTED FOR REVIEW PRIOR TO STAFF?S | | APPROVAL OF THIS BUILDING PERMIT. NOTE: THE PROPOSED | | PARKING SPACES, REGULAR AND ADA, LOCATED ALONG THE EAST | | SIDE OF THE BUILDING WILL NOT FUNCTION AS SHOWN DUE TO | | THE DOORWAYS THAT ARE SHOWN ON THE PROPOSED FLOOR PLAN. | | | | 5) IN ACCORDANCE WITH THE PROVISOS APPROVED AS PART OF | | PERMIT NO. 15100589, THE CURBING AND STRIPING SHOWN ON | | THE ISSUED PARKING LOT PERMIT SHALL BE COMPLETED PRIOR | | TO THE FINAL (104) INSPECTION/CERTIFICATE OF COMPLETION | | OF THE VANILLA BOX PERMIT OR CERTIFICATE OF OCCUPANCY | | FOR THE SPACE, WHICHEVER FIRST OCCURS. | | | | 6) THE VALUE OF THE CONSTRUCTION ($241,020) EXCEEDS 50% | | OF THE STRUCTURE'S VALUE ($339,394) ACCORDING TO THE | | P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT | | TO SECTION 94-441(C)(2) OF THE ZONING AND LAND | | DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE | | SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE | | REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. SINCE THE | | SITE DOES NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE | | ZONING APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE | | PERMIT AND IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING | | MATERIAL TO BRING THE SITE INTO CONFORMITY. THE | | LANDSCAPE WORK SHALL BE COMPLETED PRIOR TO A | | CERTIFICATE OF OCCUPANCY FOR THE BUILDING. | | | | 7) STAFF SUGGESTS REVIEWING THE OPTION OF REMOVING THE | | POWER POLES AND BURYING THE UTILITY LINES AS THIS WILL | | IMPROVE THE AESTHETICS OF THE SITE. IT APPEARS EACH | | POLE ONLY SERVES ONE OF THE BUILDINGS. ANOTHER OPTION | | MAY BE TO CONSOLIDATE THE SERVICES ON ONE POLE. | | | | 8) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR: | | | | A. PARKING LOT | | B. LANDSCAPE | | C. IRRIGATION | | D. DUMPSTER ENCLOSURE | | E. AWNINGS | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | |
|
|
|
Account Summary | Usage Policy | Privacy Policy