Plan Review Details - Permit 16040383
Plan Review Stops For Permit 16040383
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-05-17 Cont ID  
Sent By jwitmer Date 2016-05-17 Time 17:29 Rev Time 0.00
Received By jwitmer Date 2016-05-17 Time 16:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-04-18 Cont ID  
Sent By jwitmer Date 2016-04-18 Time 06:36 Rev Time 0.00
Received By jwitmer Date 2016-04-18 Time 05:57 Sent To  
Notes
2016-04-18 06:36:51BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16040383
 ADD: 777 S. FLAGLER DR. FLOORS 4TH & 5TH FLOORS.
 CONT: TBD
 TEL: 561-251-3865
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. APRIL 18/ 2016
 ACTION: DENIED
  
 1) THE LOCATION OF THE PROJECT, THERE SEEMS TO BE A
 DISCREPANCY AS TO WHERE THE LOCATION OF THE PROJECT.
 THE PERMIT APPLICATION UNDER THE DESCRIPTION OF WORK
 LIST 777 S. FLAGLER DR. 3RD & 4TH FLOORS WHERE AS THE
 PLAN TITLE BLOCK INDICATES THE PROJECT LOCATED AT 777
 S. FLAGLER THE 4TH & 5TH FLOORS?????
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION ADDITIONAL INFORMATION IS REQUIRED,
 DISCREPANCY.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
  
 2) SHEET A4.01 INDICATES NEW CARPET (CP-1) IN THE EXIT
 ACCESS CORRIDOR AND NEW CARPET (CP-2) ON THE CONVENIECE
 STAIRS BETWEEN FLOORS. PLEASE PROVIDE COMPLIANCE WITH
 2014 FBC-B SECTIONS:
  
 804.4.2 MINIMUM CRITICAL RADIANT FLUX.
 IN ALL OCCUPANCIES, INTERIOR FLOOR FINISH AND FLOOR
 COVERING MATERIALS IN ENCLOSURES FOR STAIRWAYS AND
 RAMPS, EXIT PASSAGEWAYS, CORRIDORS AND ROOMS OR SPACES
 NOT SEPARATED FROM CORRIDORS BY PARTITIONS EXTENDING
 FROM THE FLOOR TO THE UNDERSIDE OF THE CEILING SHALL
 WITHSTAND A MINIMUM CRITICAL RADIANT FLUX. THE MINIMUM
 CRITICAL RADIANT FLUX SHALL NOT BE LESS THAN CLASS I IN
 GROUPS I-1, I-2 AND I-3 AND NOT LESS THAN CLASS II IN
 GROUPS A, B, E, H, I- 4, M, R-1, R-2 AND S.
  
 EXCEPTION: WHERE A BUILDING IS EQUIPPED THROUGHOUT WITH
 AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 SECTION 903.3.1.1 OR 903.3.1.2, CLASS II MATERIALS ARE
 PERMITTED IN ANY AREA WHERE CLASS I MATERIALS ARE
 REQUIRED, AND MATERIALS COMPLYING WITH DOC FF-1 ?PILL
 TEST? (CPSC 16 CFR PART 1630) OR WITH ASTM D 2859 ARE
 PERMITTED IN ANY AREA WHERE CLASS II MATERIALS ARE
 REQUIRED.
  
 3) SHEET A5.01 THE FURNITURE PLAN SHOWS A COURTROOM AND
 CONFERENCE ROOMS, PLEASE SHOW COMPLIANCE WITH 2014
 FBC-ACCESSIBILTY CODE 902.3 HEIGHT. THE TOPS OF WORK
 SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34
 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 4) THE CONTRACTOR TO PROVIDE A COPY OF THE CONTRACT
 BEFORE PERMIT ISSUANCE. THE CONTRACTOR IS TO ALSO LIST
 THE VALUE OF THE SUB-CONTRACTORS WORK, EVEN IF THEY
 COME IN UNDER A SEPERATE PERMIT, SUB-PERMITS ARE A
 $80.00 ADMINISTRATIVE FEE IF NOT SUBMITTED THE SAME
 TIME AS THE PRIME PERMIT. THE VALUE OF WORK APPEARS TO
 BE LOW.
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-04-15 Cont ID  
Sent By vperez Date 2016-04-15 Time 12:27 Rev Time 0.00
Received By vperez Date 2016-04-15 Time 11:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-04-12 Cont ID  
Sent By pleduc Date 2016-04-12 Time   Rev Time 0.00
Received By pleduc Date 2016-04-11 Time 16:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-17 Cont ID  
Sent By jwitmer Date 2016-05-17 Time 17:29 Rev Time 0.00
Received By jwitmer Date 2016-05-16 Time 15:57 Sent To  
Notes
2016-05-16 15:57:27RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-18 Cont ID  
Sent By jwitmer Date 2016-04-18 Time 06:37 Rev Time 0.00
Received By jwitmer Date 2016-04-07 Time 08:34 Sent To  
Notes
2016-04-08 08:34:36C10

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-05-17 Cont ID  
Sent By ccole Date 2016-05-17 Time 11:10 Rev Time 0.00
Received By ccole Date 2016-05-17 Time 11:10 Sent To  
Notes
2016-05-17 11:18:52MECHANICAL PROVISO:
  
 SEPARATE PERMIT REQUIRED FOR HVAC WORK ON THE 4TH
 FLOOR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-04-13 Cont ID  
Sent By ccole Date 2016-04-13 Time 15:31 Rev Time 0.00
Received By ccole Date 2016-04-13 Time 15:31 Sent To  
Notes
2016-04-13 15:41:011ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16040383
 4/13/16
  
 1) SHEET M2.1: THE PLAN IS MISLABELED AS "DEMO FLOOR
 PLAN": PLEASE CORRECT.
 2) PROVIDE 4TH FLOOR MECHANICAL DEMOLITION AND
 CONSTRUCTION PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  