2016-06-29 19:01:03 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE FLORIDA LICENSED ENGINEER IS REQUIRED TO SIGN BY | | HAND HIS HANDWRITTEN SIGNATURE (FACSIMILES ARE NOT | | ACCEPTABLE) ON THE PLANS AND OTHER CONSTRUCTION | | DOCUMENTS. FAC 61G15-23.002 DIGITAL SIGNATURES ARE ONLY | | ACCEPTABLE ON ELECTRONICALLY SUBMITTED DOCUMENTS. | | FAC61G15-23.003 | | | | 2) PROVIDE DOCUMENTATION FROM THE MANUFACTURED BUILDING | | DESIGNER OF RECORD TO SHOW THAT THE BUILDING CAN SAFELY | | SUPPORT ALL ADDITIONAL LOADING THAT MAY BE CREATED BY | | INSTALLATION OF THIS PHOTOVOLTAIC SYSTEM AND SOLAR | | WATER HEATER COLLECTOR ON THE ROOF. FBC-R 301.1 SUBMIT | | A SIGNED AND SEALED LETTER FROM THE ENGINEER CERTIFYING | | THAT HE HAS REVIEWED THE STRUCTURE AND FOUND IT TO BE | | STRUCTURALLY CAPABLE OF SAFELY SUPPORTING ALL | | ADDITIONAL LOADING THAT WILL BE CREATED BY INSTALLATION | | OF THIS PHOTOVOLTAIC SYSTEM AND SOLAR WATER HEATER | | COLLECTOR ON THE ROOF. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2016-04-08 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-04-08 |
Time |
11:31 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-04-07 |
Time |
18:42 |
Sent To |
Z |
|
Notes |
2016-04-08 11:06:59 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THERE ARE NOT ANY REFERENCES OR DRAWINGS ON THE | | APPROVED PLANS THAT SHOW THE PHOTOVOLTAIC OR SOLAR | | WATER HEATER COLLECTOR ON THE ROOF OF THE MANUFACTURED | | BUILDING. THIS A SEPARATE PERMIT WITH AN APPLICATION | | DATE THAT PLACES IT UNDER THE 2014 FLORIDA BUILDING | | CODE RESIDENTIAL. THE APPLICABLE CODES ARE THE 2014 | | FBC-R AND THE 2011 NEC. PLEASE REVISE THE PLANS | | ACCORDINGLY. | | | | 2) THERE IS A SOLAR WATER HEATER COLLECTOR SHOWN ON | | SHEET S-1 OF THE DRAWINGS, HOWEVER, NO OTHER | | INFORMATION WAS PROVIDED. IF THIS IS TO BE INSTALLED, A | | SEPARATE PERMIT, APPLICATION AND REVIEWS ARE REQUIRED. | | | | 3) PROVIDE DOCUMENTATION FROM THE MANUFACTURED BUILDING | | DESIGNER OF RECORD TO SHOW THAT THE BUILDING CAN SAFELY | | SUPPORT ALL ADDITIONAL LOADING THAT MAY BE CREATED BY | | INSTALLATION OF THIS PHOTOVOLTAIC SYSTEM AND SOLAR | | WATER HEATER COLLECTOR ON THE ROOF. FBC-R 301.1 | | | | 4) THE STRUCTURAL MOUNTING DETAILS THAT WERE SUBMITTED | | ON SHEET S-2 ARE FOR A DIFFERENT TYPE OF ROOF | | CONSTRUCTION THAN THE ONE THAT WAS PERMITTED. THE | | APPROVED PLANS SHOW A 60 MIL TPO MEMBRANE ROOF COVERING | | OVER 1/4" TAPERED ISO OVER ZIP BOARD ROOF SHEATHING | | ATTACHED TO 22 GA. STEEL 1-1/2" CORRUGATED B DECK ON 8" | | X 2" 16 GA. STEEL JOISTS SPACED 24" O.C. THE | | CALCULATIONS AND DETAILS THAT WERE SUBMITTED ARE FOR | | ATTACHMENT TO WOOD TRUSSES USING LAG SCREWS. PLEASE | | CORRECT. FBC 107.2.1 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2016-08-01 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-08-01 |
Time |
09:12 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-08-01 |
Time |
09:12 |
Sent To |
|
|
Notes |
2016-08-01 09:13:05 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | PASSED WITH THE FOLLOWING PROVISO : | | | | - PER FAC RULE 61G4-15.021, A SEPERATE ELECTRICAL | | PERMIT BY A LICENSED ELECTRICAL CONTRACTOR IS REQUIRED | | FOR THE CONNECTION TO THE PREMISES INTERGAL WIRING OR | | UTILITY SERVICE. | | THE CVC CONTRACTOR IS LIMITED TO THE PV SUPPLY SIDE OF | | THE POWER CONDITIONING UNIT, PV SOURCE CIRCUITS, PV | | OUTPUT CIRCUITS, AND BATTERY STORAGE SYSTEM CIRCUITS. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2016-06-23 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-06-23 |
Time |
17:15 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-06-23 |
Time |
17:15 |
Sent To |
|
|
Notes |
2016-06-23 17:16:31 | ELECTRICAL SUB PERMIT REQUIRED. ROUTED TO ROBERT | | MCDOUGAL |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2016-04-07 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-04-07 |
Time |
09:53 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-04-07 |
Time |
09:53 |
Sent To |
|
|
Notes |
2016-04-07 10:24:16 | JOB PERMIT NUMBER: 16040300 | | JOB ADDRESS: 201 SANTA LUCIA DR | | WEST PALM BEACH FLORIDA | | DATE: APRIL 7, 2016 | | ELECTRICAL PLAN REVIEW COMMENTS | | | | | | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION | | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF | | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, | | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST | | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF | | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. | | | | - THE SCOPE OF WORK ACCORDING TO FLORIDA STATUE | | 61G4-15.021 LIMITS THE CVC CONTRACTOR TO THE PV SUPPLY | | SIDE , THEREFORE ANY CONNECTION TO THE ELECTRICAL | | BUILDING PREMISES MUST BE DONE BY A LICENSED ELECTRICAL | | CONTRACTOR. | | - PLANS ARE MISSING LABELS AND MARKINGS | | 1 NEC 690.5 C GROUND FAULT PROTECTION | | 2 NEC 690.14 C 2 PERMANENTLY MARK DISCONNECT | | 3 NEC 690.31 E 3 IDENTIFY PV SOURCE CONDUCTORS | | 4 NEC 705.12 7 DO NOT RELOCATE SOURCE DISCONNECT | | - SITE CURRENT CODE STANDARDS NEC 2011 AND FBC 2014 | | | | | | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE | | MENTIONED DEFICIENCIES. | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE | | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE | | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD | | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE | | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT | | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE | | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. | | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | CONTACT ME DIRECTLY. | | | | FBC 2014 5TH ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 516-805-6713 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2016-06-29 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-06-29 |
Time |
19:01 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-06-17 |
Time |
12:49 |
Sent To |
|
|
Notes |
2016-06-20 12:53:20 | RESUB ROUTED TO AJONES VIA ZONING INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-04-12 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2016-04-12 |
Time |
17:12 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2016-04-05 |
Time |
10:28 |
Sent To |
|
|
Notes |
2016-04-06 09:02:46 | ELECTRICAL INBOX |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2016-06-21 |
|
|
Cont ID |
|
Sent By |
njwira |
Date |
2016-06-21 |
Time |
15:32 |
Rev Time |
0.00 |
Received By |
njwira |
Date |
2016-06-21 |
Time |
15:32 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2016-04-12 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2016-04-12 |
Time |
16:05 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2016-04-12 |
Time |
16:05 |
Sent To |
|
|
Notes |
|
|