Plan Review Details - Permit 16040300
Plan Review Stops For Permit 16040300
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-07-29 Cont ID  
Sent By rmcdouga Date 2016-07-29 Time 19:05 Rev Time 0.00
Received By rmcdouga Date 2016-07-29 Time 19:05 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-06-29 Cont ID  
Sent By rmcdouga Date 2016-06-29 Time 19:01 Rev Time 0.00
Received By rmcdouga Date 2016-06-29 Time 18:34 Sent To  
Notes
2016-06-29 19:01:03PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE FLORIDA LICENSED ENGINEER IS REQUIRED TO SIGN BY
 HAND HIS HANDWRITTEN SIGNATURE (FACSIMILES ARE NOT
 ACCEPTABLE) ON THE PLANS AND OTHER CONSTRUCTION
 DOCUMENTS. FAC 61G15-23.002 DIGITAL SIGNATURES ARE ONLY
 ACCEPTABLE ON ELECTRONICALLY SUBMITTED DOCUMENTS.
 FAC61G15-23.003
  
 2) PROVIDE DOCUMENTATION FROM THE MANUFACTURED BUILDING
 DESIGNER OF RECORD TO SHOW THAT THE BUILDING CAN SAFELY
 SUPPORT ALL ADDITIONAL LOADING THAT MAY BE CREATED BY
 INSTALLATION OF THIS PHOTOVOLTAIC SYSTEM AND SOLAR
 WATER HEATER COLLECTOR ON THE ROOF. FBC-R 301.1 SUBMIT
 A SIGNED AND SEALED LETTER FROM THE ENGINEER CERTIFYING
 THAT HE HAS REVIEWED THE STRUCTURE AND FOUND IT TO BE
 STRUCTURALLY CAPABLE OF SAFELY SUPPORTING ALL
 ADDITIONAL LOADING THAT WILL BE CREATED BY INSTALLATION
 OF THIS PHOTOVOLTAIC SYSTEM AND SOLAR WATER HEATER
 COLLECTOR ON THE ROOF.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-04-08 Cont ID  
Sent By rmcdouga Date 2016-04-08 Time 11:31 Rev Time 0.00
Received By rmcdouga Date 2016-04-07 Time 18:42 Sent To Z
Notes
2016-04-08 11:06:59PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THERE ARE NOT ANY REFERENCES OR DRAWINGS ON THE
 APPROVED PLANS THAT SHOW THE PHOTOVOLTAIC OR SOLAR
 WATER HEATER COLLECTOR ON THE ROOF OF THE MANUFACTURED
 BUILDING. THIS A SEPARATE PERMIT WITH AN APPLICATION
 DATE THAT PLACES IT UNDER THE 2014 FLORIDA BUILDING
 CODE RESIDENTIAL. THE APPLICABLE CODES ARE THE 2014
 FBC-R AND THE 2011 NEC. PLEASE REVISE THE PLANS
 ACCORDINGLY.
  
 2) THERE IS A SOLAR WATER HEATER COLLECTOR SHOWN ON
 SHEET S-1 OF THE DRAWINGS, HOWEVER, NO OTHER
 INFORMATION WAS PROVIDED. IF THIS IS TO BE INSTALLED, A
 SEPARATE PERMIT, APPLICATION AND REVIEWS ARE REQUIRED.
  
 3) PROVIDE DOCUMENTATION FROM THE MANUFACTURED BUILDING
 DESIGNER OF RECORD TO SHOW THAT THE BUILDING CAN SAFELY
 SUPPORT ALL ADDITIONAL LOADING THAT MAY BE CREATED BY
 INSTALLATION OF THIS PHOTOVOLTAIC SYSTEM AND SOLAR
 WATER HEATER COLLECTOR ON THE ROOF. FBC-R 301.1
  
 4) THE STRUCTURAL MOUNTING DETAILS THAT WERE SUBMITTED
 ON SHEET S-2 ARE FOR A DIFFERENT TYPE OF ROOF
 CONSTRUCTION THAN THE ONE THAT WAS PERMITTED. THE
 APPROVED PLANS SHOW A 60 MIL TPO MEMBRANE ROOF COVERING
 OVER 1/4" TAPERED ISO OVER ZIP BOARD ROOF SHEATHING
 ATTACHED TO 22 GA. STEEL 1-1/2" CORRUGATED B DECK ON 8"
 X 2" 16 GA. STEEL JOISTS SPACED 24" O.C. THE
 CALCULATIONS AND DETAILS THAT WERE SUBMITTED ARE FOR
 ATTACHMENT TO WOOD TRUSSES USING LAG SCREWS. PLEASE
 CORRECT. FBC 107.2.1

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-08-01 Cont ID  
Sent By mvaldes Date 2016-08-01 Time 09:12 Rev Time 0.00
Received By mvaldes Date 2016-08-01 Time 09:12 Sent To  
Notes
2016-08-01 09:13:05REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 PASSED WITH THE FOLLOWING PROVISO :
  
 - PER FAC RULE 61G4-15.021, A SEPERATE ELECTRICAL
 PERMIT BY A LICENSED ELECTRICAL CONTRACTOR IS REQUIRED
 FOR THE CONNECTION TO THE PREMISES INTERGAL WIRING OR
 UTILITY SERVICE.
 THE CVC CONTRACTOR IS LIMITED TO THE PV SUPPLY SIDE OF
 THE POWER CONDITIONING UNIT, PV SOURCE CIRCUITS, PV
 OUTPUT CIRCUITS, AND BATTERY STORAGE SYSTEM CIRCUITS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-06-23 Cont ID  
Sent By mvaldes Date 2016-06-23 Time 17:15 Rev Time 0.00
Received By mvaldes Date 2016-06-23 Time 17:15 Sent To  
Notes
2016-06-23 17:16:31ELECTRICAL SUB PERMIT REQUIRED. ROUTED TO ROBERT
 MCDOUGAL

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-04-07 Cont ID  
Sent By mvaldes Date 2016-04-07 Time 09:53 Rev Time 0.00
Received By mvaldes Date 2016-04-07 Time 09:53 Sent To  
Notes
2016-04-07 10:24:16JOB PERMIT NUMBER: 16040300
 JOB ADDRESS: 201 SANTA LUCIA DR
 WEST PALM BEACH FLORIDA
 DATE: APRIL 7, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - THE SCOPE OF WORK ACCORDING TO FLORIDA STATUE
 61G4-15.021 LIMITS THE CVC CONTRACTOR TO THE PV SUPPLY
 SIDE , THEREFORE ANY CONNECTION TO THE ELECTRICAL
 BUILDING PREMISES MUST BE DONE BY A LICENSED ELECTRICAL
 CONTRACTOR.
 - PLANS ARE MISSING LABELS AND MARKINGS
 1 NEC 690.5 C GROUND FAULT PROTECTION
 2 NEC 690.14 C 2 PERMANENTLY MARK DISCONNECT
 3 NEC 690.31 E 3 IDENTIFY PV SOURCE CONDUCTORS
 4 NEC 705.12 7 DO NOT RELOCATE SOURCE DISCONNECT
 - SITE CURRENT CODE STANDARDS NEC 2011 AND FBC 2014
  
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-29 Cont ID  
Sent By rmcdouga Date 2016-06-29 Time 19:01 Rev Time 0.00
Received By rmcdouga Date 2016-06-17 Time 12:49 Sent To  
Notes
2016-06-20 12:53:20RESUB ROUTED TO AJONES VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-12 Cont ID  
Sent By cpuell Date 2016-04-12 Time 17:12 Rev Time 0.00
Received By cpuell Date 2016-04-05 Time 10:28 Sent To  
Notes
2016-04-06 09:02:46ELECTRICAL INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2016-06-21 Cont ID  
Sent By njwira Date 2016-06-21 Time 15:32 Rev Time 0.00
Received By njwira Date 2016-06-21 Time 15:32 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-04-12 Cont ID  
Sent By ajones Date 2016-04-12 Time 16:05 Rev Time 0.00
Received By ajones Date 2016-04-12 Time 16:05 Sent To  
Notes
***NONE***