Plan Review Details - Permit 16040257
Plan Review Stops For Permit 16040257
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-05-04 Cont ID  
Sent By   Date 2016-05-04 Time 17:15 Rev Time 0.00
Received By   Date 2016-05-04 Time 16:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-04-20 Cont ID  
Sent By jwitmer Date 2016-04-20 Time 08:01 Rev Time  
Received By jwitmer Date 2016-04-20 Time 07:30 Sent To  
Notes
2016-04-20 08:01:13 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16040257
 ADD: 1617 N. FLAGLER DR. SUITE 12A & 12B
 CONT: COUNIHAN CONSTRUCTION
 TEL: 561-722-6266
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. APRIL 20/2016
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION HAS A HOLD NOT TO ISSUE UNTIL
 THE OWNER SIGNS AND HAS NOTIRIZED THEIR SIGNATURE.
  
 2) SHEET A1 THE BALCONY SHOWS THE REMOVAL & INFILL OF
 (2) DOGGIE DOORS. PLEASE PROVIDE THE STRUCTURAL DETAILS
 OF THIS WORK AND THE MATERIALS TO BE USED IN THE
 INFILL. NOTE THIS IS A HIGH RISE, HOW WILL THE INFILL
 BE SEALED TO THE CONCRETE SLAB FOR WEATHER INTRUSION.
  
 2014 FBC-B 1403.3 STRUCTURAL. EXTERIOR WALLS, AND THE
 ASSOCIATED OPENINGS, SHALL BE DESIGNED AND CONSTRUCTED
 TO RESIST SAFELY THE SUPERIMPOSED LOADS REQUIRED BY
 CHAPTER 16.
  
 2014 FBC-B 1403.2 WEATHER PROTECTION. EXTERIOR WALLS
 SHALL PROVIDE THE BUILDING WITH A WEATHER-RESISTANT
 EXTERIOR WALL ENVELOPE. THE EXTERIOR WALL ENVELOPE
 SHALL INCLUDE FLASHING, AS DESCRIBED IN SECTION 1405.4.
 THE EXTERIOR WALL ENVELOPE SHALL BE DESIGNED AND
 CONSTRUCTED IN SUCH A MANNER AS TO PREVENT THE
 ACCUMULATION OF WATER WITHIN THE WALL ASSEMBLY BY
 PROVIDING A WATER-RESISTIVE BARRIER BEHIND THE EXTERIOR
 VENEER, AS DESCRIBED IN SECTION 1404.2, AND A MEANS FOR
 DRAINING WATER THAT ENTERS THE ASSEMBLY TO THE
 EXTERIOR. PROTECTION AGAINST CONDENSATION IN THE
 EXTERIOR WALL ASSEMBLY SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTION 1405.3.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-04-11 Cont ID  
Sent By mvaldes Date 2016-04-11 Time 17:55 Rev Time 0.00
Received By mvaldes Date 2016-04-11 Time 17:55 Sent To  
Notes
2016-04-11 17:58:42JOB PERMIT NUMBER: 16040257
 JOB ADDRESS: 1617 N FLAGLER DR
 WEST PALM BEACH FLORIDA
 DATE: APRIL 11 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - SITE CURRENT CODE STANDARDS NEC 2011 AND FBC 2014,
 NEC 2008 NO LONGER APPLICABLE.
 - FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN. THE PLANS ARE MISSING COFFEE MAKER , SHOWS
 2 DISHWASHER ON FLOOR PLANS AND CLACS REFLECT ONLY 1 ,
 REFLECT THESE LOADS ON PANEL A.
 - ADD THE FOLLOWING GENERAL ELECTRICAL NOTES : NEC
 406.11 TAMPER RESISTANT RECEPTACLES , NEC 210.12 B AFCI
 PROTECTION , FBC-E C 404.1.1 / 402.4.4 RECESSED LIGHTS
 SHALL BE 75 % HIGH EFFICIENT AS WELL AS IC RATED AND
 SEALED TO NOT COMPROMISE BUILDING THERMAL ENVELOPE. ( 2
 CFM )
 - NEC 404.2 C PROVIDE A GROUNDED CONDUCTOR AT EACH
 SWITCH LOCATION.
 - NEC 210.52 , 210.8 BALCONY RECEPTACLES MUST BE GFCI
 PROTECTED.
 - NFPA SECTION 29.8.3.4(6). SMOKE ALARMS AND SMOKE
 DETECTORS SHALL NOT BE INSTALLED WITHIN A 36 IN. (910
 MM) HORIZONTAL PATH FROM A DOOR TO A BATHROOM
 CONTAINING A SHOWER OR TUB UNLESS LISTED FOR
 INSTALLATION IN CLOSE PROXIMITY TO SUCH LOCATIONS.
 RELOCATE THE UNITS ACCORDINGLY. ( BY GUEST BEDROOM 1 &
 2. )
 - ALL ELECTRICAL BOXES IN A DEMISING WALL SHALL COMPLY
 WITH NEC 300.21 & FBC-B SECTION 714. ANY FIRE RATED
 STRUCTURE OR SURFACE THAT IS COMPROMISED SHALL BE
 RETURNED TO ITS ORIGINAL FIRE-RATING WITH APPROVED FIRE
 SEALING MATERIAL.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-04-11 Cont ID  
Sent By scaldero Date 2016-04-11 Time 13:52 Rev Time 0.00
Received By scaldero Date 2016-04-11 Time 13:43 Sent To  
Notes
2016-04-11 13:52:32PERMIT # 16040257
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 2) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 3) HARD-WIRED MULTI-STATION SMOKE ALARMS SHALL BE
 INSTALLED ON ALL LEVELS OF THE DWELLING UNIT, INSIDE
 EACH BEDROOM AND DIRECTLY OUTSIDE BEDROOM DOORS.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-04 Cont ID  
Sent By jwitmer Date 2016-05-04 Time 17:15 Rev Time 0.00
Received By jwitmer Date 2016-04-26 Time 14:32 Sent To  
Notes
2016-04-26 14:33:34RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-25 Cont ID  
Sent By gjohnson Date 2016-04-25 Time 13:54 Rev Time 0.00
Received By gjohnson Date 2016-04-06 Time 10:53 Sent To  
Notes
2016-04-07 10:53:10B16

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-04-20 Cont ID  
Sent By jwitmer Date 2016-04-20 Time 07:50 Rev Time 0.00
Received By jwitmer Date 2016-04-20 Time 07:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-05-05 Cont ID  
Sent By ccole Date 2016-05-05 Time 14:14 Rev Time 0.00
Received By ccole Date 2016-05-05 Time 14:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-04-26 Cont ID  
Sent By ccole Date 2016-04-26 Time 17:09 Rev Time 0.00
Received By ccole Date 2016-04-26 Time 17:09 Sent To  
Notes
2016-04-26 17:13:042ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16040257
 4/26/16
  
 1) PROVIDE THE DIMENSIONS OF THE TRANSFER GRILLS IN THE
 GUEST BEDROOMS.
 2) PLEASE COMPLY WITH COMMENTS #2 & 3 FROM THE 1ST
 REVIEW.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-04-19 Cont ID  
Sent By ccole Date 2016-04-08 Time 07:48 Rev Time 0.00
Received By ccole Date 2016-04-08 Time 09:59 Sent To  
Notes
2016-04-08 10:05:531ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16040257
 4/8/16
  
 1) PROVIDE MECHANICAL PLANS SHOWING ALL ALTERATIONS OR
 MODIFICATIONS TO THE EXISTING HVAC SYSTEMS.
 2) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 OCCUPIED ROOMS AND SPACES AS REQUIRED BY SECTION 809.2
 FBC-14 EXISTING BUILDING CODE, AND TABLE 403.3 FBC-14
 MECHANICAL.
 3) THE PROPOSED PROJECT IS DEFINED AS A RENOVATION PER
 SECTION 202 FBC-14 ENERGY CONSERVATION. SEE SECTION
 C101.4.3 AND SUBMIT ENERGY CALCULATIONS USING EITHER
 THE PRESCRIPTIVE OR PERFROMANCE BASED COMPLIANCE PATH-
 SECTION C101.5.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-04-25 Cont ID  
Sent By gjohnson Date 2016-04-25 Time 13:53 Rev Time 0.00
Received By gjohnson Date 2016-04-25 Time 13:53 Sent To  
Notes
2016-04-25 13:54:06PER GEORGE EARL 0013-B