Plan Review Details - Permit 16040252
Plan Review Stops For Permit 16040252
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-04-14 Cont ID  
Sent By mvaldes Date 2016-04-14 Time 18:25 Rev Time 0.00
Received By mvaldes Date 2016-04-14 Time 18:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-05-03 Cont ID  
Sent By ccole Date 2016-05-03 Time 17:04 Rev Time 0.00
Received By ccole Date 2016-05-03 Time 10:24 Sent To  
Notes
2016-05-03 10:24:25CCOLE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-28 Cont ID  
Sent By ccole Date 2016-04-28 Time 11:59 Rev Time 0.00
Received By ccole Date 2016-04-27 Time 11:33 Sent To  
Notes
2016-04-27 11:33:40RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-26 Cont ID  
Sent By ccole Date 2016-04-26 Time 15:59 Rev Time 0.00
Received By lmarchan Date 2016-04-05 Time 14:24 Sent To  
Notes
2016-04-05 14:24:14B06

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-05-03 Cont ID  
Sent By ccole Date 2016-05-03 Time 17:05 Rev Time 0.00
Received By ccole Date 2016-05-03 Time 17:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-04-28 Cont ID  
Sent By ccole Date 2016-04-28 Time 11:59 Rev Time 0.00
Received By ccole Date 2016-04-28 Time 11:59 Sent To  
Notes
2016-04-28 15:44:202ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16040252
 4/28/16
  
 1) THE REQUESTED AC CALCULATIONS FOR THE NEW SYSTEM
 WERE NOT SUBMITTED.
 2) SUBMIT TWO COPIES OF THE ROOF STAND NOA #13-1017.09
 WITH REVIEW AND APPROVAL SIGNATURES BY THE DESIGN
 PROFESSIONAL OF RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-04-06 Cont ID  
Sent By ccole Date 2016-04-06 Time 06:57 Rev Time 0.00
Received By ccole Date 2016-04-06 Time 07:07 Sent To  
Notes
2016-04-28 12:01:421ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16040252
 4/6/16
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW SYSTEM- SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
 2) CLARIFY THE LOCATION OF THE NEW AHU-1. NOTE 1 ON
 SHEET M0.1 IS INDICATING THE CU LOCATION.
 3) PROVIDE SITE SPECIFIC WIND LOAD ENGINEERING FOR
 INSTALLATION OF THE CU ON THE ROOF RACK. SUBMIT AN NOA
 OR FL. PRODUCT APPROVAL FOR THE RACK WITH APPROVAL
 SIGNATURE BY THE EOR- SECTION 301.15 FBC-14 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  
  
  
2016-04-06 07:03:281ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16040252
 4/6/16
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW SYSTEM- SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
 2) CLARIFY THE LOCATION OF THE NEW AHU-1. NOTE 1 ON
 SHEET M0.1 IS INDICATING THE CU LOCATION.
 3) PROVIDE SITE SPECIFIC WIND LOAD ENGINEERING FOR
 INSTALLATION OF THE CU ON THE ROOF RACK. SUBMIT AN NOA
 OR FL. PRODUCT APPROVAL FOR THE RACK WITH APPROVAL
 SIGNATURE BY THE EOR- SECTION 301.15 FBC-14 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-04-15 Cont ID  
Sent By gjohnson Date 2016-04-15 Time 08:51 Rev Time 0.00
Received By gjohnson Date 2016-04-15 Time 08:51 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved