Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-04-26 Cont ID  
Sent By cthroop Date 2016-04-26 Time 12:13 Rev Time 0.00
Received By cthroop Date 2016-04-26 Time 12:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-04-18 Cont ID  
Sent By cthroop Date 2016-04-18 Time 16:04 Rev Time 0.00
Received By cthroop Date 2016-04-18 Time 15:20 Sent To  
Notes
2016-04-18 16:11:481ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 1. COULD NOT VERIFY CU TIE DOWN FL15750.R0.11. PROVIDE
 TIE DOWN BASED ON DESIGN WIND SPEED LOAD CALC'S.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-04-25 Cont ID  
Sent By vperez Date 2016-04-25 Time 15:08 Rev Time 0.00
Received By vperez Date 2016-04-25 Time 15:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-04-09 Cont ID  
Sent By vperez Date 2016-04-09 Time 06:01 Rev Time 0.00
Received By vperez Date 2016-04-09 Time 06:01 Sent To  
Notes
2016-04-09 06:21:35INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. ELECTRICAL QUALIFIER TO SIGN DRAWINGS SUBMITTED PER
 FBC 105.3.2.1 AS DESIGNER
 2. SHOW GENERAL NOTES TO INDICATE REQUIRED AFCI
 PROTECTED CIRCUITS AND TAMPER RESISTANT RECEPTACLES PER
 FBC RES E3902 AND E4002.14
 3. PROVIDE A NOTE TO COMPLY WITH THE FBC EC
 CODE-R404.1- 75% OF LAMPS TO BE HIGH EFFICACY LAMPS.
 4. SHOW ELECTRODE CONDUCTOR AT SERVICE TO REFLECT #6
 NOT #8 PER E3603.1
 5. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE
 PER FBC RES E3609.3
 6. LABEL KITCHEN AND BATHROOM RECEPTACLES GFCI
 PROTECTED.
 7. CLARIFY IF THERE ARE EXISTING EXTERIOR FIXTURES FOR
 EGRESS PER FBC RES E3903.3
 8. SPACING REQUIREMENTS FOR RECEPTACLES TO BE ADDRESSED
 IN THE LIVING ROOM AREA PER E3901.2.2 WALL SPACE
 9. PROVIDE A RECEPTACLE WITHIN 25FT FOR AC EQUIPMENT
 EXTERIOR WP GFCI. PER FBC RES E3901.12
 10. OUTDOOR RECEPTACLE REQUIRED PER FBC RES E3901.7,
 FRONT AND BACK
 11. VERIFY THAT GDO OUTLET IS GFCI PROTECTED LABEL AS
 SUCH ON PANEL SCHEDULE. E3902.2
 12. SD/CO SMOKE DETECTORS REQUIRED ON THE EXTERIOR OF
 BEDROOM DOORS FBC RES 315
 13. FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. FEEL
 FREE TO CONTACT ME AT THE NUMBER LISTED BELOW SHOULD
 YOU HAVE ANY QUESTIONS OR CONCERNS.
  
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2016-04-28 Cont ID  
Sent By destabro Date 2016-04-28 Time 08:26 Rev Time 0.00
Received By destabro Date 2016-04-28 Time 08:26 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2016-04-18 Cont ID  
Sent By fmittner Date 2016-04-18 Time 10:40 Rev Time 0.00
Received By destabro Date 2016-04-18 Time 10:40 Sent To  
Notes
2016-04-18 10:41:414-18-2016 - EXISTING SHS WINDOWS WERE INSTALLED AFTER
 5/27/2006, PER PERMIT NO. 06041216. DLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2016-04-25 Time 12:53 Sent To  
Notes
2016-04-25 12:54:05RESUB ROUTED TO VPEREZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-18 Cont ID  
Sent By cthroop Date 2016-04-18 Time 16:04 Rev Time 0.00
Received By cthroop Date 2016-04-05 Time 08:51 Sent To  
Notes
2016-04-06 08:51:25R12

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-04-26 Cont ID  
Sent By jvalido Date 2016-04-26 Time 17:55 Rev Time 0.00
Received By jvalido Date 2016-04-26 Time 17:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-04-07 Cont ID  
Sent By jvalido Date 2016-04-07 Time 15:40 Rev Time 0.00
Received By jvalido Date 2016-04-07 Time 14:44 Sent To  
Notes
2016-04-07 15:38:52WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED REPLACED SHEETS DETACHED.
  
 107.2.1 - CONFIRM CFM QUANTITY OF AHU RH1T2417STANJA.
 AS PER RUDD/RHEEM RHIT/RH2T SERIES AHU MANUFACTURER
 SPECIFICATIONS THE HIGH SPEED IS 800 CFM AND LOW SPEED
 IS 600 CFM. AHU #2 AS PER THE PLANS SUBMITTED SHOW 933
 CFM FOR THE SPECIFIC AREA IT SUPPLIES.
  
 PROVIDE FBC 2014 WINDLOAD REQUIREMENT TIE DOWN DETAILS
 FOR CONDENSERS.(SEE NOTES ON SUBMITTED DETAIL).

Review Stop Z ZONING
Rev No 2 Status N Date 2016-04-28 Cont ID  
Sent By destabro Date 2016-04-28 Time 08:28 Rev Time 0.00
Received By destabro Date 2016-04-28 Time 08:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2016-04-18 Cont ID  
Sent By fmittner Date 2016-04-18 Time 10:44 Rev Time 0.00
Received By destabro Date 2016-04-18 Time 10:44 Sent To  
Notes
***NONE***