Plan Review Details - Permit 16040082
Plan Review Stops For Permit 16040082
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-04-29 Cont ID  
Sent By cthroop Date 2016-04-29 Time 10:09 Rev Time 0.00
Received By cthroop Date 2016-04-29 Time 10:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-04-05 Cont ID  
Sent By cthroop Date 2016-04-05 Time 08:34 Rev Time 0.00
Received By cthroop Date 2016-04-05 Time 08:34 Sent To  
Notes
2016-04-05 08:38:431ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 1. PROVIDE PROPOSED UNDERLAYMENT.
 2. PROVIDE AIR-BOURNE AND IMPACT SOUND TEST'S FOR
 UNDERLAYMENT.
 3. PROVIDE FLAME SPREAD TEST FOR UNDERLAYMENT.
  
 FBC 603.1 FLAME SPREAD
  
 FBC 1207.2 AIR-BORNE SOUND. ASTM E 09-02
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-04
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-29 Cont ID  
Sent By cthroop Date 2016-04-29 Time 10:09 Rev Time 0.00
Received By cthroop Date 2016-04-29 Time 10:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-05 Cont ID  
Sent By cthroop Date 2016-04-05 Time 08:34 Rev Time 0.00
Received By cthroop Date 2016-04-04 Time 14:37 Sent To  
Notes
2016-04-04 14:38:00BLDG <5K