Plan Review Details - Permit 16040071
Plan Review Stops For Permit 16040071
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2016-04-12 Cont ID  
Sent By tklarge Date 2016-04-12 Time 09:37 Rev Time 0.00
Received By tklarge Date 2016-04-12 Time 09:36 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-04-07 Cont ID  
Sent By tklarge Date 2016-04-07 Time 05:26 Rev Time 0.00
Received By tklarge Date 2016-04-07 Time 05:21 Sent To  
Notes
2016-04-07 05:26:111) THE SUBMITTED GAS PLAN REFERS TO A 2 PSI SYSTEM YET
 THE GAS TABLE REFERENCED IN THE DOCUMENTS IS FOR A 1/2
 PSI SYSTEM. CLARIFY. ENSURE THAT YOU ARE USING THE 2014
 FBC-FUEL GAS CODE.
 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE TANKLESS WATER HEATER. WPB
 AMEND. TO FBC SEC. 107.1.
 3) INDICATE THE SIZE OF THE PIPE AT THE OUTLET OF THE
 GAS METER. THE PIPING SHALL BE SIZED FOR THE TOTAL BTU
 LOAD ON THE SYSTEM. 2014 FGC SEC.402.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-12 Cont ID  
Sent By tklarge Date 2016-04-12 Time 09:37 Rev Time 0.00
Received By tklarge Date 2016-04-12 Time 09:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-07 Cont ID  
Sent By tklarge Date 2016-04-07 Time 05:26 Rev Time 0.00
Received By tklarge Date 2016-04-07 Time 05:26 Sent To  
Notes
***NONE***