Plan Review Stops For Permit 16040039 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2016-05-23 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-05-23 |
Time |
10:38 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-05-23 |
Time |
10:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2016-05-17 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-05-17 |
Time |
08:35 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-05-17 |
Time |
08:35 |
Sent To |
|
|
Notes |
2016-05-17 08:59:43 | 3RD REVIEW: FBC 2014 5TH ED | | CHRISTOPHER S. THROOP, C.B.O. | | BLDG. PLANS EXAMINER ? PX3169 | | (561) 805-7918 | | [email protected] | | | | 1. PROVIDE FASTENER SCHEDULE FOR WOOD AND DRYWALL | | REPLACEMENT. | | 2. PROVIDE REPAIR DETAIL FOR REMOVAL OF CONCRETE SLAB. | | 3. PROVIDE DETAIL FOR RATED FLOOR/CEILING ASSEMBLY. | | 4. PROVIDE FLOOR PLAN WITH DEMENSIONS. | | 5. DESIGNER TO SIGN PALNS. | | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | CONSTRUCTION DOCUMENTS SHALL BE | | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL | | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, | | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS | | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH | | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES | | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE | | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE | | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE | | DESIGN. (SEE ALSO SECTION 107.3.5). | | | | R302.3 TWO-FAMILY DWELLINGS. | | DWELLING UNITS IN TWO-FAMILY DWELLINGS SHALL BE | | SEPARATED FROM EACH OTHER BY WALL AND/OR FLOOR | | ASSEMBLIES HAVING NOT LESS THAN A 1-HOUR | | FIRE-RESISTANCE RATING WHEN TESTED IN ACCORDANCE WITH | | ASTM E 119 OR UL 263. FIRE-RESISTANCE-RATED | | FLOOR/CEILING AND WALL ASSEMBLIES SHALL EXTEND TO AND | | BE TIGHT AGAINST THE EXTERIOR WALL, AND WALL ASSEMBLIES | | SHALL EXTEND FROM THE FOUNDATION TO THE UNDERSIDE OF | | THE ROOF SHEATHING. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2016-04-07 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-04-07 |
Time |
08:56 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-04-07 |
Time |
08:56 |
Sent To |
|
|
Notes |
2016-04-29 11:26:36 | 1ST REVIEW: FBC 2014 5TH ED | | CHRISTOPHER S. THROOP, C.B.O. | | BLDG. PLANS EXAMINER ? PX3169 | | (561) 805-6718 | | [email protected] | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | | | 1. PROVIDE FLOOR PLAN WITH DEMENSIONS OF ALL AREAS OF | | PROJECT THAT WORK SHALL BE PERFORMED. | | 2. PROVIDE DETAILED SCOPE OF WORK. | | 3. PROVIDE FASTENER SCHEDULE FOR ALL DRYWALL AND WOOD | | SHEATHING, (FLOOR & WALLS). | | 4. PROVIDE DOOR AND WINDOW SCHEDULE FOR ANY REPLACEMENT | | DOORS &/OR WINDOWS. | | 5. PROVIDE DETAIL ON TENANT SEPERATION WALLS (FIRE | | WALL). | | 6. PROVIDE DETAIL ON HORIZONTAL RATED FLOOR/CEILING | | ASSEMBLIES. | | 7. DESIGNER TO SIGN PLANS. | | 8. ADDITIONAL COMMENTS MAY BE GENERATED UPON REVIEW OF | | PROPERLY SUBMITTED DOCUMENTS. | | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | CONSTRUCTION DOCUMENTS SHALL BE | | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL | | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, | | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS | | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH | | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES | | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE | | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE | | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE | | DESIGN. (SEE ALSO SECTION 107.3.5). | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
N |
Date |
2016-04-05 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-04-05 |
Time |
13:12 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-04-05 |
Time |
13:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
N |
Date |
2016-04-04 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-04-04 |
Time |
18:11 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-04-04 |
Time |
18:11 |
Sent To |
|
|
Notes |
2016-04-04 18:11:55 | ROUTED TO CHRIS THROOP. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2016-05-23 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-05-23 |
Time |
10:39 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-05-19 |
Time |
10:38 |
Sent To |
|
|
Notes |
2016-05-20 10:39:11 | RESUB ROUTED TO CTHROOP |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2016-05-17 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-05-17 |
Time |
08:35 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-05-12 |
Time |
10:21 |
Sent To |
|
|
Notes |
2016-05-13 10:21:19 | RESUB ROUTED TO TKLARGE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-04-07 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-04-07 |
Time |
08:56 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-04-01 |
Time |
10:12 |
Sent To |
|
|
Notes |
2016-04-04 10:12:16 | ROUTED TO ELECTRICAL INBOX |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2016-05-17 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-05-17 |
Time |
14:58 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-05-17 |
Time |
14:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2016-05-17 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-05-17 |
Time |
04:54 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-05-17 |
Time |
03:17 |
Sent To |
|
|
Notes |
2016-05-17 04:54:54 | TABLE 403.1 OF THE 2014 FBC-PLUMBING REQUIRES A MINIMUM | | OF ONE AUTOMATIC CLOTHES WASHER CONNECTION IN THE | | UNITS. THE PLANS DO NOT SHOW ANY PROVISIONS FOR | | AUTOMATIC CLOTHES WASHER CONNECTION. SHOW THE LOCATION | | OF THE AUTOMATIC CLOTHES WASHER CONNECTION ON THE FLOOR | | PLAN AND ALSO ON THE PLUMBING RISER. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2016-04-29 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-04-29 |
Time |
10:09 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-04-29 |
Time |
09:43 |
Sent To |
|
|
Notes |
2016-04-29 10:09:55 | 1) SUBMIT A SANITARY DRAINAGE RISER AND A WATER RISER | | THAT CLEARLY SHOWS THE SCOPE OF PLUMBING WORK TO BE | | DONE AND HOW IT IS TO BE DONE. THE SUBMITTED DRAWING IS | | UNACCEPTABLE AND DOES NOT COMPLY WITH THE PLUMBING | | CODE.FBC 107.1, 107.2.1. THE DRAWING DOES NOT SHOW ALL | | THE PIPING THAT IS TO BE REPLACED. THERE ARE PLUMBING | | RISERS AND STACKS AND UNDERGROUND PIPING THAT IS BEING | | REPLACED THAT IS NOT BEING SHOWN ON THE PLANS. | | 2) SUBMIT A FLOOR PLAN THAT CLEARLY REFLECTS THE ENTIRE | | SCOPE OF WORK TO BE DONE.CLEARLY IDENTIFY WHAT WORK IS | | BEING DONE IN WHAT AREAS. FBC 107.1. | | 3) SHOW ALL FIXTURE CLEARANCE DIMENSIONS AS REQUIRED BY | | THE 2014 FBC-PLUMBING SEC. 405.3.1. | | 4) PLANS SHALL BE SUBMITTED IN DUPLICATE PER THE 2014 | | FBC-PLUMBING SEC.107.1. | | 5) THE PLAN SHOWS A FLAT, DRY VENT ON THE SHOWER AND | | THE WATER CLOSET. VENTS SHALL CONNECT TO THE HORIZONTAL | | DRAIN PIPE IN ACCORDANCE WITH THE 2014 FBC-PLUMBING | | SEC.905.3. | | 6) CLEANOUTS ARE REQUIRED IN THE BASE OF ALL STACKS PER | | 2014 FBC-PLUMBING SEC.708.3.4. | | 7) SIZE ALL OF THE DRAIN AND VENT PIPES IN ACCORDANCE | | WITH THE 2014 FBC-PLUMBING SECS.710.1, TABLE 710.1 (2), | | 906.1, 906.2. | | | | THESE PLANS ARE SEVERELY DEFICIENT IN THE SCOPE OF | | WORK. DO NOT RESUBMIT JUST THE PLUMBING PLANS FOR | | REVIEW AGAIN. RESUBMITTED PLANS SHALL ADDRESS ALL THE | | COMMENTS FROM ALL TRADES. | | | | PLEASE REFER TO THE FLORIDA BUILDING CODE WEBSITE FOR | | FUTHER INFORMATION REGARDING THE ABOVE NOTED CODE | | SECTIONS AT WWW.FLORIDABUILDING.ORG. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2016-04-06 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-04-06 |
Time |
14:39 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-04-06 |
Time |
14:39 |
Sent To |
|
|
Notes |
2016-04-06 14:39:00 | 1) SUBMIT A SANITARY DRAINAGE RISER THAT CLEARLY SHOWS | | THE SCOPE OF PLUMBING WORK TO BE DONE. THE SUBMITTED | | DRAWING IS UNACCEPTABLE.FBC 107.1 | | 2) SUBMIT A FLOOR PLAN THAT CLEARLY REFLECTS THE ENTIRE | | SCOPE OF WORK TO BE DONE.CLAERLY IDENTIFY WHAT WORK IS | | BEING DONE IN WHAT AREAS. FBC 107.1. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|
|