Plan Review Details - Permit 16040029
Plan Review Stops For Permit 16040029
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-06-03 Cont ID  
Sent By cthroop Date 2016-06-03 Time 14:53 Rev Time 0.00
Received By cthroop Date 2016-06-03 Time 14:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-04-12 Cont ID  
Sent By cthroop Date 2016-04-12 Time 10:33 Rev Time 0.00
Received By cthroop Date 2016-04-12 Time 09:12 Sent To E
Notes
2016-04-12 11:23:341ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 1. EXISTING STRUCTURE SUPPORT NOTE ON PG. A-1 APPEARS
 TO BE INCORRECT. EXISTING BEARING APPEARS TO BE 4"
 STEEL POST ATTACHED TO A BEAM (UNKNOWN).
 2. SPECIFY UPLIFT AT EXISTING 4" STEEL POST TO
 BEAM/ROOF ASSEMBLY CONNECTION.
 3. PROVIDE DETAIL OF EXISTING UPLIFT CONNECTORS AT POST
 TO BEAM/ROOF ASSEMBLY.
 4. PROVIDE DETAIL FOR EXISTING POST TO FOOTING/COLUMN
 BASE CONNECTION.
 5. PROVIDE DETAIL FOR NEW SLAB-ON-GRADE TO EXISTING
 S.O.G CONNECTION.
 6. NEW EXT. WALLS SUBJECT TO WIND LOADS. PROVIDE
 WINDLOAD CALC'S.
 7. PROVIDE DETAIL FOR LINTEL AT NEW 3-0 EXT. DOOR.
 8. PROVIDE PRODUCT APPROVALS FOR NEW 3-0 EXT. DOOR.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE DOOR SUBMITTALS.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-06-02 Cont ID  
Sent By mvaldes Date 2016-06-02 Time 11:50 Rev Time 0.00
Received By mvaldes Date 2016-06-02 Time 11:50 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-04-13 Cont ID  
Sent By mvaldes Date 2016-04-13 Time 15:29 Rev Time 0.00
Received By mvaldes Date 2016-04-13 Time 15:29 Sent To  
Notes
2016-04-13 15:42:331ST REVIEW 4/13/16
 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 - PROVIDE EXISTING DEMAND CALCS ALONG WITH NEW
 ADDITIONAL LOADS, EXISTING RISER DIAGRAM AND PANEL
 SCHEDULES TO INCLUDE CONDUIT , OVERCURRENT PROTECTION
 AND WIRE SIZES.
 - NEC 210.8 A GARAGE OR STORAGE AREAS REQUIRE GFCI
 PROTECTION OF RECEPTACLE OUTLETS
 - NEC 210.70 2B A LIGHTING OUTLET REQUIRED FOR EXTERIOR
 DOORS.
 - SMOKE/CARBON MONOXIODE ALARMS SHALL BE INSTALLED PER
 RESIDENTIAL CODE SECTIONS 314 & 315.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-03 Cont ID  
Sent By cthroop Date 2016-06-03 Time 14:53 Rev Time 0.00
Received By cthroop Date 2016-05-12 Time 15:15 Sent To  
Notes
2016-05-12 15:16:01RESUB ROUTED TO AJONES VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-13 Cont ID  
Sent By mvaldes Date 2016-04-13 Time 15:42 Rev Time 0.00
Received By mvaldes Date 2016-04-01 Time 15:06 Sent To  
Notes
2016-04-01 15:06:35ROUTED TO ZONING

Review Stop Z ZONING
Rev No 3 Status P Date 2016-06-16 Cont ID  
Sent By ajones Date 2016-06-16 Time 10:47 Rev Time 0.00
Received By ajones Date 2016-06-16 Time 10:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2016-06-01 Cont ID  
Sent By njwira Date 2016-06-01 Time 16:09 Rev Time 0.00
Received By njwira Date 2016-06-01 Time 16:09 Sent To E
Notes
2016-06-01 16:09:416/1/16- FAILED- NEED 2 COPIES OF A SURVEY OF THE
 PROPERTY.
  
 PLEASE CONTACT:
 NATHAN WIRA
 (561)822-1442
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-04-06 Cont ID  
Sent By ajones Date 2016-04-06 Time 17:04 Rev Time 0.00
Received By ajones Date 2016-04-06 Time 17:04 Sent To B
Notes
2016-04-06 17:06:144/6/16- FAILED. NEED 2 COPIES OF THE SURVEY.
 ANGELLA VANN, PLANNING AND ZONING ADMINISTRATOR
 561-822-1441
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved