Plan Review Details - Permit 16031457
Plan Review Stops For Permit 16031457
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-04-19 Cont ID  
Sent By rmcdouga Date 2016-04-19 Time 10:25 Rev Time 0.00
Received By rmcdouga Date 2016-04-19 Time 09:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-04-06 Cont ID  
Sent By rmcdouga Date 2016-04-06 Time 08:01 Rev Time 0.00
Received By rmcdouga Date 2016-04-06 Time 06:48 Sent To  
Notes
2016-04-06 08:01:11PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010 / NEC 2008
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS INDICATE A MAIN LUG ONLY PANEL AND NO MAIN
 BREAKER OR DISCONNECT IS SPECIFIED. A DISCONNECT AND
 /OR MAIN BREAKER IS REQUIRED TO PROVIDE OVERCURRENT
 PROTECTION FOR THE SERVICE ENTRANCE CONDUCTORS. NEC
 230.70 & 230.91
  
 2) THE PANEL SCHEDULE FEEDER SIZE IS LISTED AS 3/0 AND
 THE RISER HAS 2/0. PLEASE CORRECT. FBC 107.2.1
  
 3) THE ELECTRICAL NOTES SPECIFY THE 2012 NEC AND THIS
 PROJECT IS SUBJECT TO THE 2008 NEC. PLEASE CORRECT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-19 Cont ID  
Sent By rmcdouga Date 2016-04-19 Time 10:25 Rev Time 0.00
Received By rmcdouga Date 2016-04-12 Time 14:14 Sent To  
Notes
2016-04-12 14:15:05RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-06 Cont ID  
Sent By rmcdouga Date 2016-04-06 Time 08:01 Rev Time 0.00
Received By rmcdouga Date 2016-03-31 Time 13:11 Sent To  
Notes
2016-03-31 13:12:09REVISION ROUTED TO RMCDOUGAL