Plan Review Details - Permit 16031398
Plan Review Stops For Permit 16031398
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-04-04 Cont ID  
Sent By mvaldes Date 2016-04-04 Time 13:06 Rev Time 0.00
Received By mvaldes Date 2016-04-04 Time 13:06 Sent To  
Notes
2016-04-04 13:17:07 
 REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 - CUSTOMER ADRESSED COMMENTS UP FRONT THERE FORE A
 PROVISO WAS ISSUED.
  
 - REFER TO PREVIOUS COMMENTS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-30 Cont ID  
Sent By mvaldes Date 2016-03-30 Time 18:06 Rev Time 0.00
Received By mvaldes Date 2016-03-30 Time 18:06 Sent To  
Notes
2016-03-30 18:07:02JOB PERMIT NUMBER: 16031398
 JOB ADDRESS: 513 58TH ST
 WEST PALM BEACH FL
 DATE: MARCH 30 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - NEC 210.52 A 1 & 2 OUTLET SPACING, IT APPEARS SOME
 POINTS ALONG THE WALL EXCEED 6? FROM AN OUTLET ( MARKED
 ON PLANS RED INK )
 - NEC 210.52 H IN DWELLING UNITS HALLWAYS 10 FT OR OR
 MORE SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET. (
 MARKED ON PLANS RED INK )
 - NEC 210.E 1 FOR A ONE & TWO FAMILY DWELLING UNIT AT
 LEAST ONE GFCI RECEPTACLES IN THE FRONT AND BACK OF THE
 DWELLING . ( MARKED ON PLANS RED INK )
 - SMOKE ALARMS REQUIRED PER RESIDENTIAL CODE SECTIONS
 314 & 315 ( MARKED ON PLANS RED INK )
 - ADD INTERSYSTEM BONDING TERMINAL TO RISER DIAGRAM
 GROUNDING DETAIL NEC 250.94
 - NEC 210.12 B AFCI PROTECTION REQUIRED. CHECK ALL
 AREAS APPLICABLE.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-04 Cont ID  
Sent By mvaldes Date 2016-04-04 Time 13:21 Rev Time 0.00
Received By mvaldes Date 2016-04-04 Time 11:00 Sent To  
Notes
2016-04-04 11:01:05RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-30 Cont ID  
Sent By mvaldes Date 2016-03-30 Time 18:07 Rev Time 0.00
Received By mvaldes Date 2016-03-30 Time 11:26 Sent To  
Notes
2016-03-30 11:27:17ROUTED TO ELECTRICAL INBOX