Plan Review Stops For Permit 16031307 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2016-04-07 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-04-07 |
Time |
16:13 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-04-07 |
Time |
16:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2016-03-28 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-03-28 |
Time |
17:35 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-03-28 |
Time |
17:35 |
Sent To |
|
|
Notes |
2016-03-28 17:49:10 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 516-805-6713 | | [email protected] | | | | | | - RISER DIAGRAM SHOWS NO DISCONNECTING MEANS OF THE | | ELECTRICAL SERVICE PLEASE LOCATE NEAREST POINT OF | | ENTRY. NEC 230.70 A1 | | KEEP IN MIND ALL DISCONNECTS MUST BE GROUPED AND | | PROPERLY LABELED. NEC 230.72 A , NEC 408.4 B | | | | - GROUNDING DETAIL TO INCLUDE INTERSYSTEM BONDING | | TERMINAL. NEC 250.94 | | | | - CLARIFY IF METER ENCLOSURE LUGS ARE RATED FOR DUAL | | WIRES ? ( ACCORDING TO DRAWING ) |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-03-28 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-03-28 |
Time |
17:49 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-03-28 |
Time |
15:00 |
Sent To |
|
|
Notes |
2016-03-28 15:00:44 | REVISION ROUTED TO ELECC <5K |
|
|
|