Plan Review Details - Permit 16031271
Plan Review Stops For Permit 16031271
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-03-31 Cont ID  
Sent By mvaldes Date 2016-03-31 Time 12:03 Rev Time 0.00
Received By mvaldes Date 2016-03-31 Time 12:03 Sent To  
Notes
2016-03-31 12:09:34REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 PASSED WITH A PROVISO OF THE FOLLOWING ITEMS
  
 - ADD A SMOKE DETECTOR IN FRONT OF FACP. NFPA 72 10.15
 , FBC 907 .4.1
  
 - INCLUDE GENERAL NOTE STATING MECHANICAL PROTECTION
 REQUIRED AND RED MARKING LABELED " FIRE ALARM CIRCUIT "
 . NEC 760 , NFPA 72 10.5.5.2

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-03-29 Cont ID  
Sent By fstal Date 2016-03-29 Time 16:12 Rev Time  
Received By fstal Date   Time   Sent To E
Notes
2016-03-29 16:22:01(1) FIRE ALARM INSTALLATION SHALL COMPLY WITH NEC, NFPA
 70 AND 72. ALL FIRE PROTECTION EQUIPMENT SHALL REMAIN
 INSERVICE DURING ALL PHASES OF CONSTRUCTION AND
 INSTALLATION.
  
 (2) NFPA 90A-6.4.2.1 SMOKE DETECTORS LISTED FOR USE IN
 AIR DISTRIBUTION SYSTEMS SHALL BE LOCATED AS FOLLOWS:
 DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY BRANCH
 CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING A CAPACITY
 GREATER THAN 944 L/SEC (2000 FT3/MIN) AT EACH STORY
 PRIOR TO THE CONNECTION TO A COMMON RETURN AND PRIOR TO
 ANY RECIRCULATION OR FRESH AIR INLET CONNECTION IN AIR
 RETURN SYSTEMS HAVING A CAPACITY GREATER THAN 7080
 L/SEC (15,000 FT3/MIN) AND SERVING MORE THAN ONE STORY.
  
 (3) NFPA 72-10.18.2.4, 2010 VERIFICATION OF COMPLIANT
 INSTALLATION. WHERE REQUIRED, COMPLIANCE OF THE
 COMPLETED INSTALLATION WITH THE REQUIREMENTS OF THIS
 CODE, AS IMPLEMENTED VIA THE REFERRING CODE(S),
 SPECIFICATIONS, AND/OR OTHER CRITERIA APPLICABLE TO THE
 SPECIFIC INSTALLATION, SHALL BE CERTIFIED BY A
 QUALIFIED AND IMPARTIAL THIRD-PARTY ORGANIZATION
 ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION.
  
 FRANK STALLWORTH, FIRE INSPECTOR I
 WEST PALM BEACH FIRE PREVENTION BUREAU
 500 N. DIXIE HWY
 WEST PALM BEACH, FLORIDA 33401
 OFFFICE: 561-840-4780
 FAX: 561-840-4774
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-31 Cont ID  
Sent By mvaldes Date 2016-03-31 Time 12:09 Rev Time 0.00
Received By mvaldes Date 2016-03-28 Time 10:25 Sent To  
Notes
2016-03-28 10:25:21ROUTED TO FIRE INBOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved