Plan Review Details - Permit 16031224
Plan Review Stops For Permit 16031224
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-06-22 Cont ID  
Sent By jgomez Date 2016-06-22 Time 13:56 Rev Time 0.00
Received By jgomez Date 2016-06-22 Time 13:56 Sent To  
Notes
2016-06-22 13:57:10 
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-06-13 Cont ID  
Sent By jgomez Date 2016-06-10 Time 18:19 Rev Time 0.00
Received By jgomez Date 2016-06-10 Time 17:28 Sent To  
Notes
2016-06-10 18:23:54RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC, 5TH EDITION (2014).
  
 ***NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. WITH
 PROVISO THE OWNER/BUILDER MAY SUBMIT THE REQUIRED
 INFORMATION AFTER THE PERMIT IS ISSUED AND BEFORE
 REQUIRED INSPECTION TO AVOID CONFLICTS OR DELAYS.
 REVISION FEES MAY APPLY. OWNER/BUILDER TO ADVICE IF THE
 PROVISO OPTION IS PREFERRED AT THIS TIME OR IF
 RE-SUBMITTING REQUIRED INFORMATION BEFORE ISSUING THE
 PERMIT.
  
  
 ORIGINAL COMMENT:
 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
 RESPONSE:
 A) ENERGY CALCULATIONS SUBMITED ARE MISSING THE
 INSPECTION CHECKLIST AS REQUIRED BY SEC. R405.4.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) ITEM #5 SPECIFIES THAT THIS IS NOT WORST CASE.
 CLARIFY WHY PAGE 2 OF 5 SPECIFIES AN ANGLE ROTATION OF
 180 DEGREES. THE CALCULATIONS NEED TO BE DONE TO THE
 ACTUAL ORIENTATION OF THE BUILDING. REVISE THE WALLS,
 DOORS AND WINDOWS INFORMATION ON PAGE 3 OF 5. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 MULTIPLE ORIENTATIONS IS ONLY ALLOWED WHEN THERE IS THE
 CONSTRUCTION OF A BUILDING MODEL.
  
 C) PROVIDE DOCUMENTATION OF THE COMPONENT EFFICIENCIES
 USED FOR THE WINDOWS AND DOORS U-FACTOR AND SHGC FACTOR
 SPECIFIED ON ITEM # 7 OF THE ENERGY CALCULATIONS AS
 REQUIRED BY SEC. R405.4.3 (2) FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
 NOTE: THIS IS REQUIRED WHEN THE ENERGY CALCULATIONS ARE
 USING ANOTHER EFFICIENCY FACTOR OTHER THAN THE SOFTWARE
 DEFAULT FACTOR FOR GLAZING.
  
 D) ITEM #9(C) CALLS FOR ADJACENT WOOD FRAME WALLS.
 CLARIFY WHERE ARE THE WOOD FRAMED WALLS. PLANS DON'T
 SHOW ANY. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 E) COMPLETE ALL THE INFORMATION ON TOP OF FORM
 INCLUDING BUILDER NAME, PERMIT OFFICE, JURISDICTION
 NUMBER. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 ORIGINAL COMMENT:
 2- NEED TO SPECIFY ON PLANS CARBON MONOXIDE ALARMS
 WITHIN 10 FEET OF ALL BEDROOMS AS REQUIRED BY SEC. R315
 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
 RESPONSE: CARBON MONOXIDE ALARMS WERE SPECIFIED FOR THE
 ADDITION ONLY. NEED TO SPECIFY ALARMS FOR ALL BEDROOMS,
 INCLUDING THE EXISTING ONES.
  
 ORIGINAL COMMENT:
 3- EXISTING AND DEMOLITION PLAN ON SHEET 2 SHOWS
 EXISTING MEDIA ROOM. ACCORDING TO CITY RECORDS AND
 PROPERTY APPRAISER THIS ROOM IS AN UNFINISHED ENCLOSED
 PORCH NOT A LIVING SPACE. REVISE AS REQUIRED. THIS ROOM
 MAY BE CONVERTED TO A MEDIA ROOM AS SHOWN ON SHEET 4
 BUT NEEDS TO SHOW COMPLIANCE WITH THE ENERGY
 CALCULATIONS (WALLS AND CEILING INSULATION) AND WITH
 THE ELECTRICAL REQUIREMENTS ( SEE ELECTRICAL REVIEW
 COMMENTS). SEC. 102.2 CITY AMENDMENTS.
 RESPONSE: INFORMATION ON PROPOSED NEW FLOOR PLAN ON
 SHEET #4 WAS REVISED. NOW IT READS "EXISTING ENCLOSED
 PORCH". CLARIFY IF THIS ROOM IS GOING TO BE A MEDIA
 ROOM OR ENCLOSED PORCH.
 SHEET #1 SAYS "EXISTING ENCLOSED PORCH CONVERTED TO NEW
 MEDIA ROOM". PLEASE COORDINATE ALL PLANS IN ORDER TO
 HAVE A PROPER PLAN REVIEW.
  
 ORIGINAL COMMENT:
 4- ROOF SHEATHING SPECIFICATIONS SHOWN ON NAILING
 DETAIL ON SHEET #8, TYPICAL WALL SECTION ON SHEET #9
 AND ROOF SHEATHING NOTES ON SHEET #10 DON'T MATCH
 SPECIFICATIONS SHOWN ON FASTENER SCHEDULE ON SHEET #5.
 REVISE AS REQUIRED TO MATCH. NOTE: SEC. R803.2.3.1
 FBC-RESIDENTIAL REQUIRES 8D RING SHANK NAILS MIN.
 RESPONSE: SPECIFICATIONS WERE NOT CHANGED ON TYPICAL
 WALL SECTION ON SHEET #9.
  
 NEW COMMENT:
 5- TRUSS PACKAGE WAS SUBMITTED AT THIS TIME. THERE IS
 NO NEED TO SUBMITT TRUSS PACKAGE FOR REVIEW. TRUSS
 PACKAGE MAY BE GIVEN TO THE BUILDING INSPECTOR AT TIME
 OF FRAMING INSPECTION. THE FOLLOWING NEEDS TO BE
 ADDRESSED BY THE TRUSS ENGINEER:
 A) NEED ORIGINAL SIGNATURE AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTE WHEN SUBMITTING DOCUMENTS FOR PUBLIC
 RECORDS. RUBBER STAMP IS NOT ALLOWED.
 B) THE COVER PAGE IS MISSING AL THE INFORMATION OF THE
 STRUCTURAL ENGINEER OF RECORD AS REQUIRED BY SEC.
 61G15-31.003.
 C) ALL THE GENERAL STANDARD ENGINEERING PAGES NEED
 ENGINEER'S ORIGINAL SEAL, SIGNATURE, DATE. AS REQUIRED
 BY SEC. 61G15-23.003 AND CHAPTER 471 FLORIDA STATUTES.
 D) REVISED TRUSS PACKAGE TO BE REVIEWED AND APPROVED BY
 THE ENGINEER OF RECORD.
 NOTE: REVISED TRUSS PACKAGE MAY BE SUBMITTED TO THE
 BUILDING INSPECTOR AT TIME OF FRAMING INSPECTION. NO
 NEED TO RESUBMIT NOW.
  
  
 ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. DON'T STAPLE OLD DRAWINGS TO NEW SET OF
 PLANS. SUBMIT OLD DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-04-20 Cont ID  
Sent By jgomez Date 2016-04-20 Time 14:34 Rev Time 0.00
Received By jgomez Date 2016-04-20 Time 12:45 Sent To  
Notes
2016-04-20 15:01:59RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE; FBC, 5TH EDITION (2014).
  
 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 2- NEED TO SPECIFY ON PLANS CARBON MONOXIDE ALARMS
 WITHIN 10 FEET OF ALL BEDROOMS AS REQUIRED BY SEC. R315
 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 3- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 4- EXISTING AND DEMOLITION PLAN ON SHEET 2 SHOWS
 EXISTING MEDIA ROOM. ACCORDING TO CITY RECORDS AND
 PROPERTY APPRAISER THIS ROOM IS AN UNFINISHED ENCLOSED
 PORCH NOT A LIVING SPACE. REVISE AS REQUIRED. THIS ROOM
 MAY BE CONVERTED TO A MEDIA ROOM AS SHOWN ON SHEET 4
 BUT NEEDS TO SHOW COMPLIANCE WITH THE ENERGY
 CALCULATIONS (WALLS AND CEILING INSULATION) AND WITH
 THE ELECTRICAL REQUIREMENTS ( SEE ELECTRICAL REVIEW
 COMMENTS). SEC. 102.2 CITY AMENDMENTS.
  
 5- FLOOR PLAN ON SHEET 4 SPECIFY EXISTING WINDOWS TO BE
 REPLACED. CLEARLY SPECIFY THE TYPE AND SIZE OF EXISTING
 BEDROOM WINDOWS AND TYPE AND SIZE OF PROPOSED BEDROOM
 WINDOWS TO VERIFY COMPLIANCE WITH THE EGRESS
 REQUIREMENTS OF SEC. 704 OF FBC-EXISTING BUILDING, 5TH
 EDITION (2014). NOTE: THIS INCLUDES THE EXISTING
 BEDROOM THAT WAS LOCATED ON THE NORTH-EAST CORNER AND
 WAS RENAMED AS "OFFICE". THIS ROOM CAN BE USED AS
 OFFICE OR BEDROOM.
  
 6- WINDOW ON THE EXISTING BATHROOM WAS BLOCKED TO ALLOW
 FOR THE MASTER BEDROOM ADDITION. SHOW COMPLIANCE WITH
 THE BATHROOM VENTILATION REQUIRED BY SEC. R303.3 OF
 FBC-RESIDENTIAL. NOTE: SEE EXCEPTION ON SEC. R303.3.
  
 7- PROPOSED NEW FLOOR PLAN ON SHEET #4 SPECIFIES THE
 FINISH FLOOR AT THE NEW MEDIA ROOM TO BE RAISED TO
 MATCH EXISTING HOUSE FLOOR ELEVATION. SPECIFY THE NEW
 CEILING HEIGHT TO VERIFY COMPLIANCE WITH SEC. R305 OF
 FBC-RESIDENTIAL.
  
 8- SPECIFY SIZE OF ATTIC ACCESS LOCATED IN THE NEW
 MASTER BEDROOM WALK-IN-CLOSET TO VERIFY COMPLIANCE WITH
 SEC. R807 FBC-RESIDENTIAL.
  
 9- EXTERIOR ELEVATIONS SHOW ROOF PITCH OF 3:12 +/-.
 NEED TO SPECIFY 2 LAYERS OF UNDERLAYMENT AS REQUIRED BY
 SEC. R905.2.2 FBC-RESIDENTIAL.
  
 10- A) PROVIDE COMPLETE SPECIFICATION S FOR THE BEAMS
 TO BE INSTALLED ON THE NEW ENTRY PORCH. ROOF FRAMING
 PLAN DOESN'T PROVIDE ANY SPECIFICATION. SEC. R301
 FBC-RESIDENTIAL.
  
 B) CLARIFY CONNECTION OF ENTRY PORCH TO THE EXISTING
 WALL. ROOF FRAMING PLAN ON SHEET #5 SPECIFIES "BEAM
 CONNECTOR C. SEE DETAIL ON PG-7". THERE IS NO DETAIL ON
 PAGE 7. REVISE AS REQUIRED. CLEARLY SPECIFY CONNECTOR
 AT THE END OF THE BEAM. SEC. R301 FBC-RESIDENTIAL.
  
 11- ROOF SHEATHING SPECIFICATIONS SHOWN ON NAILING
 DETAIL ON SHEET #8, TYPICAL WALL SECTION ON SHEET #9
 AND ROOF SHEATHING NOTES ON SHEET #10 DON'T MATCH
 SPECIFICATIONS SHOWN ON FASTENER SCHEDULE ON SHEET #5.
 REVISE AS REQUIRED TO MATCH. NOTE: SEC. R803.2.3.1
 FBC-RESIDENTIAL REQUIRES 8D RING SHANK NAILS MIN.
  
 12- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ROOF SHINGLES SPECIFIED ON PLANS.
  
 B) WINDOWS MULLIONS AS SPECIFIED ON PLANS. AND, CLEARLY
 IDENTIFY MULLION SIZE TO VERIFY COMPLIANCE WITH THE
 ENGINEER CALCULATED DESIGN PRESSURES.
  
 C) SINGLE HUNG WINDOWS AS SHOWN ON PLANS.
  
 D) GARAGE DOOR AS SHOWN ON PLANS (IF IS GOING TO BE
 REPLACED).
  
 E) ENTRY DOOR AS SHOWN ON PLANS.
  
 13- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS (NOTE:
 INCLUDING THE ONES THAT WERE ALREADY SUBMITTED) AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 14- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $100,000. THE
 PERMIT FEE BALANCE IS $2298.86.
  
 ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. DON'T STAPLE OLD DRAWINGS TO NEW SET OF
 PLANS. SUBMIT OLD DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-06-22 Cont ID  
Sent By mvaldes Date 2016-06-22 Time 10:30 Rev Time 0.00
Received By mvaldes Date 2016-06-22 Time 10:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-06-15 Cont ID  
Sent By mvaldes Date 2016-06-15 Time 18:23 Rev Time 0.00
Received By mvaldes Date 2016-06-15 Time 18:02 Sent To  
Notes
2016-06-15 18:23:24REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - SMOKE ALARMS REQUIRED PER RESIDENTIAL CODE SECTIONS
 SECTIONS 314 & 315 , VERIFY BUILDING COMMENTS FOR
 REQUEST TO PROVIDE ALL THE LOCATIONS IN AREAS
 APPLICABLE ON THE FLOOR PLAN.
  
 - MEDIA ROOM IS A HABITABLE LIVING SPACE THEREFORE NEC
 210.52(A) APPLIES AND RECEPTACLE SPACING IS REQUIRED AS
 WELL AS NEC 210.70 LIGHTING OULET REQUIRED. CLARIFY THE
 INTENT OF THE SPACE
 BECAUSE ON THE OTHER SHEETS ITS LABELED AS EXISTING
 ENCLOSED PORCH ? PLEASE REFERENCE BUILDING COMMENTS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-28 Cont ID  
Sent By mvaldes Date 2016-03-28 Time 13:21 Rev Time 0.00
Received By mvaldes Date 2016-03-28 Time 13:21 Sent To  
Notes
2016-03-28 13:53:05REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
  
 - PLEASE ADD THE FOLLOWING ELECTRICAL NOTES TO BE
 COMPLIANT
  
 1 AFCI PROTECTION REQUIRED PER NEC 210.12B ( E3902.13 )
 2 TAMPER RESISTANT RECEPTACLES REQUIRED PER NEC 406.11
 ( E4002.14 )
 3 BOXES AT FAN OUTLETS SHALL BE LISTED FOR 70 LB. NEC
 314.27C ( E3905.8 )
 4 CLOTHES CLOSET LIGHTS NEAR COMBUSTIBLE MATERIAL NEC
 410.16 A,B,C ( E4003.12 )
 5 RECESSED LIGHTS SHALL BE 75 % HIGH EFFICIENT,AS WELL
 AS IC RATED AND SEALED TO NOT COMPROMISE
 BUILDING THERMAL ENVELOPE. ( 2 CFM ) FBC-ER 404.1.1 /
 402.4.4
  
 - INCLUDE GROUNDING DETAIL AND METER ENCLOSURE IN RISER
 DIAGRAM. WPBA 107
 - NEC 210.52(A)(1)&(2) OUTLET SPACING, IT APPEARS SOME
 POINTS ALONG THE WALL EXCEED 6? FROM AN OUTLET ( CHECK
 BUILDING COMMENTS FOR MEDIA ROOM. )

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-22 Cont ID  
Sent By jgomez Date 2016-06-22 Time 13:57 Rev Time 0.00
Received By jgomez Date 2016-05-31 Time 09:56 Sent To  
Notes
2016-06-01 09:56:18R32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-21 Cont ID  
Sent By jgomez Date 2016-04-21 Time 16:56 Rev Time 0.00
Received By jgomez Date 2016-03-25 Time 11:05 Sent To  
Notes
2016-03-25 11:05:44R26

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2016-06-10 Cont ID  
Sent By jgomez Date 2016-06-10 Time 18:18 Rev Time 0.00
Received By jgomez Date 2016-06-10 Time 18:18 Sent To  
Notes
2016-06-10 18:19:09$417.24 PAID. MU-2016-013591.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-04-20 Cont ID  
Sent By jgomez Date 2016-04-20 Time 15:22 Rev Time 0.00
Received By jgomez Date 2016-04-20 Time 15:22 Sent To  
Notes
2016-04-20 15:22:351- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-06-22 Cont ID  
Sent By jvalido Date 2016-06-22 Time 09:05 Rev Time 0.00
Received By jvalido Date 2016-06-22 Time 09:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-04-04 Cont ID  
Sent By jvalido Date 2016-04-04 Time 16:39 Rev Time 0.00
Received By jvalido Date 2016-04-04 Time 16:17 Sent To  
Notes
2016-04-04 16:37:42CITY OF WEST PALM BEACH
 LOCAL AMENDMENTS TO THE
 FLORIDA BUILDING CODE (FBC) 2010
 CHAPTER 1 ADMINISTRATION
  
 107.2.1 - CONFIRM CFM QUANTITY OF AHU SPECIFIED ON
 PLANS. AS PER CARRIER AIR HANDLER (INDOOR BLOWER &
 EVAP) OWNERS MANUAL SPECIFICATIONS - AHU - FVC4 - 003
 MATCHED WITH A CONDENSER UNIT CAPACITY 024 THE MAXIMUM
 EFFECTIVE COOLING (HIGH SPEED) IS 700 CFM, (LOW SPEED)
 560 CFM.
  
 PLANS SUBMITTED SHOW 1050 CFM AT TOTAL 23100 BTU.
 PROVIDE MANUFACTURE SPECIFICATIONS CONFIRMING THIS.
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-06-16 Cont ID  
Sent By gjohnson Date 2016-06-16 Time 14:33 Rev Time 0.00
Received By gjohnson Date 2016-06-16 Time 14:33 Sent To  
Notes
2016-06-10 18:14:35NEW DRAWINGS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-04-13 Cont ID  
Sent By gjohnson Date 2016-04-13 Time 13:16 Rev Time 0.00
Received By gjohnson Date 2016-04-13 Time 13:16 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2016-06-13 Cont ID  
Sent By jgomez Date 2016-06-13 Time 18:08 Rev Time 0.00
Received By jgomez Date 2016-06-13 Time 18:08 Sent To  
Notes
2016-06-13 18:09:441) SHINGLES FL10674-R11.
  
 2) UNDERLAYMENT FL16048-R3.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-04-21 Cont ID  
Sent By jgomez Date 2016-04-21 Time 16:55 Rev Time 0.00
Received By jgomez Date 2016-04-21 Time 07:54 Sent To  
Notes
2016-04-21 16:56:121- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ROOF SHINGLES SPECIFIED ON PLANS.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2016-06-15 Cont ID  
Sent By llouie Date 2016-06-15 Time 13:31 Rev Time 0.00
Received By llouie Date 2016-06-14 Time 15:14 Sent To  
Notes
2016-06-15 13:33:10PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY,
 THE FOLLOWING CONDITIONS SHALL BE ADDRESSED:
  
 1.) A LANDSCAPE PERMIT, WHICH INCLUDES A LANDSCAPE
 PLAN, SHALL BE SUBMITTED TO THE BUILDING DIVISION FOR
 REVIEW.
  
 2.) THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED
 LANDSCAPE PERMIT SHALL BE INSTALLED AND PASS A FINAL
 LANDSCAPE INSPECTION.
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-04-12 Cont ID  
Sent By llouie Date 2016-04-12 Time 15:02 Rev Time 0.00
Received By llouie Date 2016-04-11 Time 17:02 Sent To  
Notes
2016-04-12 15:05:09** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS IN WRITING OR ON
 THE PLANS WHERE APPLICABLE:
  
 1.) BUILDING SETBACK ON THE WEST SIDE OF THE PROPERTY
 MISSING. PLEASE NOTATE THE WEST SIDE SETBACK DIMENSION
 IN THE SITE PLAN. [ZLDR S.94-72(A)(2)]
  
 2.) THE DRIVEWAY SHALL BE SETBACK 3 FT. FROM THE WEST
 PROPERTY LINE. THE DRIVEWAY DOES NOT SEEM TO MEET THIS
 MINIMUM REQUIREMENT. ALSO, PLEASE NOTATE THE DRIVEWAY
 SETBACK DIMENSION IN THE SITE PLAN. [ZLDR
 S.94-482(D)(2)]
  
 3.) SHOW LOCATION OF THE PROPOSED A/C UNIT IN THE SITE
 PLAN. PROVIDE SETBACK DIMENSIONS FOR THE A/C UNIT FROM
 THE PROPERTY LINE. PLEASE NOTE THAT THE A/C UNIT SHALL
 NOT PROJECT MORE THAN 4 FT. INTO A SETBACK. [ZLDR
 S.94-305(B)(4)]
  
 4.) THE VALUE OF THE CONSTRUCTION ($60,515) EXCEEDS 50
 PERCENT OF THE STRUCTURE'S VALUE ($78,235) ACCORDING TO
 THE P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE,
 PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY.
  
 REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS. PLEASE CONTACT LINDA LOUIE @ (561) 822-1458
 IF THERE ARE QUESTIONS.
  