Plan Review Details - Permit 16031120
Plan Review Stops For Permit 16031120
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-01-11 Cont ID  
Sent By cthroop Date 2017-01-11 Time 09:27 Rev Time 0.00
Received By cthroop Date 2017-01-11 Time 09:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-10-25 Cont ID  
Sent By cthroop Date 2016-10-25 Time 15:14 Rev Time 0.00
Received By cthroop Date 2016-10-25 Time 15:14 Sent To P
Notes
2016-10-25 15:18:08BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
  
 1. PROVIDE DESIGN WIND LOADS FOR EACH OPENING.
 2. DESIGNER OF RECORD TO SIGN PLANS.
  
 FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4). THE STRUCTURAL PROVISIONS OF
 THIS CODE FOR WIND LOADS ARE NOT PERMITTED WHERE WIND
 DESIGN IS REQUIRED AS SPECIFIED IN SECTION R301.2.1.1.
 WHERE DIFFERENT CONSTRUCTION METHODS AND STRUCTURAL
 MATERIALS ARE USED FOR VARIOUS PORTIONS OF A BUILDING,
 THE APPLICABLE REQUIREMENTS OF THIS SECTION FOR EACH
 PORTION SHALL APPLY. WHERE NOT OTHERWISE SPECIFIED, THE
 WIND LOADS LISTED IN TABLE R301.2(2) ADJUSTED FOR
 HEIGHT AND EXPOSURE USING TABLE R301.2(3) SHALL BE USED
 TO DETERMINE DESIGN LOAD PERFORMANCE REQUIREMENTS FOR
 WALL COVERINGS, CURTAIN WALLS, ROOF COVERINGS, EXTERIOR
 WINDOWS, SKYLIGHTS AND EXTERIOR DOORS (OTHER THAN
 GARAGE DOORS). WHERE LOADS FOR GARAGE DOORS ARE NOT
 OTHERWISE SPECIFIED, THE LOADS LISTED IN TABLE
 R301.2(4) ADJUSTED FOR HEIGHT AND EXPOSURE USING TABLE
 R301.2(3) SHALL BE USED TO DETERMINE DESIGN LOAD
 PERFORMANCE REQUIREMENTS. ASPHALT SHINGLES SHALL BE
 DESIGNED FOR WIND SPEEDS IN ACCORDANCE WITH SECTION
 R905.2.4. A CONTINUOUS LOAD PATH SHALL BE PROVIDED TO
 TRANSMIT THE APPLICABLE UPLIFT FORCES IN SECTION R802.2
 FROM THE ROOF ASSEMBLY TO THE FOUNDATION.
  
 FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-04-19 Cont ID  
Sent By cthroop Date 2016-04-19 Time 08:44 Rev Time 0.00
Received By cthroop Date 2016-04-19 Time 08:34 Sent To P
Notes
2016-04-19 08:48:441ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 1. WIND LOAD CALC'S ON PG. A-1 BASED ON WRONG CODE
 EDITION.
 2. PROVIDE WINDLOAD CALC'S BASED ON THE FBC 2014.
 3. PROVIDE WINDOW AND DOOR SCHEDULE.
 4. CANNOT READ CONNECTOR SCHEDULE ON PG. S-1.
  
 FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-10-11 Cont ID  
Sent By vperez Date 2016-10-11 Time 10:52 Rev Time 0.00
Received By vperez Date 2016-10-11 Time 10:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-29 Cont ID  
Sent By vperez Date 2016-03-29 Time 08:36 Rev Time 0.00
Received By vperez Date 2016-03-29 Time 08:15 Sent To  
Notes
2016-03-29 08:36:46INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. SEE FBC RES 314 SMOKE ALARM REQUIREMENTS PER
 ALTERATION. PROVIDE SMOKE DETECTORS TO COMPLY AT THE
 EXTERIOR OF BEDROOM #3 ENTRANCE.
 2. SHOW A DISCONNECT SWITCH FOR THE NEW GAS WATER
 HEATER. FBC RES E4101.5
 3. PROVIDE DATA CUT SHEET FOR THE NEW GAS WATER HEATER
 TO VERIFY RATINGS. FBC 107.3.5
 4. FEEL FREE TO CONTACT ME AT THE NUMBER LISTED BELOW
 SHOULD YOU HAVE ANY QUESTIONS OR CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2017-01-06 Cont ID  
Sent By gjohnson Date 2017-01-06 Time 16:32 Rev Time 0.00
Received By gjohnson Date 2017-01-06 Time 16:32 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2016-10-25 Cont ID  
Sent By gjohnson Date 2016-10-25 Time 15:38 Rev Time 0.00
Received By gjohnson Date 2016-10-25 Time 15:38 Sent To  
Notes
2016-10-25 15:39:29GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
 GAS PERMIT APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF
 THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS
 BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED
 PER NFPA 58 SECTION 3-2.2.7(H).
  
 12. EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE TO BE BELOW
 CEILING. MANUAL SHUT OFF VALVE TO BE UPSTREAM. UNION TO
 BE DOWN STREAM OF MANUAL VALVE.
  
 ANY QUESTIONS REGARDING THESE REQUIREMENTS MAY BE
 REFERRED TO:
  
  
  
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-04-21 Cont ID  
Sent By gjohnson Date 2016-04-21 Time 16:08 Rev Time 0.00
Received By gjohnson Date 2016-04-21 Time 16:08 Sent To  
Notes
2016-04-21 16:17:11GAS PERMIT APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF
 THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS
 BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED
 PER NFPA 58 SECTION 3-2.2.7(H).
  
 12. EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE TO BE BELOW
 CEILING. MANUAL SHUT OFF VALVE TO BE UPSTREAM. UNION TO
 BE DOWN STREAM OF MANUAL VALVE.
  
 ANY QUESTIONS REGARDING THESE REQUIREMENTS MAY BE
 REFERRED TO:
  
  
  
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2016-10-11 Cont ID  
Sent By destabro Date 2016-10-11 Time 15:21 Rev Time 0.00
Received By destabro Date 2016-10-11 Time 15:21 Sent To B
Notes
2016-10-11 15:23:1110/11/2016 - PROPOSED WORK MATCHES APPROVED WORK UNDER
 HPB CASE NO.16-16. DLE

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2016-04-12 Cont ID  
Sent By fmittner Date 2016-04-12 Time 08:51 Rev Time 0.00
Received By destabro Date 2016-04-12 Time 08:51 Sent To  
Notes
2016-04-12 08:52:33HPB CASE 16-16 - PROPOSED WORK (WINDOW
 REPLACEMENT/NARROW FRONT WINDOWS INFILL) APPROVED BY
 HISTORIC REVIEW BOARD ON MARCH 29, 2016 - DLE - 4/12/16

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-01-11 Cont ID  
Sent By cthroop Date 2017-01-11 Time 09:27 Rev Time 0.00
Received By cthroop Date 2017-01-06 Time 16:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-25 Cont ID  
Sent By gjohnson Date 2016-10-25 Time 15:43 Rev Time 0.00
Received By gjohnson Date 2016-10-03 Time 09:51 Sent To  
Notes
2016-10-04 09:52:03R08

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-21 Cont ID  
Sent By gjohnson Date 2016-04-21 Time 16:21 Rev Time 0.00
Received By gjohnson Date 2016-03-24 Time 08:41 Sent To  
Notes
2016-03-25 08:42:01R01

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-01-06 Cont ID  
Sent By gjohnson Date 2017-01-06 Time 16:33 Rev Time 0.00
Received By gjohnson Date 2017-01-06 Time 16:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-10-25 Cont ID  
Sent By gjohnson Date 2016-10-25 Time 15:40 Rev Time 0.00
Received By gjohnson Date 2016-10-25 Time 15:40 Sent To  
Notes
2016-10-25 15:43:07PLUMBING COMMENTS:
  
 1. PROVIDE A DETAILED SCOPE OF PLUMBING WORK TO BE
 DONE. SCOPE OF WORK ON PLANS STATES NO PLUMBING WORK
 PLAN INDICATES NEW KIT SINK AND NEW TANKLESS HEATER
 PLEASE CLARIFY.
 PER WPB AMEND. 107.2.1
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 2ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-04-21 Cont ID  
Sent By gjohnson Date 2016-04-21 Time 15:57 Rev Time 0.00
Received By gjohnson Date 2016-04-21 Time 15:39 Sent To  
Notes
2016-04-21 16:08:41PLUMBING COMMENTS:
  
 1. PROVIDE A DETAILED SCOPE OF PLUMBING WORK TO BE
 DONE.
 PER WPB AMEND. 107.2.1
  
 2.PROVIDE EXISTING LOCATION OF WATER HEATER.
 PER WPB AMEND. 107.2.1
  
 3. IF MOVING STACK FOR KITCHEN SINK PROVIDE A RISER
 DIAGRAM.
 PER WPB AMEND. 107.3.5.3(11)
  
 4. IT SHOWS A STORAGE TANK TYPE WATER HEATER ON PLAN OR
 ARE YOU USING A TANKLESS WATER HEATER PLEASE CLARIFY.
 PER WPB AMEND. 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  