Plan Review Details - Permit 16031067
Plan Review Stops For Permit 16031067
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-28 Cont ID  
Sent By mvaldes Date 2016-03-28 Time 09:24 Rev Time 0.00
Received By mvaldes Date 2016-03-28 Time 09:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-24 Cont ID  
Sent By mvaldes Date 2016-03-24 Time 11:15 Rev Time 0.00
Received By mvaldes Date 2016-03-24 Time 11:15 Sent To  
Notes
2016-03-24 11:26:33REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 - PROVIDE EXISTING DWELLING UNIT LOAD CALCULATIONS WBA
 107.3.5.3, GROUNDING DETAIL ON RISER DIAGRAM TO INCLUDE
 GROUNDING ELECTRODE SIZE NEC 250.66 AND INTERSYSTEM
 BONDING TERMINAL STRIP NEC 250.94
  
 - PROVIDE GENERAL ELECTRICAL NOTES STATING NEC 300.5
 PROTECTION FROM PHYSICAL DAMAGE EMERGING FROM GRADE (
 PVC SCH 80 ) , WARNING RIBBON PLACED OVER TRENCH, AND
 RACEWAY SEAL FOR SERVICE CONDUCTORS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-28 Cont ID  
Sent By mvaldes Date 2016-03-28 Time 09:25 Rev Time 0.00
Received By mvaldes Date 2016-03-25 Time 14:26 Sent To  
Notes
2016-03-25 14:26:31RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-24 Cont ID  
Sent By mvaldes Date 2016-03-24 Time 11:26 Rev Time 0.00
Received By mvaldes Date 2016-03-23 Time 09:05 Sent To  
Notes
2016-03-24 09:05:59ELEC <5K