2016-03-24 06:15:56 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16030967 |
| ADD: 1631 42ND ST. |
| CONT: ALPHA SOUTH CONSTRUCTION |
| TEL: 561-306-3183 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. MARCH 24/ 2016 |
| ACTION: DENIED |
| |
| 1) THE CONTRACTOR SUBMITTED A MIAMI-DADE NOA 14-0224.03 |
| CERTAIN TEED MODIFIED BITUMEN ROOF SYSTEMS OVER WOOD |
| DECK. THE CONTRACTOR DID NOT IDENTIFY WHICH SUB-SYSTEM |
| AND ASSOCIATED PRESSURE WAS GOING TO BE USED IN THE |
| INSTALLATION. |
| FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING |
| SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF |
| ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF |
| ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3. IF |
| SO RAS 117 CALCULATIONS ARE REQUIRED BY EITHER A |
| FLORIDA ARCHITECT OR ENGINEER. 107.2.1.3 ADDITIONAL |
| INFORMATION IS REQUIRED TO DETERMINE CODE COMPLIANCE. |
| 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| |
| 2) THIS INFORMATION CAN BE E-MAILED TO THE ADDRESS |
| BELOW. |
| |