Plan Review Details - Permit 16030881
Plan Review Stops For Permit 16030881
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-05-11 Cont ID  
Sent By vperez Date 2016-05-11 Time 09:18 Rev Time 0.00
Received By vperez Date 2016-05-11 Time 09:18 Sent To  
Notes
2016-05-11 09:19:083RD ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PROVISO TO PROVIDE AS-BUILT TO REFLECT UPDATED
 GOVERNING CODES AS STATED ABOVE AND ITEMS LISTED BELOW.
 2. SHOW GROUNDING ELECTRODE CONDUCTOR SIZE AT THE
 SERVICE PER SERVICE CHANGE. #2 GEC PER NEC 250.66
 TABLE.
 3. PROVIDE AN INTERSYSTEM BONDING CONNECTION. NEC
 250.94
 4. LABEL MAINS PER NEC 230.2 FOR ALL 100A BREAKERS
 SHOWN AT THE METER GANG BOX. EXAMPLE MAIN #1 OF 4, 2 OF
 4, ETC.
 5. PER FBC RES 315- PROVIDE SD/CO MONOXIDE DETECTORS ON
 THE EXTERIOR OF ROOMS.
 6. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-04-04 Cont ID  
Sent By albarran Date 2016-04-04 Time 17:40 Rev Time 0.00
Received By albarran Date 2016-04-04 Time 14:04 Sent To  
Notes
2016-04-04 18:02:54ELECTRICAL REVIEW COMMENTS
 REVIEWED FOR COMPLIANCE WITH:
 2010 FBC & 2008 NEC
  
 CORRECTIONS REQUIRED:
 1. THIS IS A LEVEL 2 ALTERATION OF AN R2 OCCUPANCY.
 2. HOW DID THE ELECTRICAL GO FROM WHAT WAS PRESENTED ON
 THE INITIAL PLAN APPROVED ON 4/9/15 TO THE PLAN
 SUBMITTED ON 3/21/16. THE INITIAL PLANS SHOW THE
 ELECTRIC PANEL INSIDE THE UNIT AND THE NEW ONE HAS THE
 PANEL IN THE ELECTRIC ROOM.
 3. DO ALL OF THE UNITS HAVE GAS OR ELECTRIC COOKING
 APPLIANCES. IF ELECTRIC, THE RESPECTIVE LOAD SHALL
 APPEAR ON THE LOAD CALCS.
 4. DOES EACH UNIT HAVE AN INDEPENDENT WATER HEATER OR
 IS THERE A COMMON UNIT. THE SAME ARISES, ARE THEY GAS
 OR ELECTRIC. IF ELECTRIC THE LOAD SHALL APPEAR ON THE
 LOAD CALCS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-22 Cont ID  
Sent By rmcdouga Date 2016-03-22 Time 16:52 Rev Time 0.00
Received By albarran Date 2016-03-22 Time 16:07 Sent To I
Notes
2016-03-22 17:13:12TRYING TO GET THE SCOPE OF WORK I LOOKED AT THE
 VERBIAGE ON THE PERMIT. IT DIDN'T MATCH THE DRAWING
 WHICH PROMPTED ME TO GO INTO FILENET TO DIG IN FURTHER.
 IN DOING SO I NOTICED THAT THE INITIAL PERMIT
 APPLICATION DID NOT CONCUR WITH THE APPROVED PLANS, BUT
 FURTHER THE DRAWINGS WERE SUFFICIENTLY DIFFERENT THAT I
 CONTACTED THE ENGINEER OF RECORD TO DISCUSS THE MATTER.
 WE DISCUSSED THE THIS AND MR. ROJAS WILL SUBMIT
 CORRECTED DRAWINGS FOR REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-05-11 Cont ID  
Sent By vperez Date 2016-05-11 Time 09:19 Rev Time 0.00
Received By vperez Date 2016-05-11 Time 09:19 Sent To  
Notes
2016-05-10 14:29:56RESUB OF REVISION ROUTED TO ELEC <5K

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-04 Cont ID  
Sent By albarran Date 2016-04-04 Time 18:03 Rev Time 0.00
Received By albarran Date 2016-04-01 Time 16:00 Sent To  
Notes
2016-04-04 18:05:38I SPOKE W/SAM FISH AND EXPLAINED THE REQUIRED
 CORRECTIONS TO HIM. I ADVISED HIM THAT THIS WILL BE IN
 THE DENIED BIN "B" WAITING FOR A RESUBMITTAL. MA
  
2016-04-01 16:00:45RESUB ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-22 Cont ID  
Sent By albarran Date 2016-03-22 Time 17:13 Rev Time 0.00
Received By albarran Date 2016-03-21 Time 15:23 Sent To  
Notes
2016-03-22 17:15:153/22/16 FAILED ELECTRICAL REVIEW AS NOTED. ENGINEER
 NOTIFIED VIA PHONE CONVERSATION. SENT FILE TO SMALL
 DENIED BIN "B'". MA
2016-03-21 17:29:24REVISION SHOWS FOUR METERS IN AN ELECTRIC ROOM. NO
 LONGER A TWO FAMILY DWELLING. GAVE TO M. ALBERRAN FOR
 REVIEW. RM
2016-03-21 15:24:10REVISION ROUTED TO RMCDOUGAL