Plan Review Details - Permit 16030757
Plan Review Stops For Permit 16030757
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-04-29 Cont ID  
Sent By cthroop Date 2016-04-29 Time 10:23 Rev Time 0.00
Received By cthroop Date 2016-04-29 Time 10:23 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-31 Cont ID  
Sent By cthroop Date 2016-03-31 Time 11:55 Rev Time 0.00
Received By cthroop Date 2016-03-31 Time 11:55 Sent To P
Notes
2016-03-31 11:57:181ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 1. PLUMBING PERMIT REQUIRED.
 2. IDENTIFY LOCATION OF NEW DRYWALL.
 3. STATE R-VALUE OF NEW INSULATION.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-04-29 Cont ID  
Sent By vperez Date 2016-04-29 Time 08:35 Rev Time 0.00
Received By vperez Date 2016-04-29 Time 08:35 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-21 Cont ID  
Sent By vperez Date 2016-03-21 Time 08:20 Rev Time 0.00
Received By vperez Date 2016-03-21 Time 08:20 Sent To B
Notes
2016-03-21 08:21:03INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. ELECTRICAL SHEET- PLEASE UPDATE ALL REFERENCES TO
 REFLECT CURRENT BUILDING CODES. FLORIDA BUILDING CODE
 2014 5TH EDITION FAMILY, NEC 2011.
 2.PLEASE CLARIFY ELECTRICAL SCOPE AND LABEL PLANS
 ACCORDINGLY. LABEL NEW OR EXISTING FOR EXAMPLE INTERIOR
 DEVICES. FBC 107.3.5
 3.ELECTRICAL CONTRACTOR TO SIGN AND NOTARIZED SIGNATURE
 ON DRAWINGS IF NO DESIGNER OF RECORD IS SHOWN FOR THIS
 PROJECT. ELECTRICAL PERMIT REQUIRED
 4.SHOW PROPER SPACING AT THE KITCHEN LOCATION AND
 THROUGHOUT SCOPE. PER FBC RES E3901- WALL SPACE
 REQUIREMENTS AND COUNTERTOP WALL SPACE IN KITCHEN AREA.
 5.SHOW THE SMOKE DETECTORS LAYOUT PER FBC RES 314
 REQUIREMENTS
 6.NEW SLIDING GLASS DOOR, PLEASE CLARIFY IF THERE IS AN
 EXISTING SWITCH AND LIGHTING OUTLET TO COMPLY WITH FBC
 RES E3903, IF NOT SHOW ON DRAWINGS.
 7.TAMPER RESISTANT RECEPTACLES REQUIRED, PROVIDE A NOTE
 TO COMPLY. FBC RES E4002.14
 8.FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. FEEL FREE
 TO CONTACT ME AT THE NUMBER LISTED BELOW SHOULD YOU
 HAVE ANY QUESTIONS OR CONCERNS.
  
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-05-03 Cont ID  
Sent By tklarge Date 2016-05-03 Time 11:56 Rev Time 0.00
Received By tklarge Date 2016-04-28 Time 16:25 Sent To  
Notes
2016-04-28 16:25:52RESUB ROUTED TO VPEREZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-04 Cont ID  
Sent By tklarge Date 2016-04-04 Time 05:14 Rev Time 0.00
Received By tklarge Date 2016-04-04 Time 05:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-31 Cont ID  
Sent By cthroop Date 2016-03-31 Time 11:52 Rev Time 0.00
Received By cthroop Date 2016-03-17 Time 14:01 Sent To  
Notes
2016-03-31 11:54:46CLOSED I-STOP BY MISTAKE. WILL OPEN NEW I-STOP. SENT TO
 PLUMBING. CST
2016-03-17 14:02:14ROUTED TO ELECTRICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-05-03 Cont ID  
Sent By skennedy Date 2016-05-03 Time 12:04 Rev Time 0.00
Received By skennedy Date 2016-05-03 Time 12:04 Sent To  
Notes
2016-05-03 12:12:42NO PLAN SUBMITTED, REVISION REQUIRED. APPROVED TO
 EXPEDITE FIRE REPAIR.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-05-03 Cont ID  
Sent By tklarge Date 2016-05-03 Time 11:56 Rev Time 0.00
Received By tklarge Date 2016-05-02 Time 04:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-04-04 Cont ID  
Sent By tklarge Date 2016-04-04 Time 05:14 Rev Time 0.00
Received By tklarge Date 2016-04-04 Time 05:10 Sent To  
Notes
***NONE***