Plan Review Details - Permit 16030654
Plan Review Stops For Permit 16030654
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-05-23 Cont ID  
Sent By mvaldes Date 2016-05-23 Time 12:05 Rev Time 0.00
Received By mvaldes Date 2016-05-23 Time 12:05 Sent To  
Notes
2016-05-23 12:12:09PROVISO
  
 NEC 225.37 PROVIDE ALL REQUIRED IDENTIFICATION PLAQUES
  
 NEC 250.94 INTERSYTEM BONDING TERMINAL.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-04-22 Cont ID  
Sent By albarran Date 2016-04-22 Time 12:17 Rev Time 0.00
Received By albarran Date 2016-04-22 Time 11:29 Sent To I
Notes
2016-04-22 12:17:57FAILED 2ND ELECTRICAL REVIEW
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION OF THE FBC 2014 & NFPA 70 (NEC) 2011
 EDITION
  
 CORRECTIONS REQUIRED:
 AS INSTRUCTED IN THE EMAIL ENCLOSED WITH THE SUBMITTAL
 YOU TOLD TO PROVIDE A SITE PLAN INDICATING THE LOCATION
 OF THE SERVICE EQUIPMENT ON THE PROPERTY. YOU WERE
 INSTRUCTED TO SUBMIT PROPER LOAD CALCS WHICH ARE A PART
 OF THE FEEDER DIAGRAM AS MENTIONED ON NEC 215.5.
 LOOKING AT THE PROPERTY RECORDS, THERE APPEARS TO BE
 TWO BLDGS. ON THE PROPERTY REMEMBER THAT THE NEC
 REQUIRES THAT ALL DISCONNECTS BE GROUPED TOGETHER.
 FURTHERMORE, UNLESS THERE IS A COMMON LAUNDRY FACILITY
 THERE SHALL BE A LAUNDRY CIRCUIT CALCULATED INTO THE
 LOAD OF EACH UNIT. THE SAME HOLDS TRUE FOR THE
 EMERGENCY LIGHTING REQUIRED FOR THE STAIRS. YOU WERE
 ALSO ASKED TO INCLUDE THE SCOPE OF WORK ON THE
 DRAWINGS. THE RISER DIAGRAM MEANS NOTHING WITHOUT KNOW
 WHAT IT IS MEANT FOR. YOU DID INCLUDE THE JOB ADDRESS
 AND THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-15 Cont ID  
Sent By albarran Date 2016-03-15 Time 15:52 Rev Time 0.00
Received By albarran Date 2016-03-15 Time 15:51 Sent To  
Notes
2016-03-15 16:09:19THIS CUSTOMER CALLED ME ON THE PHONE ASKING WHAT HE
 WOULD NEED FOR THIS PERMIT AND I CLEARLY TOLD HIM WHAT
 I WANTED:
 1. A SITE PLAN SHOWING THE LOCATION OF THE SERVICE ON
 THE HOUSE. (I WAS LED TO BELIEVE THAT HE HAD PURCHASED
 TWO SFR NOT A MULTI-DWELLING UNIT.
 2. A SITE SPECIFIC RISER DIAGRAM, SHOWING CONDUCTOR
 SIZING, OVER CURRENT PROTECTION AND PROPER GROUNDING
 PER NEC 250.66
 3. SCOPE OF WORK SHALL BE DEFINED ON THE DRAWING AND
 JOB ADDRESS.
 4. THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DRAWING SHALL BE ON THE DRAWING
 ON THE OTHER HAND, IF THIS IS A MULTI-DWELLING UNIT, IT
 IS NOW A COMMERCIAL INSTALLATION AND THEREFORE IN
 ADDITION TO THE ABOVE,
 1. INDIVIDUAL UNIT LOAD CALCS TO VERIFY PROPER SERVICE
 SIZING.
 2. EVERY METER SOCKET SHALL BE MARKED WITH THE NUMBER
 OF THE UNIT IT SERVES.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-05-23 Cont ID  
Sent By mvaldes Date 2016-05-23 Time 12:05 Rev Time 0.00
Received By mvaldes Date 2016-05-20 Time 14:14 Sent To  
Notes
2016-05-20 14:14:57RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-22 Cont ID  
Sent By albarran Date 2016-04-22 Time 12:41 Rev Time 0.00
Received By albarran Date 2016-04-20 Time 10:06 Sent To  
Notes
2016-04-22 12:42:234/22/16 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA PHONE FOR LACK OF LISTED EMAIL ADDRESS.
 SENT FILE TO SMALL DENIED BIN "O". MA
2016-04-21 10:06:20RESUB ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-15 Cont ID  
Sent By albarran Date 2016-03-15 Time 16:25 Rev Time  
Received By albarran Date   Time   Sent To  
Notes
2016-03-15 16:26:563-15-16 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. FILE SENT TO SMALL DENIED BIN "O".
 MA