Plan Review Details - Permit 16030582
Plan Review Stops For Permit 16030582
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-03-21 Cont ID  
Sent By jwitmer Date 2016-03-21 Time 08:21 Rev Time 0.00
Received By jwitmer Date 2016-03-21 Time 07:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-31 Cont ID  
Sent By mvaldes Date 2016-03-31 Time 10:20 Rev Time 0.00
Received By mvaldes Date 2016-03-31 Time 10:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-17 Cont ID  
Sent By mvaldes Date 2016-03-17 Time 13:02 Rev Time 0.00
Received By mvaldes Date 2016-03-17 Time 13:02 Sent To  
Notes
2016-03-17 13:41:23JOB PERMIT NUMBER: 16030582
 JOB ADDRESS: 701 S OLIVE AVE
 WEST PALM BEACH FLORIDA
 DATE: MARCH 17 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - COMPLY WITH THE CURRENT APPLICABLE CODES ACCEPTABLE
 TO THE CITY OF WEST PALM BEACH BUILDING DEPARTMENT
 WHICH ARE NEC 2011 & FBC 2014 5TH EDITION.
 - CLARIFY AND SPECIFY IF SMOKE ALARMS ARE INSTALLED BY
 SECTIONS 314 / 315 OF THE RESIDENTIAL CODE? IF EXISTING
 PLEASE MAKE A NOTE. SAME APPLIES WITH AFCI PROTECTION
 NEC 210.12 B
 - NEW LIGHTING SHALL BE 75 % HIGH EFFICIENCY IC RATED
 AS WELL AS SEALED (2CFM) TO NOT COMPROMISE THERMAL
 ENVELOPE.
 - NEC 680.73 ACCESSIBILITY OF CORD AND PLUG RECEPTACLE
 FOR HYDRO MASSAGE TUB SHALL BE WITHIN 1 FT OF OPENING.
 - NEC 422.31 STEAM UNIT REQUIRES DISCONNECT WITHIN
 SIGHT OR BREAKER LOCK CAPABLE OF BEING LOCKED IN THE
 OPEN POSITION.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-03-16 Cont ID  
Sent By pleduc Date 2016-03-16 Time   Rev Time 0.00
Received By pleduc Date 2016-03-16 Time 16:25 Sent To  
Notes
2016-03-16 16:36:04THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1. THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF
 THE SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE.
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS REQUIRE AN
 EVALUATION BY A FIRE SPRINKLER CONTRACTOR.
  
 2. IF EXISTING, THE FIRE ALARM SYSTEM SHALL REMAIN
 ACTIVE THROUGHOUT THE CONSTRUCTION PERIOD.
  
 3. ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE
 DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE
 SAFETY CONTRACTORS.
  
 4. ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEM,
 EXCEEDS 4 HOURS, A FIRE WATCH SHALL BE IMPLEMENTED AND
 MAINTAINED UNTIL FULL AND COMPLETE PROTECTION IS
 RETURNED.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-31 Cont ID  
Sent By mvaldes Date 2016-03-31 Time 10:20 Rev Time 0.00
Received By mvaldes Date 2016-03-30 Time 11:14 Sent To  
Notes
2016-03-30 11:14:54RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-25 Cont ID  
Sent By lmarchan Date 2016-03-25 Time 08:14 Rev Time 0.00
Received By lmarchan Date 2016-03-14 Time 10:24 Sent To  
Notes
2016-03-15 10:25:02B01

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-03-21 Cont ID  
Sent By jwitmer Date 2016-03-21 Time 07:42 Rev Time 0.00
Received By jwitmer Date 2016-03-21 Time 07:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2016-03-24 Cont ID  
Sent By jvalido Date 2016-03-24 Time 18:27 Rev Time 0.00
Received By jvalido Date 2016-03-24 Time 18:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-03-24 Cont ID  
Sent By gjohnson Date 2016-03-24 Time 15:56 Rev Time 0.00
Received By gjohnson Date 2016-03-24 Time 15:56 Sent To  
Notes
***NONE***