Plan Review Details - Permit 16030508
Plan Review Stops For Permit 16030508
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-04-05 Cont ID  
Sent By jwitmer Date 2016-04-05 Time 09:01 Rev Time 0.00
Received By jwitmer Date 2016-04-05 Time 07:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-21 Cont ID  
Sent By jwitmer Date 2016-03-21 Time 10:45 Rev Time 0.00
Received By jwitmer Date 2016-03-21 Time 08:41 Sent To  
Notes
2016-03-21 10:45:23BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030508
 ADD: 477 S. ROSEMARY SUITE # 230
 CONT: TBD
 TEL: 684-6844/ NIKI BENNETT
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. MARCH 21/2016
 ACTION: DENIED
  
 1) PLEASE REVIEW SHEET 004_A1.0 CORRIDOR 206 AND SHEET
 16044_M1_1. PLEASE REVIEW 2014 FBC-B 1018.5 AIR
 MOVEMENT IN CORRIDORS. CORRIDORS SHALL NOT SERVE AS
 SUPPLY, RETURN, EXHAUST, RELIEF OR VENTILATION AIR
 DUCTS. THE MECHANICAL PLANS SHOW THE RETURN AIR IS
 BEING PULLED DOWN THRU THE CEILING ABOVE INTO THE
 CORRIDOR AND INTO THE AIR HANDLER CLOSET 209. THE DOOR
 SCHEDULE INDICATES THIS DOOR IS A WOOD LOUVERED DOOR.
 THE 2014 FBC-M DOES NOT ALLOW COMBUSTIBLE MATERIALS
 WITHIN PLENUMS. THE SAME ISSUE WITH DOOR 224B, NO
 COMBUSTIBLES ALLOWED WITHIN PLENUMS.
  
 NOTE FBC-B 1018.5 EXC. # 3 IS FOR OFFICES LESS THAN
 1,000 SQ. FT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-04-06 Cont ID  
Sent By albarran Date 2016-04-06 Time 13:47 Rev Time 0.00
Received By albarran Date 2016-04-04 Time 18:49 Sent To  
Notes
2016-04-06 13:49:10ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY CORRECTED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-03-29 Cont ID  
Sent By albarran Date 2016-03-29 Time 09:43 Rev Time 0.00
Received By albarran Date 2016-03-29 Time 07:58 Sent To  
Notes
2016-03-29 09:45:36REVIEW COMPLETED AFTER RECEIVING THE MISSING E1.1.
 GLIDDEN SPINA, CP, LEM & SAK NOTIFIED VIA EMAIL. MA

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-22 Cont ID  
Sent By albarran Date 2016-03-22 Time 12:55 Rev Time  
Received By albarran Date 2016-03-18 Time 12:02 Sent To  
Notes
2016-03-22 12:56:201ST ELECTRICAL REVIEW NOTES FOR REVISION #:16030508
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014
 NFPA 70 2011 (NEC)
  
 CORRECTIONS REQUIRED:
 SHEET E0.1
 1. DEMOLITION NOTES 10 HAVE UNDEFINED CODE QUOTED. SEE
 CURRENT ADOPTED APPLICABLE CODE WHICH MAY NOT
 NECESSARILY BE THE LATEST EDITIONS.
 2. SHEET E1.1 ELECTRICAL POWER PLAN IS MISSING. PLEASE
 PROVIDE THIS SHEET FOR REVIEW. PLEASE NOTE THAT THE
 FAILURE TO INCLUDE THIS SHEET IN THE INITIAL SUBMITTAL
 MAY CREATE THE NEED FOR A SECOND RESUBMITTAL AS THIS
 PAGE IS REVIEWED.
 SHEET E2.1
 1. IN ADDITION TO THE LIGHTING CONTROLLED MENTIONED.
 COMPLIANCE W/FBC-EC405.2.2.3 DAYLIGHT ZONES SHALL BE
 CONTROLLED SEPARATELY.
 2. FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES.
 SHEET E3.1
 1. NEC 110.16 ARC-FLASH HAZARD WARNING LABELS REQUIRED
 ON ALL ELECTRICAL APPARATUS.
 2. NEC 110.24 MAXIMUM AVAILABLE FAULT CURRENT SHALL BE
 DURABLY MARKED AND DATED ON ALL ELECTRICAL APPARATUS.
 3. NEC 408.4(B) ALL SWITCHBOARDS AND PANELBOARDS
 SUPPLIED BY A FEEDER IN OTHER THAN A ONE OR TWO FAMILY
 DWELLING SHALL BE MARKED TO INDICATE THE LOCATION AND
 TYPE OF THE SOURCE OF POWER.
 SHEET E5.1
 1. INCLUDE THE PROPOSED FIRE STOPPING DETAIL FOR
 ELECTRICAL OUTLET BOX IN A RATED WALL.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-04-05 Cont ID  
Sent By scaldero Date 2016-04-05 Time 12:25 Rev Time 0.00
Received By scaldero Date 2016-04-05 Time 12:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-03-21 Cont ID  
Sent By scaldero Date 2016-03-21 Time 16:16 Rev Time 0.00
Received By scaldero Date 2016-03-21 Time 16:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-18 Cont ID  
Sent By skennedy Date 2016-04-18 Time 11:41 Rev Time 0.00
Received By skennedy Date 2016-03-30 Time 09:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-24 Cont ID  
Sent By lmarchan Date 2016-03-24 Time 14:43 Rev Time 0.00
Received By lmarchan Date 2016-03-16 Time 17:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-04-05 Cont ID  
Sent By ccole Date 2016-04-04 Time 17:13 Rev Time 0.00
Received By ccole Date 2016-04-04 Time 17:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-03-21 Cont ID  
Sent By ccole Date 2016-03-21 Time 15:23 Rev Time 0.00
Received By ccole Date 2016-03-21 Time 15:23 Sent To  
Notes
2016-03-21 15:28:531ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030508
 3/21/16
  
 1) THE SUMMARY AC CALCULATIONS REQUIRE AN ENGINEERS
 SIGNATURE AND SEAL PER SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION. PLEASE CLARIFY WHY THERE IS NO
 VENTILATION AIR FOR OCCUPANTS SHOWN ON THE CALCS.
 2) PROVIDE A DOOR SCHEDULE THAT INDICATES THE TYPE OF
 AND SIZE OF LOUVERED DOORS AT THE AC CLOSETS- REFER TO
 SECTION C403.2.7.2 FBC-14 ENERGY CONSERVATION.
 3) THE CORRIDOR (HALLWAY 206) CANNOT SERVE AS A RETURN
 AIR DUCT FOR AHU-2- SEE SECTION 601.2 FBC-14
 MECHANICAL.
 4) THE AC SCHEDULE INDICATES A TOTAL OF 1600 CFM'S OF
 SUPPLY AIR FOR AHU-2, HOWEVER THE PLAN SHOWS A TOTAL OF
 1795 CFM'S BEING DISTRIBUTED IN THE ZONE.
 5) ALL NEW DUCT SMOKE DETECTORS SHALL BE INSTALLED IN
 THE RETURN AIR SYSTEMS OF THE AIR HANDLERS PER SECTION
 606.2.1 FBC-14 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-04-06 Cont ID  
Sent By gjohnson Date 2016-04-06 Time 15:01 Rev Time 0.00
Received By gjohnson Date 2016-04-06 Time 13:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-03-24 Cont ID  
Sent By gjohnson Date 2016-03-24 Time 13:04 Rev Time 0.00
Received By gjohnson Date 2016-03-23 Time 15:14 Sent To  
Notes
2016-03-24 13:26:321ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1.SHOW DISTANCE T DRINKING FOUNTAIN TO COMPLY WITH FBC
 PL SEC. 403.5
  
 2. EXISTING PRINTS SHOW THE SPACE AS MIXED OCCUPANCY
 RESIDENTIAL AND BUSINESS NOW ITS JUST BUSINESS WHICH
 MAKES THIS A CHANGE OF OCCUPANCY PLEASE CLARIFY.
 PER WPB AMEND. TO FBC SEC 107.2.1
  
 3. SHOW COMPLIANCE FOR GRAB BARS TO COMPLY WITH FBC
 ACC. SEC 604.5.1-604.5.2
  
 4. PROVIDE RISER DIAGRAM FOR WOMENS BATHROOMS PER WPB
 AMEND TO FBC 107.3.5.1.3(13)
  
 5. PROVIDE HOT WATER FOR LAVS TO COMPLY WITH FBC PL SEC
 607.1

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2016-04-18 Cont ID  
Sent By skennedy Date 2016-04-18 Time 11:41 Rev Time 0.00
Received By skennedy Date 2016-04-18 Time 11:41 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-04-14 Cont ID  
Sent By eschneid Date 2016-04-14 Time 13:41 Rev Time 0.50
Received By eschneid Date 2016-04-14 Time 13:41 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-03-24 Cont ID  
Sent By eschneid Date 2016-03-24 Time 14:36 Rev Time 0.25
Received By eschneid Date 2016-03-24 Time 14:36 Sent To  
Notes
***NONE***