Plan Review Details - Permit 16030431
Plan Review Stops For Permit 16030431
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-06-08 Cont ID  
Sent By jwitmer Date 2016-06-08 Time 13:56 Rev Time 0.00
Received By jwitmer Date 2016-06-08 Time 13:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-22 Cont ID  
Sent By jwitmer Date 2016-03-22 Time 09:58 Rev Time 0.00
Received By jwitmer Date 2016-03-22 Time 08:00 Sent To  
Notes
2016-03-22 09:02:59BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030431
 ADD: 1200 S. FLAGLER DR./ ROOF TOP EQUIPMENT
 CONT: HILL YORK SERVICES
 TEL: 561-689-7355
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 22/ 2016
 ACTION: DENIED
  
 1) SHEET S1 THE GENERAL DESIGN NOTE # 5 INDICATES THE
 CONTRACTOR TO ATTACH THE NEW ROOF TOP UNIT PER THE
 MANUFACTURERS SPECIFICATION. THE MANUFACTUTURERS
 SPECIFICATION FOR THE ATTACHMENT OF THE NEW ROOF TOP
 UNIT HAD NOT SUBMITTED ANY CALCULATIONS FOR THE
 ATTACHMENT OF THE NEW UNIT TO THE
 ELEVATED STEEL STAND. PLEASE SHOW COMPLIANCE WITH:
  
 2014 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON
 STRUCTURAL MEMBERS AND THEIR CONNECTIONS SHALL BE
 DETERMINED BY METHODS OF STRUCTURAL ANALYSIS THAT TAKE
 INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC
 COMPATIBILITY AND BOTH SHORT- AND LONG-TERM MATERIAL
 PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED TO RESIST
 THE OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS?
  
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2) THE ENGINEERING CALCULATIONS FOR THE ATTACHMENT
 METHOD OF THE NEW ROOF TOP UNIT TO THE STEEL STAND BY A
 DELEGATE ENGINEER WILL NEED TO BE REVIEWED BY THE
 STRUCTURAL ENGINEER OF RECORD, VICTOR G. GARAYCOCHEA
 P.E., APPROVED AND SHOP DRAWING STAMP OF APPROVAL,
 BEFORE THE SUBMITTAL CAN BE SUBMITTED TO THE BUILDING
 DEPARTMENT.
  
 3) IF THERE IS TO BE ANY FIELD WIELDING COMPLETED ON
 SITE, CERTIFICATES WILL BE REQUIRED FOR THE
 QUALIFICATIONS OF A CERTIFIED WIELDER WILL ALSO BE
 REQUIRED.
  
 4) JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-06-06 Cont ID  
Sent By mvaldes Date 2016-06-06 Time 17:04 Rev Time 0.00
Received By mvaldes Date 2016-06-06 Time 16:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-21 Cont ID  
Sent By mvaldes Date 2016-03-21 Time 10:10 Rev Time 0.00
Received By mvaldes Date 2016-03-21 Time 10:10 Sent To  
Notes
2016-03-21 10:43:12REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 - ELECTRIC RISER TO INCLUDE FEEDER/BRANCH CIRCUIT WIRE
 SIZES AND CONDUIT DETAIL FROM ROOFTOP PANEL A TO AC
 DISCONNECT WBA 107.3.5.3
  
 - PROVIDE PANEL SCHEDULE WITH DEMAND LOADS ,AIC RATINGS
 OF EQUIPMENT & OCPD TO VERIFY IF LOAD CAPACITY MATCHES
 NAMEPLATE OF ROOFTOP CONDENSER UNIT. NEC 215.5 ,
 110.9/10 , 440
  
 - ELECTRICAL SUB-PERMIT IS REQUIRED PLEASE MAKE A NOTE
 FOR ARC-FLASH HAZARD WARNING LABEL AND AVAILABLE FAULT
 CURRENT MARKINGS. NEC 110.16 , 110.24
  
 - ADJUSTMENT FACTORS WILL BE TAKEN INTO CONSIDERATION
 FOR ALL RACEWAYS EXPOSED TO DIRECT SUNLIGHT ON TOP OF
 ROOFTOPS ACCORDING TO NEC TABLE 310.15 B3. A NOTE WILL
 SUFFICE.
  
 - PROVIDE A SERVICE RECEPTACLE GFCI PROTECTED WITHIN 25
 FT OR WITHIN SIGHT OF MECHANICAL EQUIPMENT. NEC 210.63
 , 210.8 B

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-08 Cont ID  
Sent By jwitmer Date 2016-06-08 Time 13:56 Rev Time 0.00
Received By jwitmer Date 2016-06-06 Time 14:06 Sent To  
Notes
2016-06-06 14:06:09RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-22 Cont ID  
Sent By cpuell Date 2016-03-22 Time 09:58 Rev Time 0.00
Received By jwitmer Date 2016-03-10 Time 11:10 Sent To  
Notes
2016-03-10 11:10:35ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-03-14 Cont ID  
Sent By jvalido Date 2016-03-14 Time 16:42 Rev Time 0.00
Received By jvalido Date 2016-03-14 Time 16:41 Sent To  
Notes
2016-03-14 17:24:11BLDG MISC 2