Plan Review Details - Permit 16030381
Plan Review Stops For Permit 16030381
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-03-23 Cont ID  
Sent By jwitmer Date 2017-03-23 Time 09:13 Rev Time 0.00
Received By jwitmer Date 2017-03-23 Time   Sent To  
Notes
2017-03-23 09:13:24BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030381
 ADD: 1301 SUMMIT BLVD.
 CONT: GAST CONSTRUCTION
 TEL: 561-281-1001
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 3RD REVIEW
 DATE: THURS. MARCH 23/2017
 ACTION: BUILDING PROVISO/ APPROVED WITH EXCEPTION
  
 1) THE REQUIRED REMAINING FLOOD ZONE CERTIFICATES MUST
 BE ON THE NEW FLOOD ELEVATION CERTIFICATE FORM OMB NO.
 1660-0008
 EXPIRATION DATE: NOV. 30/2018
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD
 ZONE CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL
 EXTERIOR ATTENDANTS A/C PADS OR OTHER SLABS FOR
 EQUIPMENT AND OR GENERATOR.
  
 2) WOOD PILE-INSTALLATION MONITORING. ALLTERRA TO
 MONITOR INSTALLATION OF PILES. FOR DRIVEN TIMBER PILES,
 MONITORING SHALL INCLUDE:
 2A) CHECK PILE LAYOUT FOR CONFORMANCE TO DESIGN
 FOUNDATION PLAN.
 2B) OBSERVE DRIVING OF PILE TO VERIFY TARGET DEPTHS ARE
 ACHIEVED. RECORD HAMMER BLOWS PER UNIT LENGTH OF
 PILE.
 2C) CHECK CONDITIONS OF PILE UPON COMPLETION OF DRIVE.
 2D) PREPARE REPORT OF WORK ACCEPTANCE SIGNED AND SEALED
 BY PROFESSIONAL ENGINEER.
  
 3) BUILDING PROVISO: FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS: (31)(D) ROOFING PRODUCTS AND
 ASSEMBLIES.
 THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 V-CRIMP CORRUGATED GALV. METAL ROOF SYSTEM OVER WOOD
 PURLINS INSTALLED PER THE MANUFACTURER?S INSTRUCTIONS.
 2014 FBC-B 2210.1.1.2 STEEL ROOF DECK. STEEL ROOF DECKS
 SHALL BE PERMITTED TO BE DESIGNED AND CONSTRUCTED IN
 ACCORDANCE WITH ANSI/SDI-RD1.0.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-06-20 Cont ID  
Sent By jwitmer Date 2016-06-20 Time 13:55 Rev Time 0.00
Received By jwitmer Date 2016-06-20 Time 12:53 Sent To  
Notes
2016-06-20 13:53:26BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030381
 ADD: 1301 SUMMIT BLVD.
 CONT: GAST CONSTRUCTION
 TEL: 561-281-1001
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: MON. JUNE 20/2016
 ACTION: DENIED
  
 1) COMPLIED. FLOOD ZONE CERTIFICATE.
  
 2) 2ND REQUEST. THE WHOLE AREA EAST OF I-95 FROM
 SOUTHERN BLVD. SOUTH TO THE CITY GOLF COURSE IS IN A
 QUESTIONABLE SOILS ZONE, MUCK AND ORGANICS!!!! THE
 LOCATION IS A QUESTIONABLE SOILS ZONE WHERE BEARING
 VALUES DEPENDS ON THE VALUES FROM THE SOILS TEST. THIS
 REVIEW CYCLE NO SUCH REPORT HAS BEEN SUBMITTED. 2014
 FBC-B 1803.5.2 QUESTIONABLE SOILS. THIS REPORT IS ALSO
 TO PROVIDE WHAT THE MINIMUM SAFE BEARING CAPACITY OF
 THE SOILS WILL BE.
  
 3-4) BUILDING PROVISO: V-CRIMP CORRUGATED GALV. METAL
 ROOF SYSTEM OVER WOOD PURLINS INSTALLED PER THE
 MANUFACTURERS INSTRUCTIONS.
 2014 FBC-B 2210.1.1.2 STEEL ROOF DECK. STEEL ROOF DECKS
 SHALL BE PERMITTED TO BE DESIGNED AND CONSTRUCTED IN
 ACCORDANCE WITH ANSI/SDI-RD1.0.
  
 5-6) COMPLIED.
  
 7) BUILDING PROVISO: FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS: (31)(D) ROOFING PRODUCTS AND
 ASSEMBLIES.
 THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-16 Cont ID  
Sent By jwitmer Date 2016-03-16 Time 14:49 Rev Time 0.00
Received By jwitmer Date 2016-03-16 Time 11:33 Sent To  
Notes
2016-03-16 14:49:01BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030381
 ADD: 1301 SUMMIT BLVD.
 CONT: GAST CONSTRUCTION
 TEL: 561-281-1001
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: WED. MARCH 16/2016
 ACTION: DENIED
  
 1) PLEASE PROVIDE A FLOOD ZONE CERTIFICATE SIGNED &
 SEALED BY A SURVEYOR. THE PROPERTY IS LOCATED IN AN A-7
 FLOOD ZONE. FLOOD ZONE CERTIFICATES FBC BUILDING 1612
 AND CITY OF WPB CODE OF ORDINANCES SECTION 94-546.
 STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A FLOOD
 ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE REVIEW
 CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE AN
 ADDITIONAL 6 INCHES OF ELEVATION. FINISH FLOOR
 ELEVATION OF 12 FT. -6 INCHES OR HIGHER.
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS
 A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31/2015
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015.
 FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE
 NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 2) THE WHOLE AREA EAST OF I-95 FROM SOUTHERN BLVD.
 SOUTH TO THE CITY GOLF COURSE IS IN A QUESTIONABLE
 SOILS ZONE, MUCK AND ORGANICS!!!! THE LOCATION IS A
 QUESTIONABLE SOILS ZONE WHERE BEARING VALUES DEPENDS ON
 THE VALUES FROM THE SOILS TEST. THIS REVIEW CYCLE NO
 SUCH REPORT HAS BEEN SUBMITTED. 2014 FBC-B 1803.5.2
 QUESTIONABLE SOILS. THIS REPORT IS ALSO TO PROVIDE WHAT
 THE MINIMUM SAFE BEARING CAPACITY OF THE SOILS WILL BE.
  
 3) SHEET A-3 VERSES S2.0 ROOF SUB-SHEATHING THERE IS A
 DISCREPANCY IN THE PLANS. A-3 SHOWS SPACED SHEATHING,
 WHERE SHEET S2.0 DETAIL 6 SHOWS 5/8 INCH PLYWOOD ROOF
 SHEATHING. DISCREPANCY IN PLANS.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) PLEASE NOTE IF THE DESIGNER OF RECORD IS GOING TO
 USE THE SPACED SHEATHING DESIGN THE PRODUCT APPROVALS
 WILL HAVE TO BE FOR STRUCTURAL PANELS, NOT THE
 ARCHITECTURAL PANELS THAT REQUIRED CLOSELY FITTED
 SHEATHING.
 2014 FBC-B 2210.1.1.2 STEEL ROOF DECK. STEEL ROOF DECKS
 SHALL BE PERMITTED TO BE DESIGNED AND CONSTRUCTED IN
 ACCORDANCE WITH ANSI/SDI-RD1.0.
  
 5) SHEET A3.01 DETAIL 2A-A PLEASE SHOW COMPLIANCE WITH:
 5A) FBC-B 1012.2 HEIGHT & 1012.3 HANDRAIL GRASPABILITY,
 5B) FBC-B 1013.3 HEIGHT OF GUARDRAILS. , 1013.3 HEIGHT,
 1013.4 OPENINGS.
 5C) STAIR RISERS SHALL BE CLOSED. FBC-B 1009.7.5.3.
  
 6) SHEET A302 SHOWS A STAIR WITH A 6 INCH TREAD AND 6
 INCH RISER. PLEASE SHOW COMPLIANCE WITH 1009.7.2.
 RECTANGULAR TREAD DEPTHS SHALL BE 11 INCHES (279 MM)
 MINIMUM MEASURED HORIZONTALLY BETWEEN THE VERTICAL
 PLANES OF THE FOREMOST PROJECTION OF ADJACENT TREADS
 AND AT A RIGHT ANGLE TO THE TREAD?S NOSING.
 6A) FBC-B 1012.2 HEIGHT & 1012.3 HANDRAIL GRASPABILITY,
 6B) FBC-B 1013.3 HEIGHT OF GUARDRAILS. , 1013.3 HEIGHT,
 1013.4 OPENINGS.
 6C) STAIR RISERS SHALL BE CLOSED. FBC-B 1009.7.5.3.
  
 7) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS: (31)(D) ROOFING PRODUCTS AND ASSEMBLIES
  
 8) THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-03-16 Cont ID  
Sent By vperez Date 2016-03-16 Time 09:52 Rev Time 0.00
Received By vperez Date 2016-03-16 Time 09:02 Sent To  
Notes
2016-03-16 09:54:14INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PROVISO TO REFLECT AT FINAL AN UPDATED PANEL
 SCHEDULE REFLECTING LOADS TO STRUCTURE.
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-06-17 Cont ID  
Sent By wjolin Date 2016-06-17 Time 11:36 Rev Time 0.00
Received By wjolin Date 2016-06-17 Time 11:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-04-06 Cont ID  
Sent By wjolin Date 2016-04-06 Time 10:09 Rev Time 0.00
Received By wjolin Date 2016-04-06 Time 08:36 Sent To  
Notes
2016-04-06 10:09:431301 SUMMIT BOULEVARD
 PERMIT #16030381
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 UPDATE THE CODE LIST TO REFERENCE THE 2009 EDITION OF
 NFPA 150 - FIRE & LIFE SAFETY IN ANIMAL HOUSING
 FACILITIES
  
 SHEET A-001 INDICATES THE CONSTRUCTION TYPE TO BE TYPE
 VB. PER NFPA 150 - TABLE 7.2.2 ALL NON-SPRINKLERED
 BUILDINGS HOUSING CATERGORY B ANIMALS SHALL BE TYPE I
 OR TYPE II NON-COMBUSTIBLE CONSTRUCTION WHEN LOCATED
 ABOVE GRADE.
  
 SHEET A-001 ALSO INDICATES THAT OCELOTS ARE DEEMED TO
 BE A CATEGORY B IN LIEU OF A CATEGORY A. PLEASE DEFEND
 YOUR POSITION HOW A LARGE, FERAL FELINE SUBJECTED TO A
 STRENOUS EVENT SUCH AS A FIRE WOULD NOT POSE A DANGER
 TO HUMANS ATTEMPTING RESCUE.
  
 SECTION 6.3.1.1 CATEGORY A. CATEGORY A ANIMALS SHALL
 INCLUDE ANY OF THE FOLLOWING TYPES OF ANIMALS:
 (1) ANIMAL(S) THAT POSE A POTENTIAL RISK TO THE HEALTH
 OR SAFETY OF RESCUERS OR THE GENERAL PUBLIC
 (2) ANIMAL(S) THAT CANNOT BE REMOVED WITHOUT POTENTIAL
 RISK TO THE HEALTH AND WELFARE OF THE ANIMAL OR OTHER
 ANIMALS
 (3) ANIMAL(S) THAT ARE IMPOSSIBLE OR IMPRACTICAL TO
 MOVE
 CATEGORY B ANIMALS SHALL INCLUDE ALL ANIMALS NOT IN
 CATEGORY A.
  
 SHEET A-302: STAIR TREAD DEPTH IS ONLY 6-INCHES IN
 WIDTH AND NEEDS TO BE A MINIMUM OF 11-INCHES WIDE PER
 NFPA 101 - TABLE 7.2.2.2.1.1(A).
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-03-23 Cont ID  
Sent By jwitmer Date 2017-03-23 Time 09:14 Rev Time 0.00
Received By jwitmer Date 2017-03-21 Time 14:56 Sent To  
Notes
2017-03-22 14:56:40RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-28 Cont ID  
Sent By jroach Date 2016-06-28 Time 13:20 Rev Time 0.00
Received By jroach Date 2016-06-08 Time 14:03 Sent To  
Notes
2016-06-09 14:04:00C25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-07 Cont ID  
Sent By jroach Date 2016-04-07 Time 09:35 Rev Time 0.00
Received By jroach Date 2016-03-09 Time 10:33 Sent To  
Notes
2016-03-09 10:33:33C25

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-03-16 Cont ID  
Sent By jwitmer Date 2016-03-16 Time 11:53 Rev Time 0.00
Received By jwitmer Date 2016-03-16 Time 11:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-06-14 Cont ID  
Sent By ccole Date 2016-06-14 Time 11:08 Rev Time 0.00
Received By ccole Date 2016-06-14 Time 11:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-03-15 Cont ID  
Sent By ccole Date 2016-03-15 Time 14:52 Rev Time 0.00
Received By ccole Date 2016-03-15 Time 14:52 Sent To  
Notes
2016-03-15 14:56:451ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030381
 3/15/16
  
 1) PROVIDE AN EXHAUST VENTILATION CALCULATION FOR EF-1.
 2) PROVIDE THE WIND LOAD DESIGN CRITERIA AND
 ENGINEERING FOR INSTALLATION OF THE ROOF MOUNTED FAN
 AND CURB. PROVIDE A SECTION CUT INDICATING THE TYPE,
 SIZE, AND AMOUNT OF FASTENERS FOR ANCHORING THE CURB TO
 THE STRUCTURE, AND THE FAN TO THE CURB.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status P Date 2019-04-25 Cont ID  
Sent By shill Date 2019-04-25 Time 14:57 Rev Time 0.00
Received By shill Date 2019-04-25 Time 14:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-03-23 Cont ID  
Sent By gjohnson Date 2016-03-23 Time 14:52 Rev Time 0.00
Received By gjohnson Date 2016-03-23 Time 14:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2017-03-06 Cont ID  
Sent By jroach Date 2017-03-06 Time 13:48 Rev Time 0.00
Received By jroach Date 2017-03-06 Time 13:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2016-06-28 Cont ID  
Sent By jroach Date 2016-06-28 Time 11:59 Rev Time 0.00
Received By jroach Date 2016-06-27 Time 08:54 Sent To  
Notes
2016-06-28 12:00:30ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 06.28.2016
 PERMIT NO.: 16030381
 ADDRESS: 1301 SUMMIT BOULEVARD
 CONTRACTOR/CONTACT: ALLEN GAST
 TELEPHONE NO.: 561.281.1001
 SCOPE OF REVIEW: OCELOT EXHIBIT MODIFICATIONS
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 ALL COMMENTS HAVE BEEN SATISFACTORILY ADDRESSED AND
 THERE ARE NO ISSUES WITH THE PLANS. STAFF IS AWAITING
 APPROVAL BY THE CITY COMMISSION BEFORE PASSING THIS
 REVIEW AND ISSUING THE PERMIT. UPON APPROVAL, THIS
 REVIEW STATUS WILL BE CHANGED TO "PASSED" AND THE
 PERMIT APPLICATION WILL BE PROCESSED FOR ISSUANCE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-04-07 Cont ID  
Sent By jroach Date 2016-04-07 Time 09:34 Rev Time 0.00
Received By jroach Date 2016-04-06 Time 16:02 Sent To  
Notes
2016-04-07 09:35:13ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 04.07.2016
 PERMIT NO.: 16030381
 ADDRESS: 1301 SUMMIT BOULEVARD
 CONTRACTOR/CONTACT: ALLEN GAST
 TELEPHONE NO.: 561.281.1001
 SCOPE OF REVIEW: NEW OCELOT EXHIBIT
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PURSUANT TO THE PALM BEACH ZOO?S LEASE AGREEMENT
 WITH THE CITY OF WEST PALM BEACH, INDIVIDUAL STRUCTURES
 OR IMPROVEMENTS IN EXCESS OF $5,000 ARE TO BE SUBMITTED
 TO THE CITY COMMISSION FOR PRIOR APPROVAL AS SUCH
 IMPROVEMENTS WOULD OCCUR ON CITY-OWNED PROPERTY.
  
 2. PLEASE PROVIDE TWO (2) COPIES OF A CURRENT AND
 ACCURATE SURVEY.
  
 3. THE SITE PLAN SHALL PROVIDE THE SETBACK DIMENSIONS
 FROM ANY NEW STRUCTURES TO THE SURROUNDING PROPERTY
 LINES.
  
 4. REMOVAL OF TREES SHALL REQUIRE THE ISSUANCE OF A
 TREE ALTERATION PERMIT FROM THE CITY?S DEVELOPMENT
 SERVICES DEPARTMENT - PLANNING DIVISION. PLEASE CONTACT
 RAY CARANCI, LANDSCAPE PLANNER, AT 561.822.1462.
  
 5. BEFORE COMMENCING THE IMPROVEMENTS, THE ZOO SHALL
 PROVIDE THE CITY?S RISK MANAGER WITH CERTIFICATES OF
 INSURANCE EVIDENCING THAT ANY CONTRACTOR(S) PERFORMING
 THE IMPROVEMENTS CARRIES COMMERCIAL GENERAL LIABILITY
 INSURANCE (INCLUDING, WITHOUT LIMITATION, CONTRACTOR?S
 LIABILITY COVERAGE), WRITTEN ON AN OCCURRENCE BASIS
 WITH A MINIMUM COMBINED SINGLE LIMIT OF $2,000,000,
 ALONG WITH WORKERS COMPENSATION INSURANCE AS REQUIRED
 BY LAW, AND INCLUDING THE CITY OF WEST PALM BEACH AS AN
 ADDITIONAL INSURED.
  
 6. ALL LANDSCAPING SHALL BE SUBMITTED UNDER A SEPARATE
 APPLICATION FOR A LANDSCAPE PERMIT. THE PERMIT
 APPLICATION SHALL BE ACCOMPANIED BY LANDSCAPE PLANS
 SIGNED/SEALED BY A REGISTERED LANDSCAPE ARCHITECT, AS
 WELL AS A CERTIFIED COST ESTIMATE (MATERIAL + LABOR).
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved