Plan Review Details - Permit 16030369
Plan Review Stops For Permit 16030369
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2016-11-28 Cont ID  
Sent By cthroop Date 2016-11-28 Time 08:58 Rev Time 0.00
Received By cthroop Date 2016-11-28 Time 08:58 Sent To  
Notes
2016-11-28 08:59:58INTERIOR DEMO AND NEW STAIR FOUNDATIONS. FIRE WATCH
 REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-08-22 Cont ID  
Sent By cthroop Date 2016-08-22 Time 12:23 Rev Time 0.00
Received By cthroop Date 2016-08-22 Time 10:56 Sent To  
Notes
2016-08-22 12:24:56SCOPE OF WORK LIMITED TO DEMO, FOUNDATIONS AND
 STRUCTURAL STEEL SUPPORTS FOR NEW STAIRS. OWNER TO MAKE
 APPLICATION FOR THE INSTALLATION OF NEW STAIRS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-07-28 Cont ID  
Sent By cthroop Date 2016-07-28 Time 10:03 Rev Time 0.00
Received By cthroop Date 2016-07-28 Time 10:03 Sent To  
Notes
2016-07-28 10:04:46DEMO PHASE ONLY. SEE REVISED WORK DESCRIPTION.
 RE-SUBMITTAL REQUIRED. APPLICANT TO COMPLY WITH
 PREVIOUS REVIEW COMMENTS. CST

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-06-15 Cont ID  
Sent By cthroop Date 2016-06-15 Time 13:33 Rev Time 0.00
Received By cthroop Date 2016-06-15 Time 11:07 Sent To  
Notes
2016-06-15 14:02:48BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 DATE: 6/15/16
 ACTION: FAIL
  
 THE PLANS RE-SUBMITTED FOR REVIEW CONSIST OF A
 RE-DESIGN FROM THE 1ST REVIEW. THE ARCHITECTURAL AND
 LIFE SAFETY PLANS SUBMITTED ARE LIMITED IN SCOPE AND
 GENERAL IN NATURE. A THOROUGH REVIEW CANNOT BE
 PERFORMED AT THIS TIME. THE ATTACHED LIST OF ITEMS IS
 FOR GUIDANCE ONLY AND IS NOT TO BE CONSTRUED AS A FINAL
 LIST OF COMMENTS TO BE ADDRESSED BY THE DESIGN TEAM.
 ADDITIONAL COMMENTS MAY BE GENERATED UPON RE-SUBMITTAL
 OF PLANS.
  
 1. PROVIDE DETAIL OF NEW ISOLATED SPREAD FOOTINGS.
 2. PROVIDE DETAIL & SHOP DRAWINGS OF NEW STRUCTURAL
 STEEL SKELETON STRUCTURE.
 3. PROVIDE SHOP DRAWINGS OF NEW STAIRS (BY OTHERS).
 4. PROVIDE SHORING PLAN FOR REMOVAL OF STRUCTURAL
 SLABS.
 5. PROVIDE DETAIL OF EXISTING WALLS TO BE USED AS PART
 OF RATED SHAFT. WALLS SHALL COMPLY WITH FBC 706 (WALLS)
 AND 713 (SHAFTS).
 6. PROVIDE DETAIL OF NEW WALLS TO BE USED AS PART OF
 RATED SHAFT. WALLS SHALL COMPLY WITH UL 404 PER PLANS.
 7. PROVIDE DETAIL OF RATED DOOR ASSEMBLY. DOORS SHALL
 BE RATED PER FBC TABLE 716.5 AND INSTALLED PER NFPA 80.
 8. PROVIDE EXIT DOOR HARDWARE SPECS.
 9. PROVIDE STAIRWAY ILLUMINATION PER FBC 1011.3.
 10. LABEL STAIRS ACCORDING TO THE JEZERINAC GROUP'S
 REPORT. STAIR # 1 AND STAIR #2. LOBBY STAIRS ARE
 EXISTING AND ARE OUTSIDE THE SCOPE OF THIS SUBMITTAL.
 11. PROVIDE LIFE SAFETY PLAN INDICATING PATH OF TRAVEL
 AND EXIT DISCHARGE TO A PUBLIC WAY, DISTANCE TO EXIT'S,
 EMERGENCY ILLUMINATION AND RATED WALLS.
 12. VALUE OF PROJECT APPEARS LOW.
 13. MECHANICAL, ELECTRICAL & PLUMBING PERMITS REQUIRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
 FAILURE TO PROVIDE DOCUMENTATION OF ESTIMATED COSTS MAY
 DELAY THE APPLICATION PROCESS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-18 Cont ID  
Sent By cthroop Date 2016-03-18 Time 15:39 Rev Time 0.00
Received By cthroop Date 2016-03-18 Time 15:39 Sent To FIRE
Notes
2016-03-18 16:09:281ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 1. PROVIDE DETAIL FOR WINDOW OPENINGS TO B ENCLOSED.
 2. PROVIDE FLOOR PLAN WITH THE FOLLOWING: EXIT ACCESS
 PER FBC 1014.1, EXIT PASSAGEWAY WIDTH PER FBC 1023,
 EXIT SIGNS PER FBC 1011, EXIT PATH OF TRAVEL PER TABLE
 1016.2, EXIT DOORS COMPLYING WITH FBC 1008.1.1 AND EXIT
 ILLUMINATION PER FBC 1011.3.
 MULTIPLE DEMENSIONS MISSING ON STAIR DETAILS: LANDING
 WIDTH AT EXIT DOOR - FBC 1008.1.6, STAIRWAY LANDING PER
 FBC 1009.8, EXIT DOORS PER FBC 1008.1.1, HANDRAIL
 DETAIL PER FBC 1012.3 AND HANDRAIL EXTENSIONS PER FBC
 1012.6.
 3. DETAIL A, PG A-1.01 SHOWS A FENCE IN THE PATH OF
 TRAVEL AT STAIR LANDING.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-27 Cont ID  
Sent By mvaldes Date 2016-07-27 Time 08:47 Rev Time 0.00
Received By mvaldes Date 2016-07-25 Time 16:56 Sent To P
Notes
2016-07-27 08:47:35REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 PASSED AS A DEMOLITION PERMIT ONLY ALL TEMPORARY
 ELECTRIC SHALL BE GFCI PROTECTED IN ACCORDANCE WITH NEC
 590.6
  
 NEW PLANS TO INCLUDE THE FOLLOWING AS A MINIMUM :
  
 1) FBC 1006.1 ILLUMINATION REQUIRED.THE MEANS OF
 EGRESS, INCLUDING THE EXIT DISCHARGE, SHALL BE
 ILLUMINATED AT ALL TIMES THE BUILDING SPACE SERVED BY
 THE MEANS OF EGRESS IS OCCUPIED.
 - PLEASE SHOW EMERGENCY LIGHTING BY THE HALLWAYS TO
 VERIFY MINIMUM ILLUMINATION LEVELS OF 1 FOOT CANDLE AT
 THE WALKING SURFACE. FBC 1006.2
  
 2) FBC 1011.1 EXITS AND EXIT ACCESS DOORS SHALL BE
 MARKED BY AN APPROVED EXIT SIGN READILY VISIBLE FROM
 ANY DIRECTION OF EGRESS TRAVEL. THE PATH OF EGRESS
 TRAVEL TO EXITS AND WITHIN EXITS SHALL BE MARKED BY
 READILY VISIBLE EXIT SIGNS TO CLEARLY INDICATE THE
 DIRECTION OF EGRESS TRAVEL IN CASES WHERE THE EXIT OR
 THE PATH OF EGRESS TRAVEL IS NOT IMMEDIATELY VISIBLE TO
 THE OCCUPANTS.
 INTERVENING MEANS OF EGRESS DOORS WITHIN EXITS SHALL BE
 MARKED BY EXIT SIGNS. EXIT SIGN PLACEMENT SHALL BE SUCH
 THAT NO POINT IN AN EXIT ACCESS CORRIDOR OR EXIT
 PASSAGEWAY IS MORE THAN 100 FEET (30 480 MM) OR THE
 LISTED VIEWING DISTANCE FOR THE SIGN, WHICHEVER IS
 LESS, FROM THE NEAREST VISIBLE EXIT SIGN.
 - SHOW EXIT SIGNS LOCATION IN THE HALLWAYS TO COMPLY.
  
 3) ILLUMINATION SHALL BE PROVIDED FOR ALL WORKING
 SPACES ABOUT SERVICE EQUIPMENT, SWITCHBOARDS,
 PANELBOARDS. NEC 110.26(D) SHOW LIGHTING BY THE
 ELECTRICAL PANELS IN THE HALLWAYS TO COMPLY WITH THIS
 REQUIREMENT.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-15 Cont ID  
Sent By mvaldes Date 2016-06-15 Time 15:30 Rev Time 0.00
Received By mvaldes Date 2016-06-15 Time 15:12 Sent To  
Notes
2016-06-15 15:30:48REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 -THE FOLLOWING ARE THE ELECTRICAL REQUIREMENTS THAT
 APPLY TO THE INTERIOR STAIRWAY MEANS OF EGRESS
  
 - 1006.1 ILLUMINATION REQUIRED. 1006.2 ILLUMINATION
 LEVEL.
 THE MEANS OF EGRESS, INCLUDING THE EXIT DISCHARGE,
 SHALL BE ILLUMINATED AT ALL TIMES THE BUILDING SPACE
 SERVED BY THE MEANS OF EGRESS IS OCCUPIED.
 THE MEANS OF EGRESS ILLUMINATION LEVEL SHALL NOT BE
 LESS THAN 1 FOOTCANDLE (11 LUX) AT THE WALKING SURFACE.
  
 - FBC-B 1011. EXIT SIGNAGE REQUIRED.THE FACE OF AN EXIT
 SIGN ILLUMINATED FROM AN EXTERNAL SOURCE SHALL HAVE AN
 INTENSITY OF NOT LESS THAN 5 FOOTCANDLES
  
 - NEC 700.12 (F) (4) ? EMERGENCY/EXIT LIGHTING SHALL BE
 FED BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR
 MORE LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY
 BE ON OWN CIRCUIT.
  
 - 1022.5 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH INTERIOR EXIT
 STAIRWAYS AND RAMPSARE PROHIBITED EXCEPT FOR REQUIRED
 EXIT DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR
 INDEPENDENT VENTILATION OR PRESSURIZATION, SPRINKLER
 PIPING, STANDPIPES, ELECTRICAL RACEWAY FOR FIRE
 DEPARTMENT COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY
 SERVING THE INTERIOR EXIT STAIRWAY AND RAMP AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING 16 SQUARE
 INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE PROTECTED
 IN ACCORDANCE WITH SECTION 714. THERE SHALL BE NO
 PENETRATIONS OR COMMUNICATING OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT INTERIOR EXIT
 STAIRWAYS AND RAMPS. OPEN PENETRATIONS SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 714.3.2.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2016-08-16 Cont ID  
Sent By pleduc Date 2016-08-16 Time   Rev Time 0.00
Received By pleduc Date 2016-08-16 Time 15:23 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2016-07-20 Cont ID  
Sent By pleduc Date 2016-07-20 Time   Rev Time 0.00
Received By pleduc Date 2016-07-20 Time 11:20 Sent To  
Notes
2016-07-20 12:14:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PROGRESS IS BEING MADE AND ALL EFFORTS ARE APPRECIATED;
 HOWEVER, LIFE SAFETY CONCERNS REMAIN UNCLEAR.
  
  
  
  
 1) A LIFE SAFETY PLAN, DURING CONSTURCTION IS NEEDED TO
 ASSIST MY REVIEW OF HOW/WHERE WILL THE RESIDENTS EXIT
 DURING CONSTRUCTION.
  
 IT APPEARS THAT THE HALLWAYS LEADING TO THE SECONDARY
 EXIT EGRESS, THE FIRE ESCAPE STAIRS, APPEARS TO BE/WILL
 BE BLOCKED BY CONSTURCTION.
  
 PLEASE PROVIDE DETAIL OF HOW EACH FLOOR WIL HAVE SAFE
 TRAVEL TO TWO REMOTE EXITS DURING CONSTUCTION.
  
  
 2) DUE TO THE NATURE OF THE DEMOLITION AND AGE OF THE
 BUILDING I AM CONCERNED REGARDING THE SAFETY OF THE
 OCCUPANTS DURING CONSTRUCTION, ESPECIALLY DURING THE
 DEMOLITION, POTENTIALLY UNSTABLE STRUCTURE, PERIOD.
  
 THERE IS NO NOTE/NARRATIVE/STATEMENT/RECOMMENDATION OF
 ANYONE WITH THE EXPERTISE AS TO THE CONTINUED OCCUPANCY
 OF RESIDENTS OF THE BUILDING DURING THE
 DEMOLITION/CONSTRUCTION PERIODS.
  
 PLEASE PROVIDE SOME SORT OF OFFICIAL SIGNED AND SEALED
 DOCUMENTATION FROM A QUALIFIED LICENSED AUTHORITY TO
 CONFIRMED/VERIFY THE RESIDENTS SAFETY OCCUPYING THE
 BUILDING DURING DEMOLITION/CONSTRUCTION.
  
  
 3) THERE DOES NOT APPEAR TO BE A NOTE OR NARRATIVE
 REAGARDING ALL WORK ON THE FIRE LARM OR FIRE SPRINKLER
 SHALL BE DONE BY CERITIFED LIFE SAFETY CONTRACTORS
 UNDER SEPARATE SHOP DRAWINGS.
  
 PLEASE PROVIDE.
  
  
 4) THE VALUE OF THIS PROJECT $150,000 APPEARS TO BE TOO
 LOW, PLEASE PROVIDE VERIFICATION/JUSTIFICATION AND/OR
 INCREASE ACCORDINGLY.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-06-09 Cont ID  
Sent By pleduc Date 2016-06-09 Time   Rev Time 0.00
Received By pleduc Date 2016-06-09 Time 11:25 Sent To B
Notes
2016-06-09 11:59:12THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 THIS PROVISO IS WRITTEN TO EXPEDITE THIS PROJECT. CLOSE
 COMMUNICATION WITH THE PREVENTION BUREAU SHALL BE
 MAINTAINED TO ENSURE THE SAFE AND EFFECTIVE EGRESS OF
 RESIDENTS DURING THE CONSTRUCTIOIN PERIOD. THIS MAY BE
 ACCOMPLISHED THROUGH PHONE, EMAIL AND WITH REGULAR SITE
 VISITS.
  
 1) SHEET LS1.01 - A FIRE WATCH SHALL BE PUT IN PLACE
 THROUGHOUT THE CONSTRUCTION PERIOD. IT SHALL BE
 REVIEWED AND APPROVED BY THE FIRE MARSHAL.
  
 2) SHEET A1.01 & 1.02 - THE STAIR CONSTRUCTION
 INCLUDING THE TREADS AND RISERS SHALL COMPLY WITH NFPA
 101, CHAPTER 7 AND WITH THE STAIR DETAIL SUBMITTED
 UNDER SEPARATE SHOP DRAWINGS.
  
 3) SHEET A0.10 - THE EXTERIOR STAIR SHALL BE CONFIMED
 TO BE OPERATIONAL AND REMAIN IN PLACE UNTIL THE
 INTERIOR STAIRS ARE COMPLETE. THE FIRE WATCH PERSONNEL
 SHALL BE INSTRUCTED AND DEMONSTRATE THAT THEY CAN USE
 THE STAIRS.
  
 4) NO SHHEET - NO EMERGENCY LIGHTING IS PROVIDED.
 EMERGENCY LIGHTING SHALL BE PROVIDED.
  
 5) NO SHEET - NO DOOR DETAIL IS PROVIDED, INCLUDING
 EXIT HARDWARE. PLEASE PROVIDE THE APPLICABLE DOOR
 DETAIL IN THE FORM OF REVISION AS SOON AS PRACTICAL.
  
 6) THE VALUE INDICATED IS $ 150,000 AND IS TOO LOW.
 PLEASE PROVIDE A COPY OF THE CONTRACT AND/OR ADJUST THE
 VALUE ACCURATELY.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-03-24 Cont ID  
Sent By wjolin Date 2016-03-24 Time   Rev Time 0.00
Received By wjolin Date 2016-03-24 Time 10:23 Sent To PC
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2016-11-28 Cont ID  
Sent By cthroop Date 2016-11-28 Time 08:58 Rev Time 0.00
Received By cthroop Date 2016-11-23 Time 16:49 Sent To  
Notes
2016-11-23 16:49:42CTHROOP'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-08-22 Cont ID  
Sent By cthroop Date 2016-08-22 Time 12:23 Rev Time 0.00
Received By cthroop Date 2016-08-12 Time 10:53 Sent To  
Notes
2016-08-15 10:53:48RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-07-28 Cont ID  
Sent By cpuell Date 2016-07-28 Time 13:51 Rev Time 0.00
Received By cpuell Date 2016-07-18 Time 09:44 Sent To  
Notes
2016-07-19 09:45:24C06

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-15 Cont ID  
Sent By gjohnson Date 2016-06-15 Time 17:00 Rev Time 0.00
Received By gjohnson Date 2016-05-25 Time 10:32 Sent To  
Notes
2016-06-06 12:00:39TO MISC 2 BOX.
2016-05-26 10:33:04RESUB ROUTED TO AAPONTE VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-24 Cont ID  
Sent By wjolin Date 2016-03-24 Time   Rev Time 0.00
Received By wjolin Date 2016-03-08 Time 08:30 Sent To Z
Notes
2016-03-16 15:23:43TO MISC 2 BOX.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-07-25 Cont ID  
Sent By ccole Date 2016-07-25 Time 07:35 Rev Time 0.00
Received By ccole Date 2016-07-25 Time 07:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-07-27 Cont ID  
Sent By mvaldes Date 2016-07-27 Time 13:25 Rev Time 0.00
Received By gjohnson Date 2016-07-27 Time 12:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-06-15 Cont ID  
Sent By gjohnson Date 2016-06-15 Time 16:32 Rev Time 0.00
Received By gjohnson Date 2016-06-15 Time 16:32 Sent To  
Notes
2016-06-15 16:59:501ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLANS ARE UNCLEAR ON THE SCOPE OF PLUMBING WORK
 BEING DONE SHOW ON PLANS WHAT FIXTURE ARE BEING REMOVED
 AND LINES CAPPED. PER WPB TO FBC SEC. 107.2.1
  
 2. ARE PLUMBING LINES BEING CAPPED OFF IN THE WALL OF
 STUBBED OUT FOR REUSE SHT A-0.10 NOTE#2 INDICATES LINES
 BEING CAPPED AND STUBBED OUT PLEASE CLARIFY.. PER WPB
 TO FBC SEC. 107.2.1
  
 3. ARE YOU ELIMINATING BATHROOMS ALONG WITH DWELLING
 UNITS THEY SERVE. . PER WPB TO FBC SEC. 107.2.1
  
 4. ARE ANY OF THE BATHROOMS THAT ARE BEING ELIMINATED
 USED FOR EMPLOYEE OR PUBLIC USE IF SO THEY WILL BE
 REQUIRED TO BE RELOCATED. PER FBC PL SEC. 403

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 4 Status P Date 2016-12-09 Cont ID  
Sent By kconrad Date 2016-12-09 Time 09:47 Rev Time 0.00
Received By kconrad Date 2016-12-09 Time 09:46 Sent To I
Notes
2016-12-09 09:49:10RECEIVED SPECIAL INSPECTOR AGREEMENT AND SI RESUME
 SIGNED BY MONZER I. FARAMAWI. PE, S.I.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status F Date 2016-11-28 Cont ID  
Sent By cthroop Date 2016-11-28 Time 09:12 Rev Time 0.00
Received By cthroop Date 2016-11-28 Time 09:12 Sent To  
Notes
2016-11-28 09:14:25BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
  
 1. RESIDENT INSPECTOR REQUIRED.
 2. COMPLETE RESIDENT INSPECTOR AGREEMENT AND RETURN IN
 TRIPLICATE.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status N Date 2016-08-22 Cont ID  
Sent By cthroop Date 2016-08-22 Time 12:25 Rev Time 0.00
Received By cthroop Date 2016-08-22 Time 10:56 Sent To  
Notes
2016-08-22 12:26:56ENGINEER OF RECORD AND GENERAL CONTRACTOR TO SUBMIT
 RESIDENT INSPECTOR AGREEMENT PRIOR TO COMMENCEMENT.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status N Date 2016-07-28 Cont ID  
Sent By cthroop Date 2016-07-28 Time 09:58 Rev Time 0.00
Received By cthroop Date 2016-07-28 Time 09:58 Sent To  
Notes
2016-07-28 10:03:22BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: N/A
 DATE: 7/28/16
  
 1. RESIDENT INSPECTOR WILL BE REQUIRED FOR THIS
 PROJECT.
 2. INCLUDE 3 COPIES OF COMPLETED RESIDENT INSPECTOR
 AGREEMENT WITH RE-SUBMITTAL.
 3. INCLUDE RESUME OF ENGINEER OF RECORD AND ANY ON-SITE
 468 LICENSED INSPECTORS.
 4. PROVIDE WORK HISTORY OF SIMILAR PROJECTS FROM
 CONTRACTOR.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2016-07-28 Cont ID  
Sent By aaponte Date 2016-07-28 Time 10:49 Rev Time 0.00
Received By aaponte Date 2016-07-28 Time 10:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-06-06 Cont ID  
Sent By aaponte Date 2016-06-06 Time 11:58 Rev Time 0.00
Received By aaponte Date 2016-06-06 Time 11:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-03-16 Cont ID  
Sent By wjolin Date 2016-03-24 Time 10:25 Rev Time 0.00
Received By aaponte Date 2016-03-16 Time 14:46 Sent To  
Notes
2016-03-16 15:23:14PROPOSED STAIR IS BLOCKING THE EXISTING 14' ALLEY ON
 THE SOUTH SIDE OF THE BUILDING. EXISITNG ALLEY CANNOT
 BE BLOCKED AS IT IS USED BY SURROUNDING PROPERTIES.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.