Plan Review Details - Permit 16030368
Plan Review Stops For Permit 16030368
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-16 Cont ID  
Sent By albarran Date 2016-03-16 Time 10:39 Rev Time 0.00
Received By albarran Date 2016-03-15 Time 18:30 Sent To I
Notes
2016-03-16 14:34:10AFTER DISCUSSING MY CONCERNS WITH PETE RUSSO, I
 UNDERSTOOD THAT THE SHEETS WERE OK AS SUBMITTED. MY
 CONCERN WAS THE OBSTRUCTION OF AN EXIT LIGHT WITH WHAT
 I THOUGHT TO BE A FULL HEIGHT WALL WHICH TURNED OUT TO
 BE ON 4 FOOT HIGH THEREFORE NOT OBSTRUCTING THE
 EMERGENCY/EXIT LIGHT. PLANS APPROVED.
2016-03-16 10:46:57THIS IS A TEMPORARY DENIAL AS I WAS TOLD THAT THE WRONG
 SHEET HAS BEEN SUBMITTED. I SPOKE WITH PETE RUSSO AND
 THE NEW SHEET WILL BE DELIVERED DIRECTLY TO ME. AS SOON
 AS I GET IT AND THE DEFICIENCY IS CORRECTED I WILL PASS
 THIS REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-09 Cont ID  
Sent By albarran Date 2016-03-09 Time 13:26 Rev Time 0.00
Received By albarran Date 2016-03-09 Time 12:50 Sent To I
Notes
2016-03-09 13:30:212ND ELECTRICAL REVIEW NOTES FOR REVISION #:16030368
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014
 NFPA 70 2011 (NEC)
  
 CORRECTIONS REQUIRED:
 1. EXIT & EMERGENCY LIGHTING AS INDICATED ON THE
 DRAWINGS DOES NOT MEET MINIMUM CODE REQUIREMENTS.
 2. NEC 600.5 REQUIREMENTS NOT SHOWN ON THE DRAWINGS. A
 DEDICATED SIGN OUTLET IS REQUIRED BY EVERY ENTRANCE.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-16 Cont ID  
Sent By albarran Date 2016-03-16 Time 14:34 Rev Time 0.00
Received By albarran Date 2016-03-14 Time 10:03 Sent To  
Notes
2016-03-16 14:35:443/16/16 PASSED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. FILE SENT TO SMALL READY BIN "F".
 MA
2016-03-15 10:03:24RESUB ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-09 Cont ID  
Sent By albarran Date 2016-03-09 Time 13:42 Rev Time 0.00
Received By albarran Date 2016-03-08 Time 09:37 Sent To  
Notes
2016-03-09 13:45:333/9/16 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT FILE TO SMALL DENIED BIN "F".
 MA
2016-03-09 09:37:39REVISION ROUTED TO MALBARRAN