Plan Review Details - Permit 16030347
Plan Review Stops For Permit 16030347
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2017-01-11 Cont ID  
Sent By jgomez Date 2017-01-10 Time 19:58 Rev Time 0.00
Received By jgomez Date 2017-01-10 Time 19:58 Sent To M
Notes
2017-01-10 19:58:35 
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2017-01-11 Cont ID  
Sent By jgomez Date 2017-01-03 Time 19:58 Rev Time 0.00
Received By jgomez Date 2017-01-03 Time 18:09 Sent To  
Notes
2017-01-03 18:21:16REVIEWED ENERGY CALCULATIONS THAT WERE E-MAILED BY
 SASHA BUBANJA FROM FASTRACK MCI. WAITING FOR
 CALCULATIONS AND SECOND SET OF PLANS TO BE RE-SUBMITTED
 TO COMPLETE BUILDING REVIEW. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2016-11-28 Cont ID  
Sent By jgomez Date 2016-11-28 Time 14:28 Rev Time 0.00
Received By jgomez Date 2016-11-28 Time 14:28 Sent To  
Notes
2016-11-28 14:45:28RESIDENTIAL (R3) ADDITION/ALTERATION SIXTH BUILDING
 REVIEW CHECKLIST.
 CODE: FBC-5TH EDITION (2014).
  
 NOTE:
 THE PERMIT CAN NOT BE ISSUED WITHOUT THE ENERGY
 CALCULATIONS.
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION
  
  
  
 1- REVISE ENERGY CALCULATIONS SUBMITTED:
 A)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM, INCLUDING CORRECT OWNER'S NAME, BUILDER NAME,
 PERMIT OFFICE AND JURISDICTION NUMBER. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE:
 REPEAT COMMENT. NEEDS BUILDER NAME, PERMIT OFFICE AND
 JURISDICTION NUMBER.
  
 B) SEC. R806.2 OF FBC-RESIDENTIAL, 5TH EDITION (2014)
 REQUIRES 1/150 ATTIC VENTILATION RATIO. ATTIC
 INFORMATION ON PAGE 2 OF 4 SPECIFIES 1/300 ATTIC
 VENTILATION RATIO. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING HOW THIS HOUSE COMPLIES WITH THE
 EXCEPTION OF SEC. R806.2 FOR 1/300 ATTIC VENTILATION
 RATIO. OTHERWISE REVISE AS REQUIRED.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL. SEE ARCHITECTURAL
 PLANS. THEY CALL FOR 1/150 RATIO NOT 1/300. REVISE AS
 REQUIRED.
  
 C) COMPLETE THE INSPECTION CHECKLIST AS REQUIRED BY
 SEC. R405.4.2 FBC-ENERGY CONSERVATION.
 RESPONSE:
 INSPECTION CHECKLIST NEED TO BE COMPLETED. CHECKLIST
 NEED TO BE CHECKED WITH THE ITEMS THAT APPLY.
  
 D) PROVIDE THE NAME OF THE INDIVIDUAL COMPLETING THE
 ENERGY CALCULATIONS AS REQUIRED BY SEC. R405.4.2
 FBC-ENERGY CONSERVATION.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL. THE NAME OF THE
 PERSON COMPLETING THE ENERGY CALCULATIONS WAS NOT
 PROVIDED. ONLY A COPY OF A SIGNATURE WAS PROVIDED.
 PROVIDE THE COMPLETE NAME OF THE PERSON COMPLETING THE
 CALCULATIONS.
  
 NOTE: LABEL FOR WINDOWS AND DOORS U-FACTOR AND SHGC
 FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL BE
 REQUIRED FOR VERIFICATION.
  
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2016-11-21 Cont ID  
Sent By jgomez Date 2016-11-21 Time 14:39 Rev Time 0.00
Received By jgomez Date 2016-11-21 Time 13:50 Sent To M
Notes
2016-11-21 14:18:40RESIDENTIAL (R3) ADDITION/ALTERATION FIFTH BUILDING
 REVIEW CHECKLIST.
 CODE: FBC-5TH EDITION (2014).
  
 NOTE:
 THE PERMIT CAN NOT BE ISSUED WITHOUT THE ENERGY
 CALCULATIONS.
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION
  
  
  
 1- REVISE ENERGY CALCULATIONS SUBMITTED:
  
 A) ORIGINAL COMMENT:
 PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM, INCLUDING CORRECT OWNER'S NAME ("HOMEOWNER" IS
 NOT AN OWNER), BUILDER NAME, PERMIT OFFICE AND
 JURISDICTION NUMBER. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 RESPONSE:
 THE NAME OF THE OWNER DOESN'T MATCH THE NAME OF THE
 OWNER SHOWN ON THE PERMIT APPLICATION. DANIEL PEREIRA
 IS NOT THE NAME LISTED IN THE PERMIT APPLICATION.
 REVISE AS REQUIRED.
  
 B) ORIGINAL COMMENT:
 SEC. R806.2 OF FBC-RESIDENTIAL, 5TH EDITION (2014)
 REQUIRES 1/150 ATTIC VENTILATION RATIO. ATTIC
 INFORMATION ON PAGE 2 OF 4 SPECIFIES 1/300 ATTIC
 VENTILATION RATIO. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING HOW THIS HOUSE COMPLIES WITH THE
 EXCEPTION OF SEC. R806.2 FOR 1/300 ATTIC VENTILATION
 RATIO. OTHERWISE REVISE AS REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL. SEE ARCHITECTURAL
 PLANS. THEY CALL FOR 1/150 RATIO NOT 1/300. REVISE AS
 REQUIRED.
  
 C) ORIGINAL COMMENT:
 REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 D) ORIGINAL COMMENT:
 MISSING THE INSPECTION CHECKLIST AS REQUIRED BY SEC.
 R405.4.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 INSPECTION CHECKLIST NEED TO BE COMPLETED. CHECKLIST
 NEED TO BE CHECKED WITH THE ITEMS THAT APPLY.
  
 E) ORIGINAL COMMENT:
 PROVIDE THE NAME OF THE INDIVIDUAL COMPLETING THE
 ENERGY CALCULATIONS AS REQUIRED BY SEC. R405.4.2
 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL. THE NAME OF THE
 PERSON COMPLETING THE ENERGY CALCULATIONS WAS NOT
 PROVIDED. ONLY A COPY OF A SIGNATURE WAS PROVIDED.
 PROVIDE THE COMPLETE NAME OF THE PERSON COMPLETING THE
 CALCULATIONS.
  
 NOTE: LABEL FOR WINDOWS AND DOORS U-FACTOR AND SHGC
 FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL BE
 REQUIRED FOR VERIFICATION.
  
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2016-10-26 Cont ID  
Sent By jgomez Date 2016-10-26 Time 10:53 Rev Time 0.00
Received By jgomez Date 2016-10-26 Time 10:53 Sent To  
Notes
2016-10-26 10:55:3710/26/16 TALKED TO RICHARD BARNES (ARCH.) TO GO OVER
 COMMENTS (# OF PEOPLE , A/C SIZING, A/C SEER).
  
 10/26/16 TALKED TO TONY PIEDRA (CONTRACTOR) TO GO OVER
 COMMENTS AND PROVISO. HE SAID HE'LL RESUBMIT ALONG WITH
 LANDSCAPE REQUEST.
  
  
 RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 CHECKLIST.
 CODE: FBC-5TH EDITION (2014).
  
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT CONTRACTOR MAY SUBMIT REQUESTED INFORMATION
 AFTER THE PERMIT IS ISSUED AND BEFORE INSPECTIONS TO
 AVOID CONFLICTS/DELAYS. REVISION FEES MAY APPLY.
 CONTRACTOR TO ADVICE IF RESUBMITTING INFORMATION NOW OR
 IF PROVISO OPTION IS PREFERRED AT THIS TIME.
  
 1- REVISE ENERGY CALCULATIONS SUBMITTED:
 A) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM, INCLUDING CORRECT OWNER'S NAME ("HOMEOWNER" IS
 NOT AN OWNER), BUILDER NAME, PERMIT OFFICE AND
 JURISDICTION NUMBER. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 B) REVISE NUMBER OF OCCUPANTS SHOWN UNDER "SPACES" ON
 PAGE 2 OF 4. THIS IS A THREE BEDROOM HOUSE. CLARIFY WHY
 CONSIDERING ONLY ONE OCCUPANT. THE NUMBER OF OCCUPANTS
 MAY AFFECT THE A/C SIZING LOAD CALCULATIONS. A HIGH
 NUMBER OF OCCUPANTS MAY RESULT TO OVERSIZE THE A/C
 EQUIPMENT. ON THE OTHER HAND, A LOW NUMBER OF OCCUPANTS
 MAY RESULT TO UNDERSIZE THE A/C EQUIPMENT. PROVIDE THE
 COMPLETE A/C LOAD CALCULATIONS (NOT JUST THE SUMMARY)
 TO VERIFY EQUIPMENT SIZING. EQUIPMENT CAN NOT BE
 OVERSIZED OR UNDERSIZED. SEE SEC. R403.6.1 AND SEC.
 R403.6.1.1 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 TYPICALLY A THREE BEDROOM HOUSE IS OCCUPIED BY MORE
 THAN ONE PERSON. THE PURPOSE OF THE ENERGY CALCULATIONS
 AND EQUIPMENT SIZING IS TO CONTRIBUTE TO THE ENERGY
 CONSERVATION BY PROPERLY DESIGNING THE STRUCTURE AND
 THE EQUIPMENT TO BE USED. IF ONLY USING ONE PERSON FOR
 THE DESIGN PARAMETERS, THEN PROVIDE COMPLETE
 DOCUMENTATION SUPPORTING THIS DESIGN APPROACH.
 DOCUMENTATION WILL BE FORWARDED TO THE BUILDING
 OFFICIAL FOR REVIEW AND APPROVAL.
  
 C) SEC. R806.2 OF FBC-RESIDENTIAL, 5TH EDITION (2014)
 REQUIRES 1/150 ATTIC VENTILATION RATIO. ATTIC
 INFORMATION ON PAGE 2 OF 4 SPECIFIES 1/300 ATTIC
 VENTILATION RATIO. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING HOW THIS HOUSE COMPLIES WITH THE
 EXCEPTION OF SEC. R806.2 FOR 1/300 ATTIC VENTILATION
 RATIO. OTHERWISE REVISE AS REQUIRED.
  
 D) REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 E) MISSING THE INSPECTION CHECKLIST AS REQUIRED BY SEC.
 R405.4.2 FBC-ENERGY CONSERVATION.
  
 F) PROVIDE THE NAME OF THE INDIVIDUAL COMPLETING THE
 ENERGY CALCULATIONS AS REQUIRED BY SEC. R405.4.2
 FBC-ENERGY CONSERVATION.
  
 G) BUILDER TO COMPLETE AND PROVIDE THE EPL DISPLAY
 CARD. SEC. R405.4.2 FBC-ENERGY CONSERVATION.
  
 NEW COMMENT:
 H) ITEM #12 SPECIFIES 18 SEER FOR THE COOLING
 EQUIPMENT. FLOOR PLAN M-1 SPECIFIES 15 SEER. REVISE AS
 REQUIRED TO MATCH. SEC. R103.2 FBC-ENERGY CONSERVATION.
  
 NOTE: LABEL FOR WINDOWS AND DOORS U-FACTOR AND SHGC
 FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL BE
 REQUIRED FOR VERIFICATION.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE. DON'T
 STAPLE OLD DRAWINGS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
 10/26/16 TALKED TO RICHARD BARNES (ARCH.) TO GO OVER
 COMMENTS (# OF PEOPLE , A/C SIZING, A/C SEER).
  
 10/26/16 TALKED TO TONY PIEDRA (CONTRACTOR) TO GO OVER
 COMMENTS AND PROVISO. HE SAID HE'LL RESUBMIT ALONG WITH
 LANDSCAPE REQUEST.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-10-03 Cont ID  
Sent By jgomez Date 2016-10-03 Time 11:47 Rev Time 0.00
Received By jgomez Date 2016-10-03 Time 11:47 Sent To  
Notes
2016-10-03 11:52:23RESIDENTIAL (R3) ADDITION/ALTERATION THIRD BUILDING
 REVIEW CHECKLIST.
 CODE: FBC-5TH EDITION (2014).
  
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT CONTRACTOR MAY SUBMIT REQUESTED INFORMATION
 AFTER THE PERMIT IS ISSUED AND BEFORE INSPECTIONS TO
 AVOID CONFLICTS/DELAYS. REVISION FEES MAY APPLY.
 CONTRACTOR TO ADVICE IF RESUBMITTING INFORMATION NOW OR
 IF PROVISO OPTION IS PREFERRED AT THIS TIME.
  
  
  
 ORIGINAL COMMENT:
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 RESPONSE:
 ENERGY CALCULATIONS SUBMITTED:
 A) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM, INCLUDING CORRECT OWNER'S NAME ("HOMEOWNER" IS
 NOT AN OWNER), BUILDER NAME, PERMIT OFFICE AND
 JURISDICTION NUMBER. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 B) REVISE NUMBER OF OCCUPANTS SHOWN UNDER "SPACES" ON
 PAGE 2 OF 4. THIS IS A THREE BEDROOM HOUSE. PROVIDE
 PROOF OF WHY CONSIDERING ONLY ONE OCCUPANT. (THE NUMBER
 OF OCCUPANTS MAY AFFECT THE A/C SIZING LOAD
 CALCULATIONS). SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 C) SEC. R806.2 OF FBC-RESIDENTIAL, 5TH EDITION (2014)
 REQUIRES 1/150 ATTIC VENTILATION RATIO. ATTIC
 INFORMATION ON PAGE 2 OF 4 SPECIFIES 1/300 ATTIC
 VENTILATION RATIO. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING HOW THIS HOUSE COMPLIES WITH THE
 EXCEPTION OF SEC. R806.2 FOR 1/300 ATTIC VENTILATION
 RATIO. OTHERWISE REVISE AS REQUIRED.
  
 D) REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 E) MISSING THE INSPECTION CHECKLIST AS REQUIRED BY SEC.
 R405.4.2 FBC-ENERGY CONSERVATION.
  
 F) PROVIDE THE NAME OF THE INDIVIDUAL COMPLETING THE
 ENERGY CALCULATIONS AS REQUIRED BY SEC. R405.4.2
 FBC-ENERGY CONSERVATION.
  
 G) BUILDER TO COMPLETE AND PROVIDE THE EPL DISPLAY
 CARD. SEC. R405.4.2 FBC-ENERGY CONSERVATION.
  
 NOTE: LABEL FOR WINDOWS AND DOORS U-FACTOR AND SHGC
 FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL BE
 REQUIRED FOR VERIFICATION.
  
 ORIGINAL COMMENT:
 2- SITE PLAN FOOTPRINT SUBMITTED DOESN'T MATCH PROPOSED
 FLOOR PLAN ON SHEET A-5. REVISE AS REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 REVISE SITE PLAN: THE DRAWING IS NOT CLEAR. THE
 ADDITION WAS BLOCKED BY A DARK BACKGROUND. DRAWING IS
 NOT LEGIBLE. SEC. 107.2.1 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE. DON'T
 STAPLE OLD DRAWINGS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-08-10 Cont ID  
Sent By jgomez Date 2016-08-09 Time 17:53 Rev Time 0.00
Received By jgomez Date 2016-08-09 Time 17:35 Sent To  
Notes
2016-08-09 17:47:44 
 RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC-5TH EDITION (2014).
  
 ORIGINAL COMMENT:
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. PERMIT CAN NOT BE ISSUED
 WITHOUT THE ENERGY CALCULATIONS. SEC. R103.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 ORIGINAL COMMENT:
 2- DOORS AND WINDOWS DESIGN PRESSURES SHOWN ON SHEET
 A-7 DON'T MATCH DESIGN PRESSURES SPECIFIED ON SHEET
 A-2. REVISE AS REQUIRED. SEC. R301 OF FBC-RESIDENTIAL,
 5TH EDITION (2014).
 RESPONSE:
 THE DESIGN PRESSURES WERE DELETED FROM SHEET A-2. THOSE
 DESIGN PRESSURES WERE CORRECT. THEY CORRESPONDED TO
 EXPOSURE "C". THE DESIGN PRESSURES SHOWN ON SHEET A-7
 DON'T CORRESPOND TO EXPOSURE "C". ALSO, THE DESIGN
 PRESSURES ON THE SMALL OPENINGS CAN NOT BE LOWER THAN
 THE BIGGER OPENINGS. THE SMALLER THE TRIBUTARY AREA,
 THE HIGHER THE DESIGN PRESSURES. REVISE ALL THE DESIGN
 PRESSURES SHOWN ON SHEET A-7. NOTE: MAKE SURE DESIGN
 PRESSURES ARE GIVEN BASED ON THE OPENING SIZE AND
 DISTANCE FROM THE EDGE OF BUILDING. FIGURE R301.2(7)
 REQUIRES 4'-0" MINIMUM AS THE EDGE DISTANCE FOR ALL
 CASES.
  
 ORIGINAL COMMENT:
 3- PROVIDE COMPLETE WALL SECTION THRU GABLE END SHOWING
 COMPLIANCE WITH SEC. R609.4 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
 RESPONSE:
 RESPONSE LETTER STATED THAT "MASONRY WALL IS EXISTING".
 THIS IS NOT CORRECT. THE WEST GABLE END WALL BY THE
 KITCHEN AREA IS NEW. THE "PERSPECTIVE OF GABLE END
 TRUSS" DETAIL SHOWN ON SHEET A-6 DOESN'T MATCH TRUSS
 PLAN SHOWN ON SAME SHEET. THERE IS NO GABLE END TRUSS.
 THERE ARE NOT CONNECTORS SPECIFIED FOR THE 2X4
 OUTRIGGERS. THERE ARE NOT GABLE END VERTICAL WEBS
 LARGER THAN 4'-0". THEREFORE THE VERTICAL REINFORCEMENT
 WOULDN'T APPLY. SEC. R609.4 OF FBC-RESIDENTIAL REQUIRES
 CONCRETE BLOCK WALL TO BE CONTINUOUS TO THE ROOF LINE.
 OTHERWISE, WOOD FRAME CONSTRUCTION REQUIRES CONFORMANCE
 WITH TABLES R609.4A AND R609.4B AND FIGURE R609.4. SEE
 EXCEPTION FOR SEC. R609.4. PROVIDE A COMPLETE
 SECTION/DETAIL SHOWING HOW PROVIDING A CONTINUOUS LOAD
 PATH FROM THE ROOF TO THE CONCRETE BLOCK WALL. SPECIFY
 ALL CONNECTORS AS REQUIRED BY SEC. R801.2
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) FIXED WINDOWS AS SHOWN ON PLANS. NONE SUBMITTED AT
 THIS TIME.
  
 ORIGINAL COMMENT:
 B) INSWING ENTRY DOOR AS SHOWN ON PLANS.
  
 RESPONSE:
 THERE ARE TWO DIFFERENT PRODUCT APPROVALS SUBMITTED.
 NONE OF THEM MATCH SINGLE INSWING DOOR TYPE AS SHOWN ON
 PLANS. BOTH PRODUCT APPROVALS ARE FOR DOUBLE DOORS OR
 SINGLE DOOR WITH SIDELITE. NOT SINGLE DOORS ONLY.
 PROVIDE PRODUCT APPROVAL THAT MATCHES PLANS AND DOOR
 SCHEDULE.
  
 NOTE: DOOR SCHEDULE ON SHEET A-8 DOESN'T MATCH
 INFORMATION SHOWN ON PLANS. REVISE AS REQUIRED TO
 MATCH.
  
 ORIGINAL COMMENT:
 C) SHUTTERS IF DOORS AND WINDOWS DON'T HAVE IMPACT
 GLASS. AND PROVIDE COMPLETE INSTALLATION SCHEDULE.
  
 RESPONSE:
 FRENCH DOORS FLORIDA PRODUCT APPROVAL FL16904-R3
 SUBMITTED IS FOR NON-IMPACT DOORS. NEED TO PROVIDE
 SHUTTERS PRODUCT APPROVAL AND COMPLETE INSTALLATION
 SCHEDULE.
  
 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 NEW COMMENT:
 6- SITE PLAN FOOTPRINT SUBMITTED DOESN'T MATCH PROPOSED
 FLOOR PLAN ON SHEET A-5. REVISE AS REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE. DON'T
 STAPLE OLD DRAWINGS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-04-11 Cont ID  
Sent By jgomez Date 2016-04-11 Time 12:17 Rev Time 0.00
Received By jgomez Date 2016-04-11 Time 12:17 Sent To  
Notes
2016-04-11 13:23:4807/27/16:
 TALKED TO MICHELLE (PBC IMPACT FEES) TOTAL NEW A/C AREA
 754 S.F. AND TOTAL NEW PORCH AREA 247S.F. (AREA
 CALCULATIONS DONE ON PENCIL ON DRAWING A-5). ACCORDING
 TO PAPA AND CITY RECORDS THE BASE AREA WAS 854 S.F. THE
 REST WAS ENCLOSED PORCH, FINISHED PORCH, UNFINISHED
 STORAGE AND FINISHED STORAGE. TOTAL WAS 1360 S.F. SEE
 PAPA). JG.
  
  
 RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: FBC-5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- GENERAL NOTES ON SHEET A-1 REFERENCE 2010 FBC. THE
 CURRENT CODE IS THE FBC-RESIDENTIAL, 5TH EDITION
 (2014). REVISE AS REQUIRED. CHAPTER 553 FLORIDA
 STATUTES.
  
 3- SHEET A-2:
 A) STRUCTURAL DESIGN CRITERIA AND CODES REFERENCE 2010
 FBC. THE CURRENT CODE IS THE FBC-RESIDENTIAL, 5TH
 EDITION (2014). REVISE AS REQUIRED. CHAPTER 553 FLORIDA
 STATUTES.
  
 B) UPDATE YEAR FOR ALL THE REFERENCE STANDARDS SHOWN ON
 SHEET A-2. SEE CHAPTER 46 FBC-RESIDENTIAL, 5TH EDITION
 (2014) FOR CURRENT YEAR AND REVISE AS REQUIRED. FOR
 EXAMPLE THE CURRENT ACI EDITION IS THE ACI-11 NOT
 ACI-95.
  
 C) FLOOR AND ROOF LIVE LOADS SHOWN ON THE STRUCTURAL
 DESIGN CRITERIA & CODES DOESN'T MATCH LOADS SHOWN ON
 THE PRE-ENGINEERED WOOD TRUSSES NOTES ON SAME SHEET.
 SEE FOOTNOTES "B" AND "G" OF TABLE R301.5 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014) AND REVISE AS
 REQUIRED TO MATCH.
  
 D) THE CURRENT ASCE 7 IS THE ASCE 7-10 NOT ASCE 7-98
 REVISE THE PRE-ENGINEERED WOOD TRUSSES NOTES. CHAPTER
 553 F.S.
  
 E) REVISE NAIL SIZE AND TYPE SPECIFIED FOR THE PLYWOOD
 SHEATHING. SEC. R803.2.3.1 REQUIRES 8 D RING SHANK
 NAILS. OR PROVIDE ENGINEER ANALYSIS SHOWING THAT THE
 10D NAILS ARE EQUIVALENT TO THE 8D RING SHANK NAILS.
  
 4- SHEET A-4:
 A) UPDATE CODE. THE CURRENT CODE IS THE
 FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE AS
 REQUIRED. CHAPTER 553 FLORIDA STATUTES. ALSO, UPDATE
 THE LOADING NOTES AT THE BOTTOM OF THIS SHEET.
  
 B) CLARIFY THE SOIL BEARING CAPACITY 2500 PSI OR 2500
 PSF. SEC. 107.2.1 CITY AMENDMENTS.
  
 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $90,000. THE
 PERMIT FEE BALANCE IS $2148.70.
  
 6- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 7- SPECIFY ATTIC ACCESS SIZE AND LOCATION AT NEW
 ADDITION TO COMPLY WITH SEC. R807 OF FBC-RESIDENTIAL,
 5TH EDITION (2014).
  
 8- SHEET A-6. SPECIFY BEAMS AT THE NEW COVERED PORCH.
 AND, SPECIFY CONNECTORS AT THE ENDS OF EACH BEAM. SEC.
 R801.2 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 9- DOORS AND WINDOWS DESIGN PRESSURES SHOWN ON SHEET
 A-7 DON'T MATCH DESIGN PRESSURES SPECIFIED ON SHEET
 A-2. REVISE AS REQUIRED. SEC. R301 OF FBC-RESIDENTIAL,
 5TH EDITION (2014).
  
 10- PROVIDE COMPLETE WALL SECTION THRU GABLE END
 SHOWING COMPLIANCE WITH SEC. R609.4 OF FBC-RESIDENTIAL,
 5TH EDITION (2014).
  
 11- SHEET A-6: SEC. R4409.13.3.2.5 SPECIFIED FOR
 UNVENTED ATTIC APPLIES TO THE HIGH VELOCITY AREAS ONLY.
 IF DESIGNING AN UNVENTED ATTIC, THEN SEE SEC. R806.5 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014) AND REVISE AS
 REQUIRED.
  
 12- TYPICAL WALL SECTION ON SHEET A-7:
 A) CLEARLY SPECIFY TYPE AND LOCATION OF INSULATION.
 NOTE: COORDINATE WITH UNVENTED ATTIC AND ITEM #11
 ABOVE. SEC. R806.5 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 B) PROVIDE COMPLETE SPECIFICATIONS FOR THE TIE BEAM.
 SEC. R801.2 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 13- PROVIDE ICC EVALUATION REPORT FOR THE TYPE OF
 INSULATION SPECIFIED ON ITEM #12(A) ABOVE. SEC. R316 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 14- ROOF FRAMING NOTES ON SHEET A-7 REFERENCE 2010 FBC.
 THE CURRENT CODE IS THE FBC-RESIDENTIAL, 5TH EDITION
 (2014). REVISE AS REQUIRED. CHAPTER 553 FLORIDA
 STATUTES.
  
 15- CLEARLY SPECIFY TYPE AND SIZE OF EXISTING BEDROOM
 WINDOWS TO BE REPLACED AND TYPE AND SIZE OF PROPOSED
 WINDOWS TO VERIFY EGRESS REQUIREMENTS OF SEC. 704 OF
 FBC-EXISTING BUILDING, 5TH EDITION (2014).
  
 16- SPECIFY CARBON MONOXIDE ALARM BY THE NEW MASTER
 BEDROOM AS REQUIRED BY SEC. R315 OF FBC-RESIDENTIAL,
 5TH EDITION (2014).
  
 17- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) METAL ROOF AS SPECIFIED ON PLANS.
  
 B) ALL WINDOW TYPES AS SPECIFIED ON PLANS.
  
 C) INSWING ENTRY DOOR AS SHOWN ON PLANS.
  
 D) OUTSWING FRENCH DOORS AS SHOWN ON PLANS.
  
 E) ALL STRUCTURAL CONNECTORS SPECIFIED ON PLANS.
 PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE CONNECTOR OR LIST THE FLORIDA
 PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED
 CONNECTOR.
  
 F) PRECAST LINTELS (IF SPECIFIED ON PLANS)
  
 G) SHUTTERS IF DOORS AND WINDOWS DON'T HAVE IMPACT
 GLASS. AND PROVIDE COMPLETE INSTALLATION SCHEDULE.
  
 18- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE. DON'T
 STAPLE OLD DRAWINGS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-10-11 Cont ID  
Sent By vperez Date 2016-10-11 Time 10:59 Rev Time 0.00
Received By vperez Date 2016-10-11 Time 10:59 Sent To  
Notes
2016-10-11 11:01:18PROVISO- SHOW ON PLANS THE AIC RATING OF SERVICE AND
 PANEL EQUIPMENT

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-08-09 Cont ID  
Sent By vperez Date 2016-08-09 Time 08:02 Rev Time 0.00
Received By vperez Date 2016-08-09 Time 08:02 Sent To  
Notes
2016-08-09 08:07:272ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RESIDENTIAL BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 PENDING COMMENTS AND NEW PER SCOPE NOW SHOWN REGARDING
 INSTA HOT 18KV:
  
 2. PROVIDE AIC CALCULATIONS FOR NEW SERVICE PER FBC RES
 E3606
 1. SHOW AIC RATING ON PANEL SCHEDULE. FBC RES E3606
 2. CORRECT INSTA HOT 18KV ON CALCULATION SUBMITTED, ON
 PANEL SCHEDULE AND LOADS. PANEL SCHEDULE SHOWS 4500W.
 CALCULATIONS SHOW 5000, CORRECT A SUBMIT REFLECTING
 18,000W. VERIFY 200AMP SERVICE IS SUFFICIENT.
 6. FEEL FREE TO CONTACT ME AT THE NUMBER BELOW SHOULD
 YOU HAVE ANY QUESTIONS OR CONCERNS.
  
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-12 Cont ID  
Sent By vperez Date 2016-03-12 Time 05:06 Rev Time 0.00
Received By vperez Date 2016-03-12 Time 05:06 Sent To  
Notes
2016-03-12 05:17:23INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RESIDENTIAL BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. UPDATE ALL APPLICABLE CODES ON GENERAL NOTES TO
 REFLECT NEW FBC 2014 5TH EDITION SET AND NFPA 70 NEC
 2011.
 2. PROVIDE AIC CALCULATIONS FOR NEW SERVICE PER FBC RES
 E3606
 3. PROVIDE A NOTE TO INDICATE THE REQUIREMENTS OF FBC
 RES 404.1- 75% OF LAMPS TO BE HIGH EFFICACY LAMPS.
 4. SHOW ON PANEL SCHEDULE THE CONDUCTOR SIZE FOR THE
 WATER HEATER. NEC 310.15B16
 5. PER FBC RES E3706, SHOW AND LABEL BRANCH CIRCUITS ON
 PANEL BOARDS SPECIFIC AREA AS TO WHAT IT SERVES.
 GENERAL LIGHTING DESIGNATION WILL NOT SUFFICE. MUST BE
 CLEAR AND EVIDENT AS TO WHAT IT ENERGIZES.
 6. FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. FEEL
 FREE TO CONTACT ME AT THE NUMBER BELOW SHOULD YOU HAVE
 ANY QUESTIONS OR CONCERNS.
  
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2017-01-13 Cont ID  
Sent By cpuell Date 2017-01-13 Time 12:48 Rev Time 0.00
Received By cpuell Date 2017-01-05 Time 11:00 Sent To  
Notes
2017-01-06 11:00:59RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-11-22 Cont ID  
Sent By cpuell Date 2016-11-22 Time 09:25 Rev Time 0.00
Received By cpuell Date 2016-11-10 Time 10:01 Sent To  
Notes
2016-11-15 19:39:07ROUTED TO JULIO GOMEZ 11/15/2016 - JORGE V.
2016-11-14 10:02:04RESUB ROUTED TO JVALIDO

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-10-25 Cont ID  
Sent By cpuell Date 2016-10-25 Time 07:59 Rev Time 0.00
Received By cpuell Date 2016-09-27 Time 13:00 Sent To  
Notes
2016-09-29 13:01:04R29

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-24 Cont ID  
Sent By lmarchan Date 2016-08-24 Time 16:23 Rev Time 0.00
Received By lmarchan Date 2016-07-29 Time 11:20 Sent To  
Notes
2016-07-29 11:20:57R32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-11 Cont ID  
Sent By jgomez Date 2016-04-11 Time 12:17 Rev Time 0.00
Received By jgomez Date 2016-03-08 Time 13:39 Sent To  
Notes
2016-03-12 05:17:543/12 TO R09
2016-03-08 13:39:48R09

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2016-08-09 Cont ID  
Sent By jgomez Date 2016-08-09 Time 18:25 Rev Time 0.00
Received By jgomez Date 2016-08-09 Time 18:25 Sent To  
Notes
2016-08-09 18:26:16$180.65 PAID. MU-2016-19095.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-04-11 Cont ID  
Sent By jgomez Date 2016-04-11 Time 13:23 Rev Time 0.00
Received By jgomez Date 2016-04-11 Time 13:23 Sent To  
Notes
2016-04-11 13:24:141- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2016-11-18 Cont ID  
Sent By eschneid Date 2016-11-18 Time 16:31 Rev Time 0.25
Received By eschneid Date 2016-11-18 Time 16:31 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2016-10-05 Cont ID  
Sent By eschneid Date 2016-10-05 Time 09:14 Rev Time 0.25
Received By eschneid Date 2016-10-05 Time 09:14 Sent To  
Notes
2016-10-05 09:17:26FAILED
  
 THE VALUE OF THE CONSTRUCTION ($90,000) EXCEEDS 50% OF
 THE STRUCTURE'S VALUE ($88,662**) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2017-01-12 Cont ID  
Sent By jvalido Date 2017-01-12 Time 18:02 Rev Time 0.00
Received By jvalido Date 2017-01-12 Time 17:49 Sent To  
Notes
2017-01-11 11:07:14REVISED LOAD CALCULATIONS SUBMITTED. JG.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2016-11-21 Cont ID  
Sent By jgomez Date 2016-11-21 Time 17:47 Rev Time 0.00
Received By jvalido Date 2016-11-21 Time 17:10 Sent To  
Notes
2016-11-21 14:38:39REVISED DRAWING SUBMITTED. JG.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-11-15 Cont ID  
Sent By jvalido Date 2016-11-15 Time 19:37 Rev Time 0.00
Received By jvalido Date 2016-11-15 Time 19:37 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-10-24 Cont ID  
Sent By jvalido Date 2016-10-24 Time 17:57 Rev Time 0.00
Received By jvalido Date 2016-10-24 Time 17:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-08-31 Cont ID  
Sent By jgomez Date 2016-08-31 Time 16:29 Rev Time 0.00
Received By jvalido Date 2016-08-31 Time 15:47 Sent To  
Notes
2016-08-31 16:26:28 
 FLORIDA ENERGY CODE FBC 2014
  
 (1) PROVIDE ENERGY CALCULATIONS AND HEAT LOAD
 CALCULATIONS AS PER FBC ENERGY CODE 2014.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-04-04 Cont ID  
Sent By jvalido Date 2016-04-04 Time 15:14 Rev Time 0.00
Received By jvalido Date 2016-04-04 Time 14:58 Sent To  
Notes
2016-04-04 15:13:38CITY OF WEST PALM BEACH
 LOCAL AMENDMENTS TO THE
 FLORIDA BUILDING CODE (FBC) 2010
 CHAPTER 1 ADMINISTRATION
  
 107.2.1
  
 (1)PROVIDE EXHAUST IN BATHROOMS AS PER FBC 2014 SHOW
 DUCT ROUTE WITH SIZES OF DUCT AND TERMINATION
 LACATION..
 (2)PROVIDE SPECIFIC INFORMATION FOR THE NEW AHU AND
 CONDENSER ( MANUFACTURER, MODEL #, TOTAL BTU, SENSIBLE
 BTU, ETC...).
 (3)PROVIDE DIMENSIONS OF SUPPLY AND RETURN GRILLS.
 (4)PROVIDE LOCATION OF RETURN GRILL WITH DIMENSIONS IN
 COMMON AREA FOR RETURN TO AHU.
 (5)PROVIDE CONDENSER TIE DOWN DETAIL.
 (6)PROVIDE AHRI SHEET.
 (7)SHOW LOCATION OF FANTECH UNIT IN GARAGE.
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-10-24 Cont ID  
Sent By gjohnson Date 2016-10-24 Time 11:29 Rev Time 0.00
Received By gjohnson Date 2016-10-24 Time 09:26 Sent To  
Notes
2016-10-03 14:23:38NEW DRAWING SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-07-30 Cont ID  
Sent By tklarge Date 2016-07-30 Time 10:53 Rev Time 0.00
Received By tklarge Date 2016-07-30 Time 10:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-03-17 Cont ID  
Sent By gjohnson Date 2016-03-17 Time 16:38 Rev Time 0.00
Received By gjohnson Date 2016-03-17 Time 16:38 Sent To  
Notes
2016-03-17 16:43:111ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLUMBING NOTES REFERENCE FBC 2010 IT SHALL BE FBC
 2014 5TH EDITION.
 2. SHOW LOCATION TYPE MAKE MODEL OF WATER HEATER.
 PER WPB AMEND TO FBC SEC 107.2.1
 3. ADD PLUMBING WORK TO APPLICATION.
 PER WPB AMEND TO FBC SEC 107.2.1

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2016-08-10 Cont ID  
Sent By jgomez Date 2016-08-10 Time 13:10 Rev Time 0.00
Received By jgomez Date 2016-08-10 Time 13:10 Sent To  
Notes
2016-08-10 13:11:32METAL ROOF NOA 12-0227.07.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-04-11 Cont ID  
Sent By jgomez Date 2016-04-11 Time 17:39 Rev Time 0.00
Received By jgomez Date 2016-04-11 Time 17:39 Sent To  
Notes
2016-04-11 17:40:041- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) METAL ROOF AS SPECIFIED ON PLANS.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2016-10-05 Cont ID  
Sent By eschneid Date 2016-10-05 Time 08:50 Rev Time 0.50
Received By eschneid Date 2016-10-05 Time 08:50 Sent To  
Notes
2016-10-03 14:24:33NEW DRAWINGS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 2 Status P Date 2016-08-16 Cont ID  
Sent By eschneid Date 2016-08-16 Time 10:16 Rev Time 0.25
Received By eschneid Date 2016-08-16 Time 09:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-03-18 Cont ID  
Sent By eschneid Date 2016-03-18 Time 17:29 Rev Time 0.50
Received By eschneid Date 2016-03-18 Time 17:29 Sent To  
Notes
2016-03-18 17:33:25FAILED
  
 1) PROVIDE A SITE PLAN THAT SHOWS THE SETBACK
 DIMENSIONS OF THE NEW ADDITION TO THE NORTH, WEST AND
 SOUTH PROPERTY LINES AND THE AC UNIT TO THE WEST
 PROPERTY LINE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.