Plan Review Details - Permit 16030329
Plan Review Stops For Permit 16030329 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2016-04-18 |
|
|
Cont ID |
|
Sent By |
vperez |
Date |
2016-04-18 |
Time |
09:42 |
Rev Time |
0.00 |
Received By |
vperez |
Date |
2016-04-18 |
Time |
09:42 |
Sent To |
|
|
Notes |
2016-04-18 09:42:27 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 NEC | | COMMENTS: | | | | 1. PROVISO- PROVIDE PUMP DATA SHEETS ON SITE. SPOKE TO | | ELECTRICAL QUALIFIER | | 2. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | QUESTIONS REGARDING THIS PROJECT. | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2016-03-10 |
|
|
Cont ID |
|
Sent By |
vperez |
Date |
2016-03-10 |
Time |
10:11 |
Rev Time |
0.00 |
Received By |
vperez |
Date |
2016-03-10 |
Time |
10:11 |
Sent To |
FIRE |
|
Notes |
2016-03-10 10:12:42 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 NEC | | COMMENTS: | | | | 1.PER FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS | | SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. | | ALSO SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE | | LOCATION, NATURE AND EXTENT OF WORK PROPOSED. SHOW IN | | DETAIL THAT IT WILL CONFORM TO CODE. | | 2.INFORMATION PROVIDED IS VERY VAGUE. THE FOLLOWING IS | | REQUIRED TO BE PROVIDED. | | 3.PROVIDE LOCATION OF PANEL BOARD AND RATING WHERE | | POWER WILL ORIGINATE TO PROPANE DISPENSER MOTOR. FBC | | 107.3.5 | | 4.SHOW ON PLANS REQUIRED SEAL OFF INSTALLATION FROM | | CLASSIFIED AREA BOUNDARIES. FBC 107.3.5 | | 5.SHOW THE ROUTING OF UNDERGROUND CONDUIT TO VERIFY | | DEPTH OF INSTALLATION. NEC 300.5 | | 6.CLARIFY EMT BEING INSTALLED IN CLASS 1 LOCATION; IS | | IT IN THE SHOP AREA? | | 7.SHOW NOTES TO COMPLY WITH NEC 514.11 DISCONNECTS AND | | 514.16 BONDING AND GROUNDING | | 8.SHOW ON FLOOR PLAN WHERE THE DISCONNECT WILL BE | | MOUNTED AND THE DISTANCE FROM DISPENSER. NEC 514.11 | | 9.FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL | | FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD YOU HAVE | | ANY QUESTIONS OR CONCERNS. | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2016-04-20 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2016-04-20 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2016-04-19 |
Time |
15:09 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2016-03-16 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2016-03-16 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2016-03-16 |
Time |
09:31 |
Sent To |
G |
|
Notes |
2016-03-16 09:57:25 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1. THERE IS INSUFFICIENT DETAIL TO PROPERLY REVIEW AND | | APPROVE THIS SUBMITTED PLAN. | | | | 2. PROVIDE A SITE PLAN INDICATING THE LOCATIONS OF ALL | | EQUIPMENT AND DIMENSIONS TO ALL BUILDINGS AND | | EQUIPEMNT. | | | | 3. PROVIDE ALL EQUIPMENT SPECIFICATION DETAILS, PRODUCT | | SHEETS. | | | | WHAT IS "EXPLOSION PROOF J.B. DISPENSOR"? | | | | WHAT IS " EXPLOSION PROOF EM SHUT OFF"? | | | | WHAT IS " SHUNT SQD 200A2P BLKER"? | | | | 4. THE DESIGN AND INSTALLATION SHALL COMPLY WITH THE | | APPROPRIATE NFPA FIRE CODES INCLUDING, BUT NOT LIMITED | | TO, NFPA 58, LIQUEFIED PETROLEUM GAS CODE; THE PROPOSED | | PROJECT SHALL MEET THE REQUIREMENTS OF THE 5TH EDITION | | OF FLORIDA FIRE PREVENTION CODE INCLUDING THE 2012 | | EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER APPLICABLE | | CODES OR STANDARDS, AND FLAMMABLE AND COMBUSTIBLE | | LIQUIDS SHALL COMPLY WITH NFPA 30, 2012 EDITION. | | | | 5. PROVIDE THE LOCATION OF THE NEAREST FIRE | | EXTINGUISHER, WITHIN 75'. | | | | 6. PROVIDE A BRIEF NARRATIVE OR STATEMENT REGARDING | | WHAT PURPOSE/SERVCIE THIS INSTALLATION PROVIDES. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2016-04-20 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2016-04-20 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2016-04-18 |
Time |
15:24 |
Sent To |
|
|
Notes |
2016-04-18 15:24:16 | RESUB ROUTED TO FIRE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-03-16 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2016-03-16 |
Time |
14:42 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2016-03-10 |
Time |
10:12 |
Sent To |
|
|
Notes |
2016-03-10 10:13:13 | 3/10 TO CAROLINE. NEEDS FIRE AND GAS REVIEW | 2016-03-08 13:34:35 | ELEC -$5000 |
|
|
|