Plan Review Details - Permit 16030329
Plan Review Stops For Permit 16030329
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-04-18 Cont ID  
Sent By vperez Date 2016-04-18 Time 09:42 Rev Time 0.00
Received By vperez Date 2016-04-18 Time 09:42 Sent To  
Notes
2016-04-18 09:42:27INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PROVISO- PROVIDE PUMP DATA SHEETS ON SITE. SPOKE TO
 ELECTRICAL QUALIFIER
 2. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-10 Cont ID  
Sent By vperez Date 2016-03-10 Time 10:11 Rev Time 0.00
Received By vperez Date 2016-03-10 Time 10:11 Sent To FIRE
Notes
2016-03-10 10:12:42INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1.PER FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS
 SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ALSO SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF WORK PROPOSED. SHOW IN
 DETAIL THAT IT WILL CONFORM TO CODE.
 2.INFORMATION PROVIDED IS VERY VAGUE. THE FOLLOWING IS
 REQUIRED TO BE PROVIDED.
 3.PROVIDE LOCATION OF PANEL BOARD AND RATING WHERE
 POWER WILL ORIGINATE TO PROPANE DISPENSER MOTOR. FBC
 107.3.5
 4.SHOW ON PLANS REQUIRED SEAL OFF INSTALLATION FROM
 CLASSIFIED AREA BOUNDARIES. FBC 107.3.5
 5.SHOW THE ROUTING OF UNDERGROUND CONDUIT TO VERIFY
 DEPTH OF INSTALLATION. NEC 300.5
 6.CLARIFY EMT BEING INSTALLED IN CLASS 1 LOCATION; IS
 IT IN THE SHOP AREA?
 7.SHOW NOTES TO COMPLY WITH NEC 514.11 DISCONNECTS AND
 514.16 BONDING AND GROUNDING
 8.SHOW ON FLOOR PLAN WHERE THE DISCONNECT WILL BE
 MOUNTED AND THE DISTANCE FROM DISPENSER. NEC 514.11
 9.FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL
 FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD YOU HAVE
 ANY QUESTIONS OR CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-04-20 Cont ID  
Sent By pleduc Date 2016-04-20 Time   Rev Time 0.00
Received By pleduc Date 2016-04-19 Time 15:09 Sent To PC
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-03-16 Cont ID  
Sent By pleduc Date 2016-03-16 Time   Rev Time 0.00
Received By pleduc Date 2016-03-16 Time 09:31 Sent To G
Notes
2016-03-16 09:57:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. THERE IS INSUFFICIENT DETAIL TO PROPERLY REVIEW AND
 APPROVE THIS SUBMITTED PLAN.
  
 2. PROVIDE A SITE PLAN INDICATING THE LOCATIONS OF ALL
 EQUIPMENT AND DIMENSIONS TO ALL BUILDINGS AND
 EQUIPEMNT.
  
 3. PROVIDE ALL EQUIPMENT SPECIFICATION DETAILS, PRODUCT
 SHEETS.
  
 WHAT IS "EXPLOSION PROOF J.B. DISPENSOR"?
  
 WHAT IS " EXPLOSION PROOF EM SHUT OFF"?
  
 WHAT IS " SHUNT SQD 200A2P BLKER"?
  
 4. THE DESIGN AND INSTALLATION SHALL COMPLY WITH THE
 APPROPRIATE NFPA FIRE CODES INCLUDING, BUT NOT LIMITED
 TO, NFPA 58, LIQUEFIED PETROLEUM GAS CODE; THE PROPOSED
 PROJECT SHALL MEET THE REQUIREMENTS OF THE 5TH EDITION
 OF FLORIDA FIRE PREVENTION CODE INCLUDING THE 2012
 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER APPLICABLE
 CODES OR STANDARDS, AND FLAMMABLE AND COMBUSTIBLE
 LIQUIDS SHALL COMPLY WITH NFPA 30, 2012 EDITION.
  
 5. PROVIDE THE LOCATION OF THE NEAREST FIRE
 EXTINGUISHER, WITHIN 75'.
  
 6. PROVIDE A BRIEF NARRATIVE OR STATEMENT REGARDING
 WHAT PURPOSE/SERVCIE THIS INSTALLATION PROVIDES.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-20 Cont ID  
Sent By pleduc Date 2016-04-20 Time   Rev Time 0.00
Received By pleduc Date 2016-04-18 Time 15:24 Sent To  
Notes
2016-04-18 15:24:16RESUB ROUTED TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-16 Cont ID  
Sent By skennedy Date 2016-03-16 Time 14:42 Rev Time 0.00
Received By skennedy Date 2016-03-10 Time 10:12 Sent To  
Notes
2016-03-10 10:13:133/10 TO CAROLINE. NEEDS FIRE AND GAS REVIEW
2016-03-08 13:34:35ELEC -$5000