Plan Review Details - Permit 16030281
Plan Review Stops For Permit 16030281 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2016-03-11 |
|
|
Cont ID |
|
Sent By |
vperez |
Date |
2016-03-11 |
Time |
06:31 |
Rev Time |
0.00 |
Received By |
vperez |
Date |
2016-03-11 |
Time |
06:30 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2016-03-08 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2016-03-08 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2016-03-08 |
Time |
15:45 |
Sent To |
E |
|
Notes |
2016-03-08 16:34:29 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | 1. KITCHEN HOOD SUPPRESSION SYSTEM SHALL BE TIED INTO | | THE BUILDING FIRE ALARM SYSTEM TO INITIATE A GENERAL | | FIRE ALARM CONDITION. | | | | NFPA 96 | | | | CHAPTER 10 FIRE-EXTINGUISHING EQUIPMENT | | | | 10.6 SYSTEM ANNUNCIATION. | | | | 10.6.1 UPON ACTIVATION OF AN AUTOMATIC | | FIRE-EXTINGUISHING SYSTEM, AN AUDIBLE ALARM OR VISUAL | | INDICATOR SHALL BE PROVIDED TO SHOW THAT THE SYSTEM HAS | | ACTIVATED. | | | | 10.6.2 WHERE A FIRE ALARM SIGNALING SYSTEM IS SERVING | | THE OCCUPANCY WHERE THE EXTINGUISHING SYSTEM IS | | LOCATED, THE ACTIVATION OF THE AUTOMATIC | | FIRE-EXTINGUISHING SYSTEM SHALL ACTIVATE THE FIRE ALARM | | SIGNALING SYSTEM. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-03-11 |
|
|
Cont ID |
|
Sent By |
vperez |
Date |
2016-03-11 |
Time |
06:33 |
Rev Time |
0.00 |
Received By |
vperez |
Date |
2016-03-11 |
Time |
06:33 |
Sent To |
|
|
Notes |
2016-03-11 06:34:14 | 3/11 TO CAROLINE | 2016-03-08 09:52:21 | ROUTED TO FIRE |
|
|
|
Account Summary | Usage Policy | Privacy Policy