Plan Review Stops For Permit 16030214 |
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
P |
Date |
2016-03-09 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-03-09 |
Time |
08:53 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-03-09 |
Time |
08:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2016-03-05 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-03-05 |
Time |
04:58 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-03-05 |
Time |
04:53 |
Sent To |
|
|
Notes |
2016-03-05 04:58:54 | 1) THE MAXIMUM BTU LOAD ON THE CSST IS 62K PER TABLE | | 402.4 (15).. THE LINE HAS TO BE SIZED BASED ON THE | | TOTAL DISTANCE OF 100 FEET FROM THE SOURCE OF DELIVERY. | | THE 3/4" LINE IS UNDERSIZED. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|
|
|