Plan Review Details - Permit 16030102
Plan Review Stops For Permit 16030102
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-04-21 Cont ID  
Sent By jwitmer Date 2016-04-21 Time 14:37 Rev Time 0.00
Received By jwitmer Date 2016-04-21 Time 13:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-04-15 Cont ID  
Sent By jwitmer Date 2016-04-15 Time 07:45 Rev Time 0.00
Received By jwitmer Date 2016-04-15 Time 06:31 Sent To  
Notes
2016-04-15 07:47:33BUILDING PLAN REVIEW
 W. P. B. REVISION: 16030102
 W. P. B. PERMIT: 15090236
 ADD:2087 PALM BEACH LAKES
 CONT: LM DEVELOPMENT GROUP
 TEL: ( 954)476-0800
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: FRI. APRIL 15/2016
 ACTION: DENIED
  
 1) NOTICE ONLY, NO ACTION NEEDED AT THIS TIME. REVISION
 INCREASE WENT FROM $10,000 TO $95,000.00 FOR THE
 MECHANICAL, ELECTRICAL & PLUMBING BEING ADDED TO THE
 BASE BUILDING PERMIT. NOTE VALUES GO ON THE BASE
 BUILDING PERMIT. SUB-PERMITS COME IN AS A $80.00 COST
 FOR ADMINISTRATIVE SERVICES, NO VALUE.
  
 2) SEMI-COMPLIED . REVISION SHEET S-4 PROVIDES THE
 ANCHOR DETAILS FOR THE CURB TO THE DECK AND THE ROOF
 TOP UNIT TO THE CURB. WE ARE STILL MISSING THE APPROVAL
 FOR THE CURB. THE CONTRACTOR IS TO SUBMIT THE CURB
 APPROVAL TO THE DESIGNER OF RECORD FOR REVIEW, IF
 APPROVED THEN THE DESIGNER OF RECORD IS TO APPLY THEIR
 SHOP DRAWING STAMP OF APPROVAL ON THE DOCUMENT BEFORE
 SUBMITTAL TO THE BUILDING DEPARTMENT. THE M1 SHEET
 SHOWS 5 NEW ROOF TOP A/C UNITS A REVISION TO THE
 ORIGINAL PERMIT.
  
 PLEASE PROVIDE THE ACTUAL ROUGH OPENING SIZE FOR THE
 ROOF PENETRATIONS. NOTE ON THE S-4 SHEET INDICATES
 COORDINATE THE EXACT SIZE OF HOLE AND REQUIREMENTS WITH
 MECHANICAL CONTRACTOR. THE SUBMITTAL FOR THE CURB SIZE
 IS UNKNOWN, NOT PROVIDED, HOW CAN THE STRUCTURAL CALCS
 BE ACCURATE?
  
 PLEASE NOTE THE SEA COAST ENGINEERING SUBMITTAL FOR THE
 MODEL/ TAG THC092 IS 2 TONS LARGER THAN SPECED IN ON
 M-1. PLEASE REVIEW SHEET M-1 RTU SPECIFICATIONS, UNIT
 SPECED IN IS A TSC072.
  
 2A) 2ND REQUEST UNTIL THE UNKNOWNS ABOVE ARE SATISFIED
 THE AND DISCREPANCIES CLEARED UP THE WIND LOAD
 CERTIFICATION CANNOT BE APPROVED.
 DISCREPANCIES!!!!!!2014 FBC-B 1604.4 ANALYSIS. LOAD
 EFFECTS ON STRUCTURAL MEMBERS AND THEIR CONNECTIONS
 SHALL BE DETERMINED BY METHODS OF STRUCTURAL ANALYSIS
 THAT TAKE INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY,
 GEOMETRIC COMPATIBILITY AND BOTH SHORT- AND LONG-TERM
 MATERIAL PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED
 TO RESIST THE OVERTURNING EFFECTS CAUSED BY THE LATERAL
 FORCES SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR
 WIND LOADS?
  
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2B) SEMI-COMPLIED, DISCREPANCIES , AND UNKNOWN
 DIMENSION IN OPENINGS.
 IF THE ABOVE MENTIONED IS DESIGNED BY EITHER A DELEGATE
 ENGINEER OR MECHANICAL ENGINEER THE ENGINEER OF RECORD
 WILL NEED TO REVIEW THE ENGINEERED DETAILS FOR
 CONFORMANCE WITH THEIR OVERALL DESIGN FOR THE BUILDING.
 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 ENGINEERING SUBMITTED FORM BOEDOIN HUTCHINSON A
 DELEGATE ENGINEER WILL NEED TO BE SUBMITTED TO STEPHEN
 H. PAGE THE ENGINEER OF RECORD, ALSO NOTE THE SUBMITTED
 CALCULATIONS ARE COPIES NOT SIGNED AND SEALED
 ORIGINALS. PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 3 SETS OF PLANS SUBMITTED ONLY (2) SETS OF COPIES
 SUBMITTED NOT (3) ORIGINALS.
  
 3) UNTIL THE DISCREPANCIES IN THE ROOF TOP RTU?S IS
 SATISFIED THIS COMMENT WILL STAND. THIS BUILDING WAS
 DESIGNED AS A SHELL BUILDING EXEMPT FROM THE ENERGY
 CODE. WITH THE A/C ROOF TOP UNITS BEING ADDED TO THE
 SCOPE OF WORK, ELECTRICAL AND PLUMBING FOR THE HOOK UP
 OF THESE UNITS THE BUILDING NO LONGER QUALIFIES AS A
 SHELL BUILDING AND WILL NEED TO MEET THE REQUIREMENTS
 FOUND UNDER THE 2014 FBC-ENERGY CODE;
 3A) C401.2 APPLICATION. COMMERCIAL BUILDINGS SHALL
 COMPLY WITH ONE OF THE FOLLOWING:
 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1.
 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND
 C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY
 WITH EITHER SECTION C406.2, C406.3 OR
 C406.4.
 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2,
 C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE
 BUILDING ENERGY COST SHALL BE EQUAL
 TO OR LESS THAN 85 PERCENT OF THE STANDARD REFERENCE
 DESIGN BUILDING.
  
 NOTE ASHRAE 90 CALCS. WERE SUBMITTED BUT THE MANDATORY
 REQUIREMENTS FOUND ON PAGE 8 OF 13 NOT COMPLETED. TO BE
 CHECKED AT COMPLIANCE SUBMISSION, ALL BOXES WERE LEFT
 BLANK!!!!!!
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-11 Cont ID  
Sent By jwitmer Date 2016-03-11 Time   Rev Time  
Received By jwitmer Date 2016-03-11 Time 06:01 Sent To  
Notes
2016-03-11 07:34:02BUILDING PLAN REVIEW
 W. P. B. REVISION: 16030102
 W. P. B. PERMIT: 15090236
 ADD:2101 PALM BEACH LAKES (744343190020900)
 CONT: LM DEVELOPMENT GROUP
 TEL: ( 954)476-0800
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: FRI. MARCH 11/2016
 ACTION: DENIED
  
 1) THE CONTRACTOR HAS INCREASED THE SCOPE OF WORK FROM
 JUST A SHELL BUILDING WITH THE ADDITIONAL WORK INCLUDED
 MECHANICAL, PLUMBING AND ELECTRICAL.
 THE VALUE OF THE INCREASE IN THE SCOPE OF WORK IS
 DECLARED AS $10,000.00 DOLLORS. SHEET M1 SHOWS 5 ROOF
 TOP A/C UNITS ALONE, NOT COUNTING THE ADDITIONAL
 ELECTRICAL AND PLUMBING WORK AS WELL AS THE BUILDING
 CONTRACTORS WORK.
  
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) THE M1 SHEET SHOWS 5 NEW ROOF TOP A/C UNITS A
 REVISION TO THE ORIGINAL PERMIT. ON THE SHELL BUILDING
 SHEET S-4 SHOWED THE TYPICAL ROOF OPENING FRAMING
 DETAIL, BUT THERE ARE NO CURB DETAILS OF HOW THE CURB
 WILL BE ANCHORED, NOR IS THERE DETAILS OF HOW THE A/C
 UNIT WAS TO BE ANCHORED TO THE CURB.
 PLEASE PROVIDE DETAILS SHOWING CODE COMPLIANCE WITH:
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31) (D) ROOFING PRODUCTS AND ASSEMBLIES ROOF TOP
 CURBS.
  
 2A) 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON
 STRUCTURAL MEMBERS AND THEIR CONNECTIONS SHALL BE
 DETERMINED BY METHODS OF STRUCTURAL ANALYSIS THAT TAKE
 INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC
 COMPATIBILITY AND BOTH SHORT- AND LONG-TERM MATERIAL
 PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED TO RESIST
 THE OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS?
  
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2B) IF THE ABOVE MENTIONED IS DESIGNED BY EITHER A
 DELEGATE ENGINEER OR MECHANICAL ENGINEER THE ENGINEER
 OF RECORD WILL NEED TO REVIEW THE ENGINEERED DETAILS
 FOR CONFORMANCE WITH THEIR OVERALL DEDIGN FOR THE
 BUILDING. 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED
 BY DCA RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 ENGINEERING SUBMITTED FORM BOEDOIN HUTCHINSON A
 DELEGATE ENGINEER WILL NEED TO BE SUBMITTED TO STEPHEN
 H. PAGE THE ENGINEER OF RECORD, ALSO NOTE THE SUBMITTED
 CALCULATIONS ARE COPIES NOT SIGNED AND SEALED
 ORIGINALS. PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 3 SETS OF PLANS SUBMITTED ONLY (2) SETS OF COPIES
 SUBMITTED NOT (3) ORIGINALS.
  
 3) THIS BUILDING WAS DESIGNED AS A SHELL BUILDING
 EXEMPT FROM THE ENERGY CODE. WITH THE A/C ROOF TOP
 UNITS BEING ADDED TO THE SCOPE OF WORK, ELECTRICAL AND
 PLUMBING FOR THE HOOK UP OF THESE UNITS THE BUILDING NO
 LONGER QAULIFIES AS A SHELL BUILDING AND WILL NEED TO
 MEET THE REQUIREMENTS FOUND UNDER THE 2014 FBC-ENERGY
 CODE;
 3A) C401.2 APPLICATION. COMMERCIAL BUILDINGS SHALL
 COMPLY WITH ONE OF THE FOLLOWING:
 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1.
 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND
 C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY
 WITH EITHER SECTION C406.2, C406.3 OR
 C406.4.
 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2,
 C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE
 BUILDING ENERGY COST SHALL BE EQUAL
 TO OR LESS THAN 85 PERCENT OF THE STANDARD REFERENCE
 DESIGN BUILDING.
  
 NOTE ASHRAE 90 CALCS WERE SUBMITTEDBUTTHE MANDATORY
 REQUIREMENTS FOUND ON PAGE 8 OF 13 NOT COMPLETED. TO
 BECHECKED AT COMPLIANCE SUBMISSION, ALL BOXES WERE LEFT
 BLANK!!!!!!
  
 3B) NO LOAD CALS SUBMITTED.!!!!!!!! C403.2.1
 CALCULATION OF HEATING AND COOLING LOADS. SUBMIT 3 SETS
 OF CALCS.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-04-21 Cont ID  
Sent By mvaldes Date 2016-04-21 Time 17:34 Rev Time 0.00
Received By mvaldes Date 2016-04-21 Time 17:28 Sent To  
Notes
2016-04-21 17:35:59REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
 PASSED WITH A PROVISO :
  
 NEC 408.4 B DIRECTORY SHOWING SOURCE OF SUPPLY FOR THE
 SUB PANELS .
 NEC 225.37 IDENTIFICATION OF THE SERVICE DISCONECTING
 MEANS.
 NEC 230.2 E A PERMANT PLAQUE DISPLAYING ALL SERVICE
 LOCATIONS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-04-13 Cont ID  
Sent By mvaldes Date 2016-04-13 Time 12:30 Rev Time 0.00
Received By mvaldes Date 2016-04-13 Time 12:30 Sent To  
Notes
2016-04-13 12:34:00PASSED WITH A PROVISO :
  
 NEC 408.4 B DIRECTORY SHOWING SOURCE OF SUPPLY FOR THE
 SUB PANELS .
 NEC 225.37 IDENTIFICATION OF THE SERVICE DISCONECTING
 MEANS.
 NEC 230.2 E A PERMANT PLAQUE DISPLAYING ALL SERVICE
 LOCATIONS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-09 Cont ID  
Sent By skennedy Date 2016-03-09 Time 19:15 Rev Time 0.00
Received By mvaldes Date 2016-03-09 Time 19:15 Sent To  
Notes
2016-03-09 19:16:18JOB PERMIT NUMBER: 16030102
 JOB ADDRESS: 2087 PALM BEACH LAKES BLVD
 WEST PALM BEACH FLORIDA
 DATE: MARCH 9 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - ALL ELECTRICAL BOXES IN A DEMISING WALL SHALL COMPLY
 WITH NEC 300.21 & FBC-B SECTION 714. ANY FIRE RATED
 STRUCTURE OR SURFACE THAT IS COMPROMISED SHALL BE
 RETURNED TO ITS ORIGINAL FIRE-RATING WITH APPROVED FIRE
 SEALING MATERIALS.
 - NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A 125 VOLT,
 SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE OUTLET
 SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE
 SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED WITHIN 25 FT. OF THE EQUIPMENT. ( RTU 4 & 5
 WITHIN SIGHT. )
 - NEC 406.9(B) RECEPTACLES IN WET LOCATIONS. 15 AND 20
 AMPERE, 125 AND 250 VOLT RECEPTACLES INSTALLED IN A WET
 LOCATION SHALL HAVE AN ENCLOSURE THAT IS WEATHERPROOF
 WHETHER OR NOT THE ATTACHMENT PLUG CAP IS INSERTED. ALL
 15 AND 20 AMPERE, 125 AND 250 VOLT NON-LOCKING
 RECEPTACLES SHALL BE LISTED WEATHER-RESISTANT TYPE
 ?WR?.
 - NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL
 BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO
 PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP
 DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH
 ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE
 LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE
 CONSIDERED ACCESSIBLE TO PEDESTRIANS.
 - NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, PANELBOARDS.
 - NEC 250.94 BONDING FOR OTHER SYSTEMS. THE
 INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE
 INSTALLED.
 - FBC-E C405.7.3 VOLTAGE DROP. FEEDERS & CUSTOMER OWNED
 SERVICE CONDUCTORS SHALL BE SIZED FOR A MAXIMUM OF 2%
 VOLTAGE DROP. BRANCH CIRCUITS SHALL BE SIZED FOR A
 MAXIMUM OF 3% VOLTAGE DROP.
 - PLEASE CLARIFY CONDUIT DETAILS BY PROVIDING A FEEDER
 SCHEDULE SHOWING RACEWAY FILL SPECS.
 - PLEASE PROVIDE GUARDING TO SERVICE EQUIPMENT AND
 INTERIOR PANELS. NEC 110.27 , 110.12 IF SUBJECT TO
 ACCIDENTAL CONTACT. FURTHERMORE IDENTIFY SUB PANEL FOR
 ADDRESS 2089 AND 2087 ?
 - EMERGENCY LIGHTING IS REQUIRED AS MINIMUM FOR SHELL
 BUILD OUT. FBC-B 1006.2.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-03-07 Cont ID  
Sent By scaldero Date 2016-03-07 Time 12:10 Rev Time 0.00
Received By scaldero Date 2016-03-07 Time 12:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-04-21 Cont ID  
Sent By mvaldes Date 2016-04-21 Time 17:36 Rev Time 0.00
Received By mvaldes Date 2016-04-21 Time 17:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-15 Cont ID  
Sent By jwitmer Date 2016-04-15 Time 07:45 Rev Time 0.00
Received By jwitmer Date 2016-04-05 Time 09:53 Sent To  
Notes
2016-04-06 09:53:20C28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-11 Cont ID  
Sent By jwitmer Date 2016-03-11 Time 07:30 Rev Time 0.00
Received By jwitmer Date 2016-03-02 Time 14:55 Sent To  
Notes
2016-03-02 14:55:58C08

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-04-21 Cont ID  
Sent By ccole Date 2016-04-21 Time 17:12 Rev Time 0.00
Received By ccole Date 2016-04-21 Time 16:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-04-07 Cont ID  
Sent By ccole Date 2016-04-07 Time 14:12 Rev Time 0.00
Received By ccole Date 2016-04-07 Time 14:12 Sent To  
Notes
2016-04-07 14:25:262ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030102
 4/7/16
  
 1) THE ENERGY CALCULATION SUBMITTAL IS PROVIDING
 COMPLIANCE DATA FOR ONLY 4 OF THE 6 RTU'S TO BE
 INSTALLED. PLEASE PROVIDE A COMPLETE SUBMITTAL.
 2) THE SUBMITTED INVOICE COPY FROM THE COOL TEAM AT
 $12,000.00 DOES NOT INCLUDE THE COST OF THE 6 RTU'S.
 PLEAE PROVIDE THE TOTAL COST OF THE PROJECT INCLUDING
 LABOR, MATERIAL, EQUIPMENT INCLUDING THE RTU'S- SECTION
 109.3 WPB AMENDMENTS TO THE FBC-10 BUILDING CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-03-08 Cont ID  
Sent By ccole Date 2016-03-08 Time 09:48 Rev Time 0.00
Received By hmoser Date 2016-03-08 Time 09:29 Sent To  
Notes
2016-03-08 09:48:52PLAN DENIED
  
 1) VALUE IS TO LOW
 2) OUT DOOR AIR REQUIRED ON PLAN.
 PER TABLE 403.3 FBC (M) 2014
 3) DETAIL FROM THE ENGINEER ON CURB TO ROOF TIEDOWN
 AND RTU TO CURB TIEDOWN. PER SECTION 301.15
 WIND RESISTANCE 2014 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-03-04 Cont ID  
Sent By gjohnson Date 2016-03-04 Time 06:10 Rev Time 0.00
Received By tklarge Date 2016-03-04 Time 05:49 Sent To  
Notes
***NONE***