Plan Review Details - Permit 16030072
Plan Review Stops For Permit 16030072
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2017-02-15 Cont ID  
Sent By rmcdouga Date 2017-02-15 Time 15:26 Rev Time 0.00
Received By rmcdouga Date 2017-02-15 Time 15:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2017-02-03 Cont ID  
Sent By rmcdouga Date 2017-02-03 Time 10:35 Rev Time 0.00
Received By rmcdouga Date 2017-02-03 Time 07:29 Sent To  
Notes
2017-02-03 10:35:02PLAN
 REVIEW COMMENTS
  
 6TH REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE RESIDENTIAL BUILDING FORM R405 TO SHOW
 COMPLIANCE WITH THE ENERGY CODE THAT WAS SUBMITTED IS
 REQUIRED TO BE SIGNED AND DATED BY THE OWNER/AGENT. FBC
 ENERGY CONSERVATION R103.1.1.2
  
 2) SPECIFY THE SYSTEM TYPE, FASTENING OPTION AND DESIGN
 PRESSURE FOR THE GAF BUR ROOFING ASSEMBLY (NOA NO.
 13-1022.15). SUBMIT TWO SETS OF SIGNED AND SEALED RAS
 117 CALCULATIONS FOR ENHANCED FASTENING AS REQUIRED BY
 LIMITATION NUMBER 7 ON PAGE 16 OF THE NOA. THIS COMMENT
 HAS NOT BEEN ADDRESSED. ( IF YOU ELECT TO DO SO, THIS
 CAN BE SUBMITTED FOR REVIEW AT A LATER DATE. HOWEVER,
 IT WILL HAVE TO BE REVIEWED AND APPROVED BEFORE THE
 ROOFING IS INSTALLED. )
  
 3) THE PLANS WILL NEED TO BE REVIEWED BY PALM BEACH
 COUNTY TO DETERMINE IF ANY IMPACT FEES ARE DUE.
  
 4) ONE SET OF THE PLANS IS MISSING (4) PAGES. SUBMIT
 PLAN SHEETS T-1, D-1, P-1 AND E-1. 107.1 GENERAL.
 SUBMITTAL DOCUMENTS CONSISTING OF CONSTRUCTION
 DOCUMENTS, STATEMENT OF SPECIAL INSPECTIONS,
 GEOTECHNICAL REPORT AND OTHER DATA SHALL BE SUBMITTED
 IN TWO OR MORE SETS WITH EACH PERMIT APPLICATION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2016-12-16 Cont ID  
Sent By rmcdouga Date 2016-12-16 Time 18:30 Rev Time 0.00
Received By rmcdouga Date 2016-12-16 Time 17:36 Sent To  
Notes
2016-12-16 18:25:35PLAN
 REVIEW COMMENTS
  
 5TH REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) AS WE DISCUSSED PREVIOUSLY, YOU HAVE INDICATED THAT
 YOU ARE NOT ABLE TO INSTALL THE REQUIRED R-30 CEILING
 INSULATION. THEREFORE, YOU CAN NOT USE THE PRESCRIPTIVE
 METHOD TO SHOW COMPLIANCE WITH THE FBC ENERGY
 CONSERVATION. YOU SUBMITTED MANUAL J CALCULATIONS WHICH
 ARE USED TO SIZE THE HEATING AND COOLING EQUIPMENT. YOU
 WERE REQUESTED TO SUBMIT TWO SETS OF ENERGY COMPLIANCE
 FORMS TO SHOW THAT THE BUILDING ENVELOPE MEETS THE FBC
 ENERGY CONSERVATION REQUIREMENTS. SUBMIT TWO SETS OF
 THE DOCUMENTS REQUIRED BY FBC ENERGY CONSERVATION
 SECTION R101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE)
 DEMONSTRATING THAT CODE COMPLIANCE HAS BEEN ACHIEVED
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL FOR
 COMPLIANCE BY SECTION R405.
  
 2) SPECIFY THE SYSTEM TYPE, FASTENING OPTION AND DESIGN
 PRESSURE FOR THE GAF BUR ROOFING ASSEMBLY (NOA NO.
 13-1022.15). SUBMIT TWO SETS OF SIGNED AND SEALED RAS
 117 CALCULATIONS FOR ENHANCED FASTENING AS REQUIRED BY
 LIMITATION NUMBER 7 ON PAGE 16 OF THE NOA. THIS COMMENT
 HAS NOT BEEN ADDRESSED. ( IF YOU ELECT TO DO SO, THIS
 CAN BE SUBMITTED FOR REVIEW AT A LATER DATE. HOWEVER,
 IT WILL HAVE TO BE REVIEWED AND APPROVED BEFORE THE
 ROOFING IS INSTALLED. )
  
 3) THE PLANS WILL NEED TO BE REVIEWED BY PALM BEACH
 COUNTY TO DETERMINE IF ANY IMPACT FEES ARE DUE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2016-12-13 Cont ID  
Sent By rmcdouga Date 2016-12-13 Time 19:09 Rev Time 0.00
Received By rmcdouga Date 2016-12-13 Time 17:19 Sent To  
Notes
2016-12-13 19:15:01PLAN
 REVIEW COMMENTS
  
 4TH REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 THE COMMENTS FROM THE PREVIOUS REVIEW REGARDING THE
 WIND PRESSURES AND THE ENERGY CALCULATIONS WERE NOT
 CORRECTED TO BE CODE COMPLIANT. THE BUILDING OFFICIAL
 AND MYSELF CALLED THE OWNER AND THE ARCHITECT AT 6:30
 PM TO GO OVER THE DEFICIENCIES IN AN ATTEMPT TO HAVE
 THEM RESOLVED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-11-21 Cont ID  
Sent By rmcdouga Date 2016-11-21 Time 19:02 Rev Time 0.00
Received By rmcdouga Date 2016-11-18 Time 17:14 Sent To  
Notes
2016-11-21 18:53:35PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT ENERGY COMPLIANCE FORMS TO SHOW THAT THE NEW
 ADDITION MEETS THE FBC ENERGY CONSERVATION
 REQUIREMENTS. FBC ENERGY CONSERVATION R402.1 THE ENERGY
 FORM R402-2014 THAT WAS SUBMITTED CONTAINS NUMEROUS
 ERRORS AND OMISSIONS. THE OWNER'S NAME, BUILDER AND
 PERMITTING OFFICE (WEST PALM BEACH) ARE NOT LISTED AT
 THE TOP OF THE FORM. THE OWNER/AGENT SIGNATURE AND DATE
 IS MISSING. ON PAGE TWO FOR THE FLOORS THE R-VALUE IS
 SPECIFIED AS R-13. ON PAGE 1 FOR SLAB ON GRADE THE
 R-VALUE SHOULD BE NR RATHER THAN NA. THE DUCTWORK IS
 SPECIFIED AS R-16 ON PAGE 2 AND R-10 ON PAGE 1. THE
 CEILING INSULATION IS SPECIFIED AS R-30, WHICH REQUIRES
 MORE SPACE THAN THE 7-1/4 INCHES THAT THE 2 X 8 ROOF
 JOISTS PROVIDE. SOME OF THE INSULATION R-VALUES
 SPECIFIED ON THE PLANS DO NOT MATCH WHAT IS LISTED ON
 THE FORM.
  
 2) THE COMPONENT AND CLADDING PRESSURES IN THE TABLE ON
 SHEET S-2 ARE INCORRECT. THIS STRUCTURE HAS A FLAT ROOF
 AND A 14' ROOF HEIGHT PER THE PLANS. THE WIND SPEED IS
 170MPH VULT, 132MPH VASD. THE EXPOSURE CATEGORY IS C.
 FBC-R301.2.1 FOR EXAMPLE: THE WORST CASE FOR A 10SQFT
 AREA IN WALL ZONE 5 IS +37.9, -50.7 PSF IN EXPOSURE C,
 132MPH VASD WITH A 15' MEAN ROOF HEIGHT. (PREVIOUS
 COMMENT) PLEASE HAVE A FLORIDA LICENSED ENGINEER REVIEW
 THE COMPONENT AND CLADDING PRESSURES AND MAKE
 CORRECTIONS TO THE PLANS.
  
 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. (PREVIOUS COMMENT) THE PRODUCT
 APPROVALS ARE REQUIRED TO BE APPROVED IN WRITING BY THE
 ARCHITECT.
  
 4) SPECIFY THE SYSTEM TYPE, FASTENING OPTION AND DESIGN
 PRESSURE FOR THE GAF BUR ROOFING ASSEMBLY (NOA NO.
 13-1022.15). SUBMIT TWO SETS OF SIGNED AND SEALED RAS
 117 CALCULATIONS FOR ENHANCED FASTENING AS REQUIRED BY
 LIMITATION NUMBER 7 ON PAGE 16 OF THE NOA.
  
 5) THE MASTER BEDROOM IS MISLABELED AS THE MASTER
 BATHROOM ON A-1. FBC 107.2.1
  
 6) PROVIDE THE FLORIDA PRODUCT APPROVAL FL NUMBER FOR
 THE EXTERIOR DOOR THAT WILL BE USED. FBC 107.3.4
 (PREVIOUS COMMENT) THERE IS NO FL NUMBER ON THE DOOR
 PRODUCT APPROVALS.
  
 7) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-09-30 Cont ID  
Sent By rmcdouga Date 2016-09-30 Time 14:34 Rev Time 0.00
Received By rmcdouga Date 2016-09-29 Time 07:01 Sent To  
Notes
2016-09-29 17:24:09PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT ENERGY COMPLIANCE FORMS TO SHOW THAT THE NEW
 ADDITION MEETS THE FBC ENERGY CONSERVATION
 REQUIREMENTS. FBC ENERGY CONSERVATION R402.1
  
 2) SPECIFY HOW THE 3 MEMBER 2 X 8 BEAM WILL BE ANCHORED
 TO THE BLOCK WALL AND THE WOOD FRAME WALL AT EACH END.
 FBC 107.2.1 & R301.1
  
 3) REVISE THE ROOF FRAMING PLAN TO SHOW THE 12"
 OVERHANG FRAMING FOR ALL SIDES OF THE STRUCTURE. FBC
 107.2.1 & R301.1
  
 4) SHOW THE LOCATIONS OF THE VARIOUS ROOF CONNECTORS,
 HANGERS AND ANCHORS ON THE ROOF FRAMING PLAN. FOR
 CLARITY PROVIDE A ROOF FRAMING PLAN WITH CONNECTORS
 SPECIFIED AT PROPER LOCATIONS ON THE STRUCTURAL
 DRAWINGS. FBC 107.2.1 & 107.2.1.3
  
 5) THE ANCHOR SCHEDULE ON S-1, SPECIFIES AN A1 HANGER
 FOR A 6 X 12 TIMBER BEAM. THERE IS NO 6 X 12 BEAM
 SPECIFIED ON THE PLANS. PLEASE CLARIFY. FBC 107.2.1
  
 6) THERE IS AN A6 ANCHOR IN THE ANCHOR SCHEDULE AND
 THERE IS NO A6 TAG ON THE PLANS. IT APPEARS THAT THIS
 WAS MEANT TO BE THE A2 ANCHOR. PLEASE CLARIFY. FBC
 107.2.1
  
 7) THE 8D ROOF SHEATHING FASTENERS ARE REQUIRED TO BE
 RING-SHANK PER FBC-R803.2.3.1
  
 8) THE COMPONENT AND CLADDING PRESSURES IN THE TABLE ON
 SHEET S-2 ARE INCORRECT. THIS STRUCTURE HAS A FLAT ROOF
 AND A 14' ROOF HEIGHT PER THE PLANS. THE WIND SPEED IS
 170MPH VULT, 132MPH VASD. THE EXPOSURE CATEGORY IS C.
 FBC-R301.2.1 FOR EXAMPLE: THE WORST CASE FOR A 10SQFT
 AREA IN WALL ZONE 5 IS +37.9, -50.7 PSF IN EXPOSURE C,
 132MPH VASD WITH A 15' MEAN ROOF HEIGHT.
  
 9) ON SHEET S-2 THE BASIC WIND SPEED IS SPECIFIED AS
 180 MPH AND THE WIND SPEED FOR WEST PALM BEACH IS 170
 MPH VULT. FBC R301.2.1
  
 10) SPECIFY THE REQUIRED COMPONENT AND CLADDING DESIGN
 PRESSURES FOR THE NEW EXTERIOR DOOR ON THE PLANS.
 FBC-R301.2.1
  
 11) THE WRONG EDITIONS OF ACI 318 AND 530 ARE SPECIFIED
 ON S-2. THE FBC REFERENCES ACI 318 - 11 AND ACI 530 -
 11. FBC - R CHAPTER 46.
  
 12) THERE IS A 12" X 16" THICKENED EDGE MONOLITHIC
 FOOTING SHOWN ON S-1. THIS DOES NOT COMPLY WITH FBCR
 403.1.4 WHICH REQUIRES THE FOOTINGS TO BE AT LEAST 12
 INCHES BELOW GRADE AND FBCR 404.1.6 WHICH REQUIRES THE
 CONCRETE FOUNDATION TO EXTEND ABOVE THE FINISHED GRADE
 ADJACENT TO THE FOUNDATION AT ALL POINTS A MINIMUM OF 4
 INCHES (102 MM) WHERE MASONRY VENEER IS USED AND A
 MINIMUM OF 6 INCHES (152 MM) ELSEWHERE. (PREVIOUS
 COMMENT)
  
 13) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. (PREVIOUS COMMENT)
  
 14) PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH FL OR
 NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS AND
 MAXIMUM DESIGN PRESSURES FOR THE ROOFING MATERIALS. FBC
 107.3.4 (PREVIOUS COMMENT)
  
 15) PROVIDE THE FLORIDA PRODUCT APPROVAL FL NUMBER FOR
 THE EXTERIOR DOOR THAT WILL BE USED. FBC 107.3.4
 (PREVIOUS COMMENT)
  
 16) SHEET A-1 IN ONE OF THE PLAN SETS DOES NOT HAVE THE
 ARCHITECT'S EMBOSSED SEAL. FBC 107.1 & FLORIDA STATUTES
 CHAPTER 481
  
 17) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-07-29 Cont ID  
Sent By rmcdouga Date 2016-07-29 Time 16:59 Rev Time 0.00
Received By rmcdouga Date 2016-07-28 Time 18:49 Sent To  
Notes
2016-07-29 11:26:04PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS SPECIFY THIS PROJECT AS AN R-1 OCCUPANCY.
 PLEASE CLARIFY THE OCCUPANCY TYPE. IF THIS IS A ONE OR
 TWO FAMILY DWELLING THE OCCUPANCY TYPE IS R-3.
 310.3 RESIDENTIAL GROUP R-1. RESIDENTIAL OCCUPANCIES
 CONTAINING SLEEPING UNITS WHERE THE OCCUPANTS ARE
 PRIMARILY TRANSIENT IN NATURE, INCLUDING:
 BOARDING HOUSES (TRANSIENT) WITH MORE THAN 10 OCCUPANTS
 CONGREGATE LIVING FACILITIES (TRANSIENT) WITH MORE THAN
 10 OCCUPANTS
 HOTELS (TRANSIENT)
 MOTELS (TRANSIENT)
  
 2) THE PLANS SPECIFY THE CONSTRUCTION AS TYPE III. TYPE
 III CONSTRUCTION REQUIRES 2 HOUR FIRE RATED WALLS AMONG
 OTHER THINGS THAT THIS STRUCTURE DOES NOT HAVE. THIS
 APPEARS TO BE TYPE V-B CONSTRUCTION. PLEASE CLARIFY.
  
 3) LABEL THE INTENDED USE OF THE NEW AREA ADJACENT TO
 THE EXISTING UTILITY ROOM ON THE PLANS. FBC 107.2.1
  
 4) INDICATE THE USE OR ROOM TYPE OF THE LARGE UNLABELED
 AREA ADJACENT TO BEDROOM #1 ON THE PLANS. FBC 107.2.1
  
 5) SUBMIT ENERGY COMPLIANCE FORMS TO SHOW THAT THE NEW
 ADDITION MEETS THE FBC ENERGY CONSERVATION
 REQUIREMENTS.
  
 6) SPECIFY THE WALL AND CEILING INSULATION R-VALUES ON
 THE PLANS.
  
 7) THE ROOF FRAMING PLAN ON SHEET A-1 HAS 2 X 8 WOOD
 TRUSS. DID YOU INTEND THIS TO BE A WOOD JOIST OR A
 TRUSS? IF THIS IS A SINGLE ASSEMBLY FLAT ROOF SYSTEM,
 THERE ARE NO CEILING JOISTS. THERE WOULD BE ONLY ROOF
 RAFTERS WITH THE CEILING ATTACHED TO THE BOTTOM OF
 THEM. PLEASE CLARIFY ON THE PLANS.
  
 8) THE ROOF FRAMING PLAN ON SHEET A-1 SPECIFIES A (3) 2
 X 10 WOOD BEAM. THE TWO DETAILS ON SHEET S-1 SHOW A (3)
 2 X 8 BEAM. PLEASE CORRECT. FBC 107.2.1
  
 9) SECTION A-A ON SHEET S-1 SHOWS THE BLOCK WALLS
 EXTENDING TO THE UNDERSIDE OF THE ROOF SHEATHING. ONE
 OF THE DETAILS ON S-1 SHOWS THE (3) 2 X 8 BEAM ON TOP
 OF THE BLOCK WALL. PLEASE CORRECT THE INCONSISTENCIES.
  
 10) ONE OF THE DETAILS ON S-1 SHOWS THE RAFTERS BUTTING
 INTO THE (3) 2 X 8 BEAM. SPECIFY THE HANGERS THAT WILL
 BE USED AND CLARIFY THE WOOD PLATE AND ANCHOR BOLT THAT
 IS SHOWN ON TOP OF THE BEAM.
  
 11) SPECIFY HOW THE 3 MEMBER 2 X BEAM WILL BE ANCHORED
 TO THE BLOCK WALLS AT EACH END.
  
 12) SHOW THE LOCATIONS OF THE VARIOUS ROOF CONNECTORS,
 HANGERS AND ANCHORS ON THE ROOF FRAMING PLAN. FBC
 107.2.1
  
 13) SPECIFY THE ROOF SHEATHING FASTENERS AND SPACING ON
 THE PLANS.
  
 14) SPECIFY THE REQUIRED DESIGN PRESSURES FOR THE ROOF
 COVERING FOR ROOF ZONES 1, 2 AND 3 ON THE PLANS.
  
 15) SPECIFY THE REQUIRED DESIGN PRESSURES FOR THE NEW
 EXTERIOR DOOR ON THE PLANS.
  
 16) THE WINDOW SCHEDULE ON A-2 HAS HORIZONTAL SLIDING
 WINDOWS LISTED AND THE PRODUCT APPROVALS ARE FOR SINGLE
 HUNG WINDOWS. PLEASE CORRECT.
  
 17) THERE IS A 12" X 16" THICKENED EDGE MONOLITHIC
 FOOTING SHOWN ON S-1. THIS DOES NOT COMPLY WITH FBCR
 403.1.4 WHICH REQUIRES THE FOOTINGS TO BE AT LEAST 12
 INCHES BELOW GRADE AND FBCR 404.1.6 WHICH REQUIRES THE
 CONCRETE FOUNDATION TO EXTEND ABOVE THE FINISHED GRADE
 ADJACENT TO THE FOUNDATION AT ALL POINTS A MINIMUM OF 4
 INCHES (102 MM) WHERE MASONRY VENEER IS USED AND A
 MINIMUM OF 6 INCHES (152 MM) ELSEWHERE.
  
 18) FBCR 318.5 REQUIRES GUTTERS WITH DOWNSPOUTS ON ALL
 BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF. SPECIFY THE ROOF OVERHANG ON
 THE PLANS.
  
 19) SHOW COMPLIANCE WITH FBCR 314.3.1 FOR REQUIRED
 SMOKE ALARMS.
  
 20) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD.
  
 21) PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH FL OR
 NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS AND
 MAXIMUM DESIGN PRESSURES FOR THE ROOFING MATERIALS. FBC
 107.3.4
  
 22) PROVIDE THE FLORIDA PRODUCT APPROVAL FL NUMBER FOR
 THE EXTERIOR DOOR THAT WILL BE USED. FBC 107.3.4
  
 23) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-02-15 Cont ID  
Sent By rmcdouga Date 2017-02-15 Time 16:03 Rev Time 0.00
Received By rmcdouga Date 2017-02-15 Time 16:03 Sent To  
Notes
2017-02-15 16:06:41APPROVED WITH EXCEPTIONS
 PROVISO
 THE LOAD CALCULATIONS DON'T MATCH THE PANEL SCHEDULE,
 MISSING DRYER NAMEPLATE APPLIANCE LOAD. FBC-R-E36.2.2
 (MINIMUM SERVICE LOAD CALCULATIONS)

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-09-26 Cont ID  
Sent By mvaldes Date 2016-09-26 Time 13:16 Rev Time 0.00
Received By mvaldes Date 2016-09-26 Time 10:20 Sent To  
Notes
2016-09-26 13:08:31REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 PASSED WITH THE FOLLOWING PROVISO
  
 1] LOAD CALCULATIONS DON'T MATCH THE PANEL SCHEDULE,
 MISSING DRYER NAMEPLATE APPLIANCE LOAD. FBC-R_E3602.2 (
 MINIMUM SERVICE LOAD CALCS )

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-06 Cont ID  
Sent By mvaldes Date 2016-06-06 Time 18:06 Rev Time 0.00
Received By mvaldes Date 2016-06-06 Time 17:57 Sent To  
Notes
2016-06-06 18:09:05JOB PERMIT NUMBER: 16030072
 JOB ADDRESS: 618 49TH STREET
 WEST PALM BEACH FLORIDA 33407
 DATE: JUNE 6 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - THE SCOPE OF WORK DEFINES THIS AS AN ADDITION TO THE
 EXISTING DWELLING UNIT THEREFORE ELECTRICAL DRAWINGS
 MUST PROVIDE THE MINIMUM PLAN CRITERIA. FBC 107
 - SMOKE ALARMS AS PER RESIDENTIAL CODE SECTIONS 314 &
 315.
 - RECEPTACLE OUTLET SPACING AND LIGHTING OUTLET
 REQUIREMENTS IN ACCORDANCE WITH NEC 210.52 & 210.70
 - NEC 406.11 TAMPER-RESISTANT RECEPTACLES IN DWELLING
 UNITS. IN ALL AREAS SPECIFIED IN 210.52, ALL 125-VOLT,
 15 AND 20 AMPERE RECEPTACLES SHALL BE LISTED TAMPER
 RESISTANT RECEPTACLES.
 - NEC 210.12B - OUTLETS TO BE AFCI PROTECTED.
 - ELECTRIC SERVICE RISER WITH WIRE SIZES, CONDUIT
 DETAIL AND GROUNDING DETAIL. COMPLETE LOAD
 CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN.
 - AN ELECTRICAL SUB-PERMIT SHALL BE ISSUED BY THE
 ELECTRICAL CONTRACTOR PERFORMING THE WORK.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2017-02-15 Cont ID  
Sent By rmcdouga Date 2017-02-15 Time 15:26 Rev Time 0.00
Received By rmcdouga Date 2017-02-06 Time 14:11 Sent To  
Notes
2017-02-07 14:12:02RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2017-02-03 Cont ID  
Sent By rmcdouga Date 2017-02-03 Time 10:36 Rev Time 0.00
Received By rmcdouga Date 2017-01-25 Time 11:28 Sent To  
Notes
2017-01-26 11:28:32RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2016-12-16 Cont ID  
Sent By rmcdouga Date 2016-12-16 Time 18:30 Rev Time 0.00
Received By rmcdouga Date 2016-12-15 Time 14:04 Sent To  
Notes
2016-12-16 14:05:11TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-12-13 Cont ID  
Sent By rmcdouga Date 2016-12-13 Time 19:09 Rev Time 0.00
Received By rmcdouga Date 2016-12-13 Time 16:00 Sent To  
Notes
2016-12-13 16:01:23R.MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-11-22 Cont ID  
Sent By rmcdouga Date 2016-11-22 Time 06:46 Rev Time 0.00
Received By rmcdouga Date 2016-11-08 Time 14:38 Sent To  
Notes
2016-11-09 14:38:47RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-30 Cont ID  
Sent By rmcdouga Date 2016-09-30 Time 14:34 Rev Time 0.00
Received By rmcdouga Date 2016-09-07 Time 12:43 Sent To  
Notes
2016-09-07 12:43:17R04

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-29 Cont ID  
Sent By rmcdouga Date 2016-07-29 Time 16:59 Rev Time 0.00
Received By rmcdouga Date 2016-06-01 Time 09:20 Sent To  
Notes
2016-06-02 09:20:59R06
2016-03-03 10:54:223/2/16
  
 1ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 APPLICANT INFORMED TO SUBMIT PLANS. THE LACK OF PLANS
 TO DESCRIBE THE PROPOSED WORK CONSTITUTES AN INCOMPLETE
 APPLICATION.
  
 553.792?BUILDING PERMIT APPLICATION TO LOCAL
 GOVERNMENT.?
 (1)?WITHIN 10 DAYS OF AN APPLICANT SUBMITTING AN
 APPLICATION TO THE LOCAL GOVERNMENT, THE LOCAL
 GOVERNMENT SHALL ADVISE THE APPLICANT WHAT INFORMATION,
 IF ANY, IS NEEDED TO DEEM THE APPLICATION PROPERLY
 COMPLETED IN COMPLIANCE WITH THE FILING REQUIREMENTS
 PUBLISHED BY THE LOCAL GOVERNMENT.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2017-02-16 Cont ID  
Sent By rmcdouga Date 2017-02-16 Time 14:22 Rev Time 0.00
Received By rmcdouga Date 2017-02-16 Time 14:22 Sent To  
Notes
2017-02-16 14:25:22MU-2017-4261, NO FEES WERE DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2017-02-02 Cont ID  
Sent By rmcdouga Date 2017-02-02 Time 16:47 Rev Time 0.00
Received By rmcdouga Date 2017-02-02 Time 16:47 Sent To  
Notes
2017-02-02 16:49:40BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-09-29 Cont ID  
Sent By rmcdouga Date 2016-09-29 Time 11:20 Rev Time 0.00
Received By rmcdouga Date 2016-09-29 Time 11:20 Sent To  
Notes
2016-09-29 11:20:28BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-07-29 Cont ID  
Sent By rmcdouga Date 2016-07-29 Time 17:39 Rev Time 0.00
Received By rmcdouga Date 2016-07-29 Time 17:39 Sent To  
Notes
2016-07-29 17:40:35BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-09-29 Cont ID  
Sent By rmcdouga Date 2016-09-29 Time 16:12 Rev Time 0.00
Received By rmcdouga Date 2016-09-29 Time 07:01 Sent To  
Notes
2016-09-29 16:15:07PLANS SPECIFY A NEW BATH EXHAUST AND DRYER VENT. A
 MECHANICAL SUB-PERMIT IS REQUIRED.
2016-09-28 14:53:19MECH. ADDED ON P-1

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2016-07-28 Cont ID  
Sent By rmcdouga Date 2016-07-28 Time 18:54 Rev Time 0.00
Received By rmcdouga Date 2016-07-28 Time 18:54 Sent To  
Notes
2016-07-28 18:55:59NO MECHANICAL WORK SHOWN ON PLANS. SEPARATE PERMIT,
 APPLICATION AND REVIEW WILL BE REQUIRED.

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-02-15 Cont ID  
Sent By rmcdouga Date 2017-02-15 Time 16:03 Rev Time 0.00
Received By rmcdouga Date 2017-02-15 Time 16:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-09-28 Cont ID  
Sent By gjohnson Date 2016-09-28 Time 14:52 Rev Time 0.00
Received By gjohnson Date 2016-09-28 Time 13:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2016-06-20 Time   Rev Time 0.00
Received By gearl Date 2016-06-20 Time 06:50 Sent To  
Notes
2016-06-20 06:51:53NEED DRAWING OF DWV PIPING
 NEED DRAWING OOF WATER PIPING
 NEED LOCATION AND TYPE OF WATER HEATER

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2016-12-16 Cont ID  
Sent By rmcdouga Date 2016-12-16 Time 18:31 Rev Time 0.00
Received By rmcdouga Date 2016-12-16 Time 18:31 Sent To  
Notes
2016-12-16 18:34:03ROOFING
 FL16709-R3, PAGES 13-14, SYSTEM W-5

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2016-09-16 Time   Rev Time 0.00
Received By njwira Date 2016-09-16 Time 14:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-06-10 Cont ID  
Sent By nwier Date 2016-06-10 Time 16:58 Rev Time 0.00
Received By njwira Date 2016-06-10 Time 16:58 Sent To M
Notes
***NONE***