Plan Review Details - Permit 16030024
Plan Review Stops For Permit 16030024
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2016-03-04 Cont ID  
Sent By tklarge Date 2016-03-04 Time 05:40 Rev Time 0.00
Received By tklarge Date 2016-03-04 Time 05:34 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-03-02 Cont ID  
Sent By tklarge Date 2016-03-02 Time 06:10 Rev Time 0.00
Received By tklarge Date 2016-03-02 Time 05:32 Sent To  
Notes
2016-03-02 06:07:361) THE GAS DRAWING REFERS TO A 10 PSI PRESSURE ON THE
 LINE FROM THE TANK. THERE IS NO TABLE IN THE 2014 FUEL
 GAS CODE FOR A 10 PSI SYSTEM. SUBMIT A COPY OF THE
 SIZING TABLE BEING USED FOR THE 10 PSI PORTION OF THIS
 SYSTEM.
 2) THE EXISTING BTU LOAD NOTED ON THE PLAN DOES NOT
 INCLUDE THE POOL HEATER. CLARIFY.
 3) THE NEW BTU LOAD LISTED REFERS TO A RANGE BUT THE
 DRAWING ALSO SHOWS A NEW GRILL. CLARIFY.
 4) THE DRAWING REFERS TO SIZING TABLE 402.4 (32). THIS
 TABLE IS FOR CSST MATERIAL BUT THERE IS NO CSST SHOWN
 ON THE DRAWING. CLARIFY.
 5) IS THE GRILL LOCATED UNDER A ROOF, AS ON A ROOFED
 OVER PATIO? IF SO, A HOOD MAY BE REQUIRED.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-04 Cont ID  
Sent By tklarge Date 2016-03-04 Time 05:40 Rev Time 0.00
Received By tklarge Date 2016-03-03 Time 12:39 Sent To  
Notes
2016-03-03 12:39:48RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-02 Cont ID  
Sent By tklarge Date 2016-03-02 Time 06:10 Rev Time 0.00
Received By tklarge Date 2016-03-01 Time 13:03 Sent To  
Notes
2016-03-01 13:03:25PLUMB -$5000