2016-03-09 13:10:00 | REVIEW 2014 5TH FBC ED. NEC 2011 |
| MARIO VALDES |
| ELECTRICAL PLAN EXAMINER |
| 516-805-6713 |
| [email protected] |
| |
| |
| - FOR A FULL HOUSE REWIRING REMODELING PROJECT FULL |
| SIZE DRAWINGS SHALL BE SUBMITTED SIGN AND SEALED. |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE |
| DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| ELECTRONIC MEDIA DOCUMENTS SHALL BE |
| SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL. |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| DESIGN. (SEE ALSO SECTION 107.3.5). |
| FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| RECORDS MANAGEMENT. |
| |
| - KEEP IN MIND THE FOLLOWING CODE SECTIONS THAT WILL |
| APPLY. |
| NEC 210.12B - OUTLETS TO BE AFCI PROTECTED. |
| NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES. |
| FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING |
| INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC |
| RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| CONDITIONED & UNCONDITIONED SPACES. |
| SMOKE/CARBON ALARMS REQUIRED PER RESIDENTIAL CODE |
| SECTIONS 314 & 315. |
| NEC 404.2 C NUETRAL ( GROUNDED CONDUCTOR ) SHALL BE |
| PROVIDED AT SWITCH LOCATION. |
| NEC 250.94 PROVIDE INTERSYSTEM BONDING. {NOTE} I |
| NOTICED THE GROUNDING ELECTRODE CONDUCTOR IS UNDERSIZED |
| CHECK TABLE NEC 250.66 |