Plan Review Details - Permit 16021097
Plan Review Stops For Permit 16021097
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-10 Cont ID  
Sent By mvaldes Date 2016-03-10 Time 11:37 Rev Time 0.00
Received By mvaldes Date 2016-03-10 Time 11:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-09 Cont ID  
Sent By mvaldes Date 2016-03-09 Time 13:10 Rev Time 0.00
Received By mvaldes Date 2016-03-09 Time 13:10 Sent To  
Notes
2016-03-09 13:10:00REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 - FOR A FULL HOUSE REWIRING REMODELING PROJECT FULL
 SIZE DRAWINGS SHALL BE SUBMITTED SIGN AND SEALED.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
 FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 - KEEP IN MIND THE FOLLOWING CODE SECTIONS THAT WILL
 APPLY.
 NEC 210.12B - OUTLETS TO BE AFCI PROTECTED.
 NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES.
 FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES.
 SMOKE/CARBON ALARMS REQUIRED PER RESIDENTIAL CODE
 SECTIONS 314 & 315.
 NEC 404.2 C NUETRAL ( GROUNDED CONDUCTOR ) SHALL BE
 PROVIDED AT SWITCH LOCATION.
 NEC 250.94 PROVIDE INTERSYSTEM BONDING. {NOTE} I
 NOTICED THE GROUNDING ELECTRODE CONDUCTOR IS UNDERSIZED
 CHECK TABLE NEC 250.66

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-10 Cont ID  
Sent By mvaldes Date 2016-03-10 Time 11:38 Rev Time 0.00
Received By mvaldes Date 2016-03-10 Time 11:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-09 Cont ID  
Sent By mvaldes Date 2016-03-09 Time 13:10 Rev Time 0.00
Received By mvaldes Date 2016-02-29 Time 10:08 Sent To E
Notes
***NONE***