Plan Review Details - Permit 16020992
Plan Review Stops For Permit 16020992
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-07-13 Cont ID  
Sent By cthroop Date 2016-07-13 Time 12:24 Rev Time 0.00
Received By cthroop Date 2016-07-13 Time 12:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-06-13 Cont ID  
Sent By gearl Date 2016-06-13 Time   Rev Time 0.00
Received By gearl Date 2016-06-13 Time 14:12 Sent To  
Notes
2016-06-13 14:29:57MAREDK BUILDING BY MISTAKE GEORGE EARL

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-22 Cont ID  
Sent By cthroop Date 2016-03-22 Time 10:31 Rev Time 0.00
Received By cthroop Date 2016-03-22 Time 08:38 Sent To  
Notes
2016-03-22 10:44:111ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 1. PROVIDE SITE PLAN.
 2. PROVIDE ENERGY CALC'S.
 3. PROVIDE DETAIL FOR NEW MASONRY OPENINGS IN EXISTING
 CMU WALLS.
 4. PROVIDE SHORING PLAN FOR REMOVAL OF EXISTING CMU
 LOAD BEARING WALLS PER NOTE 2, PG. S-1.
 5. SPECIFY SPACING OF HORIZ. JOINT RE-INFORCING @ 8"
 CMU WALLS PER DETAIL 5, PG. S-1.
 6. IDENTIFY LENGTH OF #4 DOWELS IN NOTE # 2, FOUNDATION
 PLAN, PG. S-1.
 7. IMPACT FEES.
 8. PROVIDE FLOOR PLAN. IDENTIFY INTENDED USE OF SPACE.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 FBC 107.3.5.3 ? PROVIDE A SITE PLAN TO DEMONSTRATE
 SETBACKS AND BUILDING SEPARATION.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURN STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-06-13 Cont ID  
Sent By mvaldes Date 2016-06-13 Time 18:40 Rev Time 0.00
Received By mvaldes Date 2016-06-13 Time 18:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-03 Cont ID  
Sent By mvaldes Date 2016-03-03 Time 09:22 Rev Time 0.00
Received By mvaldes Date 2016-03-03 Time 09:22 Sent To  
Notes
2016-03-03 09:34:171ST REVIEW 2014 5TH FBC ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 -PLEASE PROVIDE A ELECTRICAL FLOOR PLAN SHOWING NEW
 WORK AND EXISTING LOCATION OF ELECTRICAL SYSTEM. WBA
 107
  
 FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN.
  
 SMOKE/CARBON ALARMS REQUIRED PER RESIDENTIAL CODE
 SECTIONS 314 & 315
  
 OUTLETS TO BE AFCI PROTECTED PER NEC 210.12 B AND
 RECEPTACLES MUST BE TAMPER RESISTANT RATED ACCORDING TO
 NEC 406.11
  
 PROVIDE GFCI PROTECTION IN THOSE AREAS COVERED IN NEC
 210.8 A
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-07-13 Cont ID  
Sent By cthroop Date 2016-07-13 Time 12:23 Rev Time 0.00
Received By cthroop Date 2016-07-12 Time 15:38 Sent To  
Notes
2016-07-12 15:38:42IMPACT FEES ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-22 Cont ID  
Sent By cthroop Date 2016-06-22 Time 16:15 Rev Time 0.00
Received By cthroop Date 2016-05-31 Time 09:40 Sent To  
Notes
2016-06-01 09:41:10R31

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-22 Cont ID  
Sent By cthroop Date 2016-03-22 Time 10:52 Rev Time 0.00
Received By cthroop Date 2016-02-25 Time 11:17 Sent To  
Notes
2016-02-26 11:17:20R26

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2016-07-13 Cont ID  
Sent By cthroop Date 2016-07-13 Time 12:23 Rev Time 0.00
Received By cthroop Date 2016-07-13 Time 12:23 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-03-22 Cont ID  
Sent By cthroop Date 2016-03-22 Time 10:28 Rev Time 0.00
Received By cthroop Date 2016-03-22 Time 10:28 Sent To  
Notes
2016-03-22 10:31:141ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURN STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2016-06-22 Cont ID  
Sent By jvalido Date 2016-06-22 Time 15:02 Rev Time 0.00
Received By jvalido Date 2016-06-22 Time 14:03 Sent To R
Notes
2016-06-22 15:39:07THIS PERMIT WAS ISSUED WITHOUT ANY MECHANICAL A/C
 REQUIREMENTS. IF AN INSPECTOR SEES ANY MECHANICAL A/C
 WORK DONE PLEASE NOTIFY THE BUILDING OFFICIAL, PLACE A
 STOP WORK ORDER AND APPLY A FOUR TIMES THE PERMIT FEE.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-03-22 Cont ID  
Sent By skennedy Date 2016-03-22 Time 10:50 Rev Time 0.00
Received By skennedy Date 2016-03-22 Time 10:47 Sent To  
Notes
2016-03-22 10:59:411ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 FBC- 107.3.5.3 ? PROVIDE A MECHANICAL PLAN TO SHOW
 SUPPLY DUCTS PER FBC-R M16 & BATH EXHAUST PER FBC-R
 M15.
  
 PROVIDE AN ENERGY SUBMITTAL.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 PROVIDE AN EQUIPMENT SIZING CALCULATION IF APPLICABLE.
  
 R403.6.1 EQUIPMENT SIZING.
 HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN
 ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR
 OTHER APPROVED HEATING AND COOLING CALCULATION
 METHODOLOGIES, BASED ON BUILDING LOADS FOR THE
 DIRECTIONAL ORIENTATION OF THE BUILDING. THE
 MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR
 UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH
 THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN
 CONDITIONS DESCRIBED IN SECTION R302.1. THIS CODE DOES
 NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR
 FUTURE EXPANSION OR OTHER FACTORS WHICH AFFECT
 EQUIPMENT SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT
 INCLUDE LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL
 VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM
 EXHAUST SYSTEMS.
  
 R403.6.1.1 COOLING EQUIPMENT CAPACITY.
 COOLING ONLY EQUIPMENT SHALL BE SELECTED SO THAT ITS
 TOTAL CAPACITY IS NOT LESS THAN THE CALCULATED TOTAL
 LOAD, BUT NOT MORE THAN 1.15 TIMES GREATER THAN THE
 TOTAL LOAD CALCULATED ACCORDING TO THE PROCEDURE
 SELECTED IN SECTION 403.6, OR THE CLOSEST AVAILABLE
 SIZE PROVIDED BY THE MANUFACTURER?S PRODUCT LINES. THE
 CORRESPONDING LATENT CAPACITY OF THE EQUIPMENT SHALL
 NOT BE LESS THAN THE CALCULATED LATENT LOAD.
  
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-06-13 Cont ID  
Sent By gearl Date 2016-06-13 Time 14:27 Rev Time 0.00
Received By gearl Date 2016-06-13 Time 14:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-03-11 Cont ID  
Sent By gjohnson Date 2016-03-11 Time 12:09 Rev Time 0.00
Received By gjohnson Date 2016-03-11 Time 12:07 Sent To  
Notes
2016-03-11 12:24:091ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PROVIDE PLUMBING RISER DIAGRAM WITH PIPE SIZES.
 PER WPB AMEND.TO FBC SEC 107.3.5.3(11)
 2. PROVIDE MANUFACTURE SPEC SHEETS FOR WATER HEATER.
 3. VALUATION OF ALL WORK ON MAIN PERMIT APPLICATION
 APPEARS TO BE LOW PLEASE PROVIDE A DETAILED QUANTITY
 ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 PER WPB AMEND. TO FBC SEC.109.3 BUILDING PERMIT
 VALUATIONS.
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2016-06-22 Cont ID  
Sent By cthroop Date 2016-06-22 Time 16:14 Rev Time 0.00
Received By cthroop Date 2016-06-22 Time 16:14 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-03-22 Cont ID  
Sent By cthroop Date 2016-03-22 Time 10:27 Rev Time 0.00
Received By cthroop Date 2016-03-22 Time 10:27 Sent To  
Notes
2016-03-22 10:28:441ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 PROVIDE ROOF SHEATHING FASTENER SCHEDULE PER DESIGN
 WIND LOAD CALC'S.

Review Stop Z ZONING
Rev No 2 Status P Date 2016-06-10 Cont ID  
Sent By llouie Date 2016-06-16 Time 16:40 Rev Time 0.00
Received By llouie Date 2016-06-10 Time 16:19 Sent To M
Notes
2016-06-10 16:40:46ZONING PASSED - ALL COMMENTS BELOW ADDRESSED ON
 6/16/16.
  
  
 FAILED ON 6/10/16
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) REPEAT COMMENT FROM 3/10/16: PROVIDE AN UPDATED
 SURVEY OF THE PROPERTY. A SURVEY OF THE PROPERTY IS
 NEEDED TO ENSURE THAT THE LOT DIMENSIONS AND EXISTING
 STRUCTURES ILLUSTRATED IN THE SITE PLAN ARE ACCURATE
 AND ARE NOT IN CONFLICT WITH ANY EASEMENTS.
  
 [PER HDM ARCHITECTURE, INC. RESPONSE LETTER TO ZONING'S
 COMMENTS, DATED 4/10/16, THE GENERAL CONTRACTOR WILL
 PROVIDE THE UPDATED SURVEY; HOWEVER, NO SURVEY WAS
 PROVIDED WITH THE RESUBMITTAL.]
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561) 822-1458 IF YOU HAVE QUESTIONS.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-03-10 Cont ID  
Sent By llouie Date 2016-03-10 Time   Rev Time 0.00
Received By llouie Date 2016-03-10 Time 15:48 Sent To  
Notes
2016-03-10 16:31:19** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS IN WRITING AND/OR
 ON THE PLANS WHERE APPLICABLE:
  
 1.) PROVIDE AN UPDATED SURVEY OF THE PROPERTY.
  
 2.) A SITE PLAN IS REQUIRED. THE SCOPE OF WORK INCLUDES
 THE EXPANSION OF THE EXISTING STRUCTURE. SETBACK
 DIMENSIONS, FROM THE PROPOSED BUILDING FOOTPRINT TO THE
 PROPERTY LINES REQUIRED TO DETERMINE IF THE EXPANSION
 MEETS SETBACK REQUIREMENTS OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS.
  
 3.) PROVIDE HEIGHT OF THE BUILDING TO THE TOP OF THE
 ROOF PITCH.
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561) 822-1458 IF YOU HAVE QUESTIONS.
  