Plan Review Details - Permit 16020945
Plan Review Stops For Permit 16020945
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-07-26 Cont ID  
Sent By jgomez Date 2016-07-26 Time 10:38 Rev Time 0.00
Received By jgomez Date 2016-07-26 Time 10:35 Sent To  
Notes
2016-07-26 10:40:17BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- SHEET A300: CLARIFY HOW PROVIDING R-30 CLOSED CELL
 INSULATION ON 2X6 WALLS. PROVIDE MANUFACTURER'S SPECS
 SHOWING THICKNESS TO MEET THE R-30 VALUE. PROVIDE ICC
 EVALUATION REPORT FOR THE FOAM INSULATION SHOWING
 COMPLIANCE WITH SEC. R316. NOTE: ENGINEER OF RECORD TO
 APPROVE IN WRITING THE EVALUATION REPORT PRIOR TO
 SUBMITTAL T THIS OFFICE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-06-15 Cont ID  
Sent By jgomez Date 2016-06-14 Time 17:34 Rev Time 0.00
Received By jgomez Date 2016-06-14 Time 17:20 Sent To  
Notes
2016-06-14 17:37:01RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 ORIGINAL COMMENT:
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 RESPONSE: NEED THE PALM BEACH COUNTY STAMP ON DRAWINGS.
  
 2- EXTERIOR WALL SECTION "C" ON SHEET S101:
 ORIGINAL COMMENT
 A)SPECIFY HOW ARE THE NEW 2 X 6 STUDS ATTACHED TO THE
 TOP AND TO THE BOTTOM PLATES. SEC. R601.2 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 RESPONSE: SPECIFICATIONS ON DETAIL "C" DON'T SEEM TO
 PROVIDE A CONTINUOUS LOAD PATH. NAILING TO THE WOOD
 GRAIN ON THE TOP PLATES AND TOE NAILING AT THE BOTTOM
 PLATE DON'T SEEM TO PROVIDE SUPPORT FOR UPLIFT LOADS.
 ENGINEER TO REVIEW DETAIL "C" AND PROVIDE A RESPONSE
 LETTER STATING THAT HE REVIEWED THE DETAIL AND THAT
 SPECIFIED CONNECTIONS ARE STRUCTURALLY ADEQUATE TO
 RESIST ALL LOADS. PROVIDE ENGINEER ANALYSIS SHOWING HOW
 PROVIDING A CONTINUOUS LOAD PATH TO RESIST ALL LOADS
 THE WAY IT'S SPECIFIED ON THE DETAIL. SEC. R601.2 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 ORIGINAL COMMENT:
 3- SHEET A300: CLARIFY HOW PROVIDING R-30 CLOSED CELL
 INSULATION ON 2X6 WALLS. PROVIDE MANUFACTURER'S SPECS
 SHOWING REQUIRED THICKNESS TO MEET THE R-30 VALUE. SEC.
 107.2.1 CITY AMENDMENTS.
  
 RESPONSE: PROVIDE ICC EVALUATION REPORT FOR THE "TIGER
 FOAM" INSULATION SHOWING COMPLIANCE WITH THE
 REQUIREMENTS OF SEC. R316 FOR FOAM PLASTIC AND TO
 VERIFY THE R-VALUE. IF THERE IS MORE THAN ONE TYPE OF
 FOAM, THEN CLEARLY IDENTIFY SPECIFIC FOAM TO BE USED.
 ENGINEER OF RECORD TO APPROVE IN WRITING THE EVALUATION
 REPORT PRIOR TO SUBMITTAL T THIS OFFICE.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 ORIGINAL COMMENT:
 A) SLIDING GLASS DOORS AS SHOWN ON PLANS. DRAWINGS
 SUBMITTED WITH FLORIDA PRODUCT APPROVAL FL8753-R3 ARE
 FOR SMALL MISSILE IMPACT PROTECTION. NEED DOORS WITH
 LARGE MISSILE IMPACT PROTECTION. SEC. R301.2.1.2 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 RESPONSE: NOT ADDRESSED. SAME PRODUCT APPROVAL WAS
 RE-SUBMITTED.
  
 ORIGINAL COMMENT:
 B) CASEMENT WINDOWS AS SHOWN ON PLANS. DRAWINGS
 SUBMITTED WITH FLORIDA PRODUCT APPROVAL FL9968-R4 ARE
 FOR SMALL MISSILE IMPACT PROTECTION. NEED WINDOWS WITH
 LARGE MISSILE IMPACT PROTECTION. SEC. R301.2.1.2 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 RESPONSE: NOT ADDRESSED. SAME PRODUCT APPROVAL WAS
 RE-SUBMITTED.
  
 5- ENGINEER OF RECORD TO APPROVE IN WRITING ABOVE
 PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 NEW COMMENT:
 6- RE-SUBMITTED PACKAGE IS MISSING THE FOLLOWING
 DRAWINGS: COVER, A201, ID100. PROVIDE TWO COMPLETE
 SETS. SEC. 107.2.1 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE. DON'T
 STAPLE OLD DRAWINGS TO NEW SETS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-16 Cont ID  
Sent By jgomez Date 2016-03-16 Time 14:59 Rev Time 0.00
Received By jgomez Date 2016-03-16 Time 14:21 Sent To  
Notes
2016-03-16 15:01:25RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO AND
 COMMENTS BELOW MAY BE ADDRESSED AFTER THE PERMIT IS
 ISSUED. FEES MAY APPLY. CONTRACTOR TO ADVICE IF PROVISO
 OPTION IS PREFERRED AT THIS TIME. OTHERWISE, RE-SUBMIT
 PACKAGE ADDRESSING THE COMMENTS. COUNTY IMPACT FEES
 ASSESSMENT IS REQUIRED PRIOR TO ISSUING THE PERMIT.
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 2- EXTERIOR WALL SECTION "C" ON SHEET S101:
 A) SPECIFY HOW ARE THE NEW 2 X 6 STUDS ATTACHED TO THE
 TOP AND TO THE BOTTOM PLATES. SEC. R801.2 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 B) SPECIFY THE MIN. STUCCO THICKNESS AS REQUIRED BY
 TABLE R702.1(1) OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 C) 4" CLEARANCE FROM FINISHED GRADE TO STUCCO DOESN'T
 COMPLY WITH SEC. R318.7 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014). REVISE AS REQUIRED.
  
 3- BREEZEWAY ROOF DETAIL "A" ON SHEET S102 AND SHEET
 A300:
 A) SPECIFY THE ROOF SLOPE AS REQUIRED BY SEC. R905.11.1
 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 B) SPECIFY SOFFIT VENT SIZE AND SPACING. SEC. R806 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 4- SHEET A300: CLARIFY HOW PROVIDING R-30 CLOSED CELL
 INSULATION ON 2X6 WALLS. PROVIDE MANUFACTURER'S SPECS
 SHOWING REQUIRED THICKNESS TO MEET THE R-30 VALUE. SEC.
 107.2.1 CITY AMENDMENTS.
  
 5- ENERGY CALCULATIONS SUBMITTED:
 NOTE: THIS IS A CONTRIBUTING HISTORIC HOUSE, ENERGY
 CALCULATIONS ARE NOT REQUIRED. IF CONTRACTOR WANTS THE
 ENERGY CALCULATIONS SUBMITTED FOR REVIEW, THEN THEY
 NEED TO BE REVISED AS FOLLOWS:
 A) OWNER/AGENT TO CERTIFY BOTTOM OF FORM AS REQUIRED BY
 SEC. R103.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 B) COMPLETE ALL THE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER NAME, PERMIT OFFICE AND
 JURISDICTION NUMBER. SEC. R101.5.1.1.2 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 C) CONTRACTOR TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD SUBMITTED AS REQUIRED BY SEC.
 R405.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 D) REVISE THE WINDOWS INFORMATION ON PAGE 3 OF 4. THE
 ORIENTATION, AREA AND OVERHANG DEPTH AND SEPARATION
 DON'T MATCH PLANS. REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED WHEN ENERGY CALCULATIONS ARE NOT USING
 THE SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
 6- ENERGY CALCULATIONS ARE TAKING THE CEILING FAN
 CREDIT. SPECIFY ON PLANS THE CEILING FAN SIZE ON EACH
 ROOM AS REQUIRED BY TABLE R405.7.6 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) SLIDING GLASS DOORS AS SHOWN ON PLANS. DRAWINGS
 SUBMITTED WITH FLORIDA PRODUCT APPROVAL FL8753-R3 ARE
 FOR SMALL MISSILE IMPACT PROTECTION. NEED DOORS WITH
 LARGE MISSILE IMPACT PROTECTION. SEC. R301.2.1.2 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 B) CASEMENT WINDOWS AS SHOWN ON PLANS. DRAWINGS
 SUBMITTED WITH FLORIDA PRODUCT APPROVAL FL9968-R4 ARE
 FOR SMALL MISSILE IMPACT PROTECTION. NEED WINDOWS WITH
 LARGE MISSILE IMPACT PROTECTION. SEC. R301.2.1.2 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 C) SHINGLES AS SPECIFIED ON PLANS (IF RE-ROOFING THE
 GUEST HOUSE).
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 ENGINEER TO LIST THE FLORIDA PRODUCT APPROVAL NEXT TO
 EACH CONNECTOR.
  
 8- ENGINEER OF RECORD TO APPROVE IN WRITING ABOVE
 PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 9- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE NEW WATER FEATURE STRUCTURE SHOWN
 ON SITE PLAN SHEET SP01. SEC. R301 OF FBC-RESIDENTIAL,
 5TH EDITION (2014).
  
 10- BREEZEWAY FLAT ROOF NOA 12-0601.10 SUBMITTED:
 A) SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE USED.
 SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED. NEED THE CALCULATIONS TO MEET THE DESIGN
 PRESSURES OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE. DON'T
 STAPLE OLD DRAWINGS TO NEW SET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-07-14 Cont ID  
Sent By mvaldes Date 2016-07-14 Time 09:06 Rev Time 0.00
Received By mvaldes Date 2016-07-14 Time 09:06 Sent To B
Notes
2016-07-14 09:07:28ROUTED TO JULIO GOMEZ

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-06-08 Cont ID  
Sent By mvaldes Date 2016-06-08 Time 14:45 Rev Time 0.00
Received By mvaldes Date 2016-06-08 Time 14:45 Sent To  
Notes
2016-06-08 15:28:422ND REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 NEC 230.70(A)(1)/E3601.6.2 -THE SERVICE DISCONNECTING
 MEANS SHALL BE INSTALLED AT A READILY ACCESSIBLE
 LOCATION EITHER OUTSIDE OF A BUILDING OR STRUCTURE OR
 INSIDE NEAREST THE POINT OF ENTRANCE OF THE SERVICE
 CONDUCTORS. UNLESS FEEDER RACEWAYS ARE BEING RANNED
 UNDERGROUND THEN THEY ARE CONSIDERED OUTSIDE THE
 BUILDING
  
 NEC 210.12B/E3902.12 - OUTLETS TO BE AFCI PROTECTED (
 MAKE A NOTE )
  
 FBC-E R404.1 A MINIMUM OF 75 PERCENT OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICACY LAMPS.
  
 FBC-E R402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-01 Cont ID  
Sent By vperez Date 2016-03-01 Time 08:20 Rev Time 0.00
Received By vperez Date 2016-03-01 Time 08:20 Sent To  
Notes
2016-03-01 08:21:28APPLICABLE CODES IN EFFECT:
 FLORIDA RESIDENTIAL BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1.PLEASE NOTE THAT ZONING WILL NEED TO APPROVE 2
 ELECTRICAL METERS AS SHOWN, TO THIS SINGLE FAMILY
 DWELLING. AT THIS TIME A SINGLE METER ARRANGEMENT WILL
 NEED TO BE SHOWN. FBC 107.3.5
 2.SHOW ONE-LINE RISER DIAGRAM WITH ALL ASSOCIATED
 INFORMATION, EXAMPLE FEEDER CONDUCTOR SIZES ETC. FBC
 107.3.5
 3.LABEL ELECTRICAL EQUIPMENT?S AIC RATINGS, SERVICE AND
 PANEL BOARDS. FBC RES E3404.2.
 4.PROVIDE A NOTE TO REFLECT FBC RES E4002.14
 RECEPTACLES TO BE LISTED TAMPER RESISTANT.
 5.FBC RES 314 REQUIRES THE INTERCONNECTION OF SMOKE
 DETECTOR DEVICES UNLESS EXCEPTIONS ARE MET. PROVIDE A
 NOTE INDICATING REQUIREMENTS.
 6.SHOW THE REQUIRED CLEARANCE FOR THE PANEL BOARD SHOWN
 IN CLOSET AREA PER FBC RES E3405.1
 7.RECEPTACLE SPACING TO BE PROVIDED PER FBC RES
 E3901.2.2 WALL SPACE: SEE LIVING ROOM AREA AND BEDROOM.
 8.FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL; PLEASE
 FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2016-03-03 Cont ID  
Sent By pleduc Date 2016-03-03 Time   Rev Time 0.00
Received By pleduc Date 2016-03-03 Time 11:41 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2016-06-03 Cont ID  
Sent By fmittner Date 2016-06-03 Time 08:51 Rev Time 0.00
Received By fmittner Date 2016-06-03 Time 08:51 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2016-03-18 Cont ID  
Sent By fmittner Date 2016-03-18 Time 15:17 Rev Time 0.00
Received By fmittner Date 2016-03-18 Time 15:17 Sent To  
Notes
2016-03-18 15:18:24NEEDS COA, NEW HORIZONTALO WINDOWS NOT APPROPRIATE FOR
 ARCHITECTURAL STYLE. QUESTIONS, CONTACT FRIEDERIKE
 MITTNER 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-07-26 Cont ID  
Sent By jgomez Date 2016-07-26 Time 10:38 Rev Time 0.00
Received By jgomez Date 2016-07-12 Time 09:27 Sent To  
Notes
2016-07-13 09:28:12RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-15 Cont ID  
Sent By jgomez Date 2016-06-15 Time 11:20 Rev Time 0.00
Received By jgomez Date 2016-05-27 Time 13:06 Sent To  
Notes
2016-05-27 13:06:59R20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-18 Cont ID  
Sent By lmarchan Date 2016-03-18 Time 15:49 Rev Time 0.00
Received By lmarchan Date 2016-02-25 Time 13:57 Sent To  
Notes
2016-03-01 08:22:163/01 TO BIN R03
2016-02-25 13:57:56R03

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2016-07-26 Cont ID  
Sent By jgomez Date 2016-07-26 Time 10:59 Rev Time 0.00
Received By jgomez Date 2016-07-26 Time 10:59 Sent To  
Notes
2016-07-26 11:00:12NO FEES DUE. MU-2016-8972.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-06-14 Cont ID  
Sent By jgomez Date 2016-06-14 Time 18:32 Rev Time 0.00
Received By jgomez Date 2016-06-14 Time 18:32 Sent To  
Notes
2016-06-14 18:35:59NEED PALM BEACH COUNTY IMPACT FEE STAMP ON PLANS.
  
 NO FEES DUE. MU-2016-008972.
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-03-16 Cont ID  
Sent By jgomez Date 2016-03-16 Time 14:57 Rev Time 0.00
Received By jgomez Date 2016-03-16 Time 14:57 Sent To  
Notes
2016-03-16 14:59:391- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-06-07 Cont ID  
Sent By jvalido Date 2016-06-07 Time 17:34 Rev Time 0.00
Received By jvalido Date 2016-06-07 Time 17:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-03-15 Cont ID  
Sent By fmittner Date 2016-03-15 Time 16:25 Rev Time 0.00
Received By jvalido Date 2016-03-15 Time 15:45 Sent To  
Notes
2016-03-15 16:25:12R103.1.1.2 - PROVIDE CERTIFICATION OF COMPLIANCE AS PER
 SEC 553.907 FLORIDA STATUES. SIGN BOTH FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILDING CONSTRUCTION.

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-06-09 Cont ID  
Sent By gjohnson Date 2016-06-09 Time 06:19 Rev Time 0.00
Received By gjohnson Date 2016-06-09 Time 06:19 Sent To  
Notes
2016-06-09 06:19:39REVIEWED AND APPROVED BY GEORGE EARL

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-02-27 Cont ID  
Sent By tklarge Date 2016-02-27 Time 11:22 Rev Time 0.00
Received By tklarge Date 2016-02-27 Time 11:09 Sent To  
Notes
2016-02-27 11:21:571) SUBMIT A SANITARY RISER FOR REVIEW FOR THE CHANGES
 BEING MADE TO THE PLUMBING SYSTEM. FBC 107.3.5.3.
 2) THE WATER SUPPLY VALVES FOR THE STACKED WASHER/DRYER
 SHALL BE PROVIDED WITH ACCESS. THEY CANNOT BE LOCATED
 BEHIND THE UNIT UNLESS THERRE IS AN ACCESS PANEL IN THE
 UNIT. 2014 FBCR SEC.P2903.9.3.
 3) SUBMIT A GAS RISER FOR REVIEW FOR THE TANKLESS WATER
 HEATERS OR PLACE A NOTE ON THE PLUMBING SHEET THAT THE
 GAS WILL BE UNDER A SEPARATE PERMIT.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2016-06-15 Cont ID  
Sent By jgomez Date 2016-06-15 Time 11:18 Rev Time 0.00
Received By jgomez Date 2016-06-15 Time 11:18 Sent To  
Notes
2016-06-15 11:19:54(1) NO RE-ROOFING AT THIS TIME. NO PRODUCT APPROVAL
 SUBMITTED.
 (2) NO FLAT ROOF ON BREEZEWAY. OPEN TRELLIS. NO ROOF.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-03-17 Cont ID  
Sent By jgomez Date 2016-03-17 Time 09:34 Rev Time 0.00
Received By jgomez Date 2016-03-17 Time 09:34 Sent To  
Notes
2016-03-17 09:36:53ROOFING REVIEW:
  
 1-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) SHINGLES AS SPECIFIED ON PLANS (IF RE-ROOFING THE
 GUEST HOUSE).
  
 2- BREEZEWAY FLAT ROOF NOA 12-0601.10 SUBMITTED:
 A) SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE USED.
 SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED. NEED THE CALCULATIONS TO MEET THE DESIGN
 PRESSURES OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2016-06-03 Cont ID  
Sent By fmittner Date 2016-06-03 Time 08:51 Rev Time 0.00
Received By fmittner Date 2016-06-03 Time 08:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-03-18 Cont ID  
Sent By fmittner Date 2016-03-18 Time 15:18 Rev Time 0.00
Received By fmittner Date 2016-03-18 Time 15:18 Sent To  
Notes
2016-03-18 15:19:38EXCEEDS LOT COVERAGE REQUIREMENT, NO SECOND KITCHEN
 PERMITTED, NEED DETAILS ON CONNECTION BETWEEN MAIN AND
 ACCESSORY STRUCTURE. QUESTIONS, CONTACT FRIEDERIKE
 MITTNER 822-1457.