Plan Review Details - Permit 16020922
Plan Review Stops For Permit 16020922
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-03-09 Cont ID  
Sent By rmcdouga Date 2016-03-09 Time 13:08 Rev Time 0.00
Received By rmcdouga Date 2016-03-09 Time 13:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-03-08 Cont ID  
Sent By rmcdouga Date 2016-03-08 Time 14:53 Rev Time 0.00
Received By rmcdouga Date 2016-03-08 Time 14:53 Sent To  
Notes
2016-03-08 14:55:39ENGINEER ONLY SIGNED PAGE 1 OF THE 3 PAGES. NOTHING ON
 PAGE 1 REFERED TO THE OTHER 2 PAGES. FS471

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-03-08 Cont ID  
Sent By rmcdouga Date 2016-03-08 Time 07:51 Rev Time 0.00
Received By rmcdouga Date 2016-03-08 Time 07:18 Sent To  
Notes
2016-03-08 09:00:20PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE RAS CALCULATIONS THAT ARE SUBMITTED FOR PUBLIC
 RECORD ARE REQUIRED TO HAVE THE ENGINEER'S HANDWRITTEN
 SIGNATURE IN ADDITION TO HIS SEAL. COPIES OR OTHER
 FACSIMILES ARE NOT ACCEPTABLE. FS 471 AND FAC
 61G15-23.002
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-02-25 Cont ID  
Sent By rmcdouga Date 2016-02-25 Time 11:06 Rev Time 0.00
Received By rmcdouga Date 2016-02-25 Time 11:06 Sent To  
Notes
2016-02-25 11:30:17PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THERE ARE TWO BUILDINGS ON THIS PROPERTY. INDICATE
 WHICH ONE OF THE BUILDINGS IS TO BE RE-ROOFED.
 FBC107.2.1
  
 2) PROVIDE TWO COPIES OF A ROOF DIAGRAM WITH
 DIMENSIONS, LOCATIONS OF SCUPPERS, ROOF SLOPE, PARAPET
 HEIGHTS ON ALL SIDES AND ANY OTHER RELAVENT
 INFORMATION. FBC 107.2.1
  
 3) THE FASTENER SPACING ON SECTION C OF THE FORM THAT
 YOU SUBMITTED DOES NOT MATCH THE SPACING SPECIFIED ON
 PAGE 23 OF THE NOA. THE MAXIMUM DESIGN PRESSURE ON PAGE
 23 IS NEGATIVE 52.5 PSF. SPECIFY THE REQUIRED DESIGN
 PRESSURES FOR THE THREE ROOF ZONES ON THE ROOF DRAWING.
 IF THE REQUIRED PRESSURES ARE MORE THAN -52.5 PSF, THEN
 SUBMIT SIGNED AND SEALED RAS 117 CALCULATIONS FOR THE
 ENHANCED FASTENING AS REQUIRED BY LIMITATION #7 ON PAGE
 42 OF THE NOA NO.14-0529.02.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-08 Cont ID  
Sent By rmcdouga Date 2016-03-08 Time 07:51 Rev Time 0.00
Received By rmcdouga Date 2016-03-04 Time 10:25 Sent To  
Notes
2016-03-07 10:26:06RMCDOUGAL'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-25 Cont ID  
Sent By rmcdouga Date 2016-02-25 Time 11:30 Rev Time 0.00
Received By rmcdouga Date 2016-02-24 Time 15:11 Sent To  
Notes
2016-02-24 15:11:58RMCDOUGAL