Plan Review Details - Permit 16020874
Plan Review Stops For Permit 16020874 |
Review Stop |
G |
GAS REVIEW |
Rev No |
4 |
Status |
P |
Date |
2016-03-08 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-03-08 |
Time |
03:22 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-03-08 |
Time |
03:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
F |
Date |
2016-03-05 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-03-05 |
Time |
03:42 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-03-05 |
Time |
03:37 |
Sent To |
|
|
Notes |
2016-03-05 03:50:03 | 1) THE PLAN THAT WAS SUBMITTED NOTES A DELIVERY | | PRESSURE OF 5 PSI. THERE IS NO GAS TABLE IN THE 2014 | | FUEL GAS CODE FOR A 5 PSI TABLE FOR PE PIPE. SUBMIT 2 | | COPIES OF THE APPLICABLE SIZING TABLE USED FOR THE | | DESIGN OF THIS SYSTEM. FBC 107.2.1 FGC SEC.402.3. I | | CANNOT CHECK THE SIZING OF THE SYSTEM WITHOUT THE | | SIZING TABLE. | | 2) THE MANUF. SPECIFICATIONS FOR THE TANKLESS WATER | | HEATER MODEL IDENTIFIED GIVES A RANGE OF 15,000 BTU'S | | UP TO 180,000 BTU'S. IINDICATE THE SPECIFIC BTU LOAD ON | | THE PLANS FOR THE TANKLESS WATER HEATER AND ALSO THE | | RANGE ( MANUF. SPECS SHOW A BTU LOAD UP TO 20,000.) 3RD | | REQUEST. | | 3) SUBMIT TWO COPIES OF THE REVISED GAS DRAWING. ONLY | | ONE COPY HAS BEEN SUBMITTED. FBC 107.2.1. | | | | NOTE: SINCE THE PLANS HAVE BEEN REJECTED THREE TIMES | | FOR THE SAME ITEMS, A RESUBMITTAL FEE OF 4 TIMES THE | | PLAN REVIEW FEE IS REQUIRED TO BE PAID PER FL. STATUTE | | 553.80. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2016-03-03 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-03-03 |
Time |
05:42 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-03-03 |
Time |
05:36 |
Sent To |
|
|
Notes |
2016-03-03 05:39:22 | 1) ALL THE PREVIOUS GAS COMMENTS HAVE NOT BEEN | | ADDRESSED. | | | | 2).SHOW THE BTU LOAD OF EACH APPLIANCE / EQUIPMENT AND | | THE TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2014 | | FBC-FUEL GAS SECS.401.8 THRU 402.6.1 AND TABLES 402.4 | | (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2413. 2ND | | REQUEST. | | | | 3).INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM | | ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES. | | SEC. G2413.2. . 2ND REQUEST. | | | | 4).SUBMIT MANUFACTURER'S SPECIFICATION SHEETSL FOR ALL | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | 54, NFPA 58, AND FBC-2014 FUEL GAS CODE SEC. 402.2, AND | | 301.3 OR 2014 FBC-RES. SEC. G2404.3. GAS APPLIANCES | | SHALL BE LISTED AND LABELED.SUBMIT TWO COPIES OF ALL | | DOCUMENTS. | | | | 5) EACH APPLIANCE SHALL BE PROVIDED WITH A SHUTOFF | | VALVE IN ACCCORDANCE WITH THE 2014 FUEL GAS CODE | | SECS.409.5, 2ND REQUEST. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2016-02-24 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-02-24 |
Time |
06:23 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-02-24 |
Time |
06:04 |
Sent To |
|
|
Notes |
2016-02-24 06:22:59 | | | 1.SHOW THE BTU LOAD OF EACH APPLIANCE / EQUIPMENT AND | | THE TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2014 | | FBC-FUEL GAS SECS.401.8 THRU 402.6.1 AND TABLES 402.4 | | (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2413. | | | | 2.INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM ON | | THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES. | | SEC. G2413.2. . | | | | 3.SUBMIT MANUFACTURER'S SPECIFICATION SHEETS / | | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY | | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014 | | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED | | AND LABELED. | | | | 4) EACH APPLIANCE SHALL BE PROVIDED WITH A SHUTOFF | | VALVE IN ACCCORDANCE WITH THE 2014 FUEL GAS CODE | | SECS.409.5, | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2016-03-08 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-03-08 |
Time |
03:23 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-03-08 |
Time |
03:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2016-03-05 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-03-05 |
Time |
03:54 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-03-04 |
Time |
10:38 |
Sent To |
|
|
Notes |
2016-03-04 10:38:22 | TLARGE'S DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2016-03-03 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-03-03 |
Time |
05:42 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-03-01 |
Time |
10:01 |
Sent To |
|
|
Notes |
2016-03-02 10:01:29 | RESUB ROUTED TO TKLARGE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-02-24 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-02-24 |
Time |
09:48 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-02-23 |
Time |
12:43 |
Sent To |
|
|
Notes |
2016-02-23 12:43:55 | PLUMB -$5000 |
|
|
|