Plan Review Details - Permit 16020859
Plan Review Stops For Permit 16020859
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-04-05 Cont ID  
Sent By jwitmer Date 2016-04-05 Time 12:31 Rev Time 0.00
Received By jwitmer Date 2016-04-05 Time 12:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-01 Cont ID  
Sent By jwitmer Date 2016-03-01 Time 08:54 Rev Time 0.00
Received By jwitmer Date 2016-03-01 Time 07:29 Sent To  
Notes
2016-03-01 08:54:39BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16020859
 ADD: 8055 IRONHORSE BLVD./ CLUBHOUSE
 CONT: DARLING CONSTRUCTION
 TEL: 772-215-9818
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 01/2016
 ACTION: DENIED
  
 NOTICE: 2014 FBC-ACCESSIBILITY CODE, SCOPE 201.1. THIS
 CODE ESTABLISHES STANDARDS FOR ACCESSIBILITY TO PLACES
 OF PUBLIC ACCOMMODATION AND COMMERCIAL FACILITIES BY
 INDIVIDUALS WITH DISABILITIES, PRIVATE CLUBS PURSUANT
 TO SECTION 553.505, F.S.
  
 1) SHEET ALR-3.0 THE NEW GUEST MENS LOCKER ROOM DOES
 NOT SHOW COMPLIANCE WITH THE 2014 FBC-ACCESS. CODE
 BENCHES SHALL COMPLY WITH 903.1 (2-6).
  
 2) SHEET ALR-3.0 THE NEW MENS TV ROOM:
 2A) SEE NOTE 11 WALL HUNG TV SHEET ALR-5.0 DETAIL 3
 WALL MOUNTED TV MUST MEET REACH RANGES, 2014
 FBC-ACCESSIBILITY CODE EITHER;
  
 308.2.1FORWARD REACH UNOBSTRUCTED. WHERE A FORWARD
 REACH IS UNOBSTRUCTED, THE HIGH FORWARD REACH SHALL BE
 48 INCHES (1220 MM) MAXIMUM AND THE LOW FORWARD REACH
 SHALL BE 15 INCHES (380 MM) MINIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 308.3.2 OBSTRUCTED HIGH REACH. WHERE A CLEAR FLOOR OR
 GROUND SPACE ALLOWS A PARALLEL APPROACH TO AN ELEMENT
 AND THE HIGH SIDE REACH IS OVER AN OBSTRUCTION, THE
 HEIGHT OF THE OBSTRUCTION SHALL BE 34 INCHES (865 MM)
 MAXIMUM AND THE DEPTH OF THE OBSTRUCTION SHALL BE 24
 INCHES (610 MM) MAXIMUM. THE HIGH SIDE REACH SHALL BE
 48 INCHES (1220 MM) MAXIMUM FOR A REACH DEPTH OF 10
 INCHES (255 MM) MAXIMUM.
  
 2B) SEE DETAIL # 7 CABINETRY NO DIMENSIONS GIVEN. 2014
 FBC-ACCESSIBILITY CODE 902.3 HEIGHT. THE TOPS OF WORK
 SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34
 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
  
 3) SHEET ALR-3.1:
 3A) NOTE # 7. OPENINGS FROM THE MENS AND LADIES LOCKER
 ROOM TO ATTENDANT ROOM. PLEASE REVIEW OPENING TO THE
 LOCKER ROOM TO BE 3 FEET 3 INCHES TO THE BOTTOM OF THE
 OPENING. 2014 FBC-ACCESSIBILITY CODE 902.3 HEIGHT. THE
 TOPS OF WORK SURFACES SHALL BE 28 INCHES (710 MM)
 MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 3B) NOTE # 9 MILLWORK CABINETRY. 2014 FBC-ACCESSIBILITY
 CODE 902.3 HEIGHT. THE TOPS OF WORK SURFACES SHALL BE
 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3C) SINK IN MILLWORK CABENTRY TO COMPLY WITH 2014
 FBC-ACCESS. CODE 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3D) THE DOOR BETWEEN THE MENS TV ROOM AND THE
 ATTENDANTS ROOM ON THE ATTENDANTS ROOM SIDE DOES NOT
 HAVE THE REQUIRED 18 INCHES ON THE LATCH SIDE OF THE
 DOOR. 2014 FBC-ACCESS. CODE 404.2.4 MANEUVERING
 CLEARANCES.
  
 3E) THE WOMENS TV ROOM NOTE 11 NEW WALL HUNG TV. 2014
 FBC-ACCESSIBILITY CODE EITHER;
  
 308.2.1FORWARD REACH UNOBSTRUCTED. WHERE A FORWARD
 REACH IS UNOBSTRUCTED, THE HIGH FORWARD REACH SHALL BE
 48 INCHES (1220 MM) MAXIMUM AND THE LOW FORWARD REACH
 SHALL BE 15 INCHES (380 MM) MINIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 308.3.2 OBSTRUCTED HIGH REACH. WHERE A CLEAR FLOOR OR
 GROUND SPACE ALLOWS A PARALLEL APPROACH TO AN ELEMENT
 AND THE HIGH SIDE REACH IS OVER AN OBSTRUCTION, THE
 HEIGHT OF THE OBSTRUCTION SHALL BE 34 INCHES (865 MM)
 MAXIMUM AND THE DEPTH OF THE OBSTRUCTION SHALL BE 24
 INCHES (610 MM) MAXIMUM. THE HIGH SIDE REACH SHALL BE
 48 INCHES (1220 MM) MAXIMUM FOR A REACH DEPTH OF 10
 INCHES (255 MM) MAXIMUM.
  
 4) PLEASE ALSO REVIEW 2014 FBC-ACCESS. CODE 202.4.1
 DISPROPORTIONATE COST. ALTERATIONS MADE TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO THE ALTERED AREA WILL BE
 DEEMED DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN
 THE COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO
 THE PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
 3)
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-31 Cont ID  
Sent By vperez Date 2016-03-31 Time 08:48 Rev Time 0.00
Received By vperez Date 2016-03-31 Time 08:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-07 Cont ID  
Sent By vperez Date 2016-03-07 Time 08:56 Rev Time 0.00
Received By vperez Date 2016-03-07 Time 08:56 Sent To  
Notes
2016-03-07 08:58:15INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1.PLEASE CLARIFY IF THE EXISTING LIGHTING COMPLIES WITH
 THE AUTOMATIC MEANS OF CONTROL PER FBC ENERGY
 CONSERVATION 2014 5TH EDITION. 405.2
 2.SHOW THE EXISTING PANEL BOARDS UNDER SCOPE OF REMODEL
 FOR REFERENCE PURPOSE. LOADS ARE NOT REQUIRED AS NO
 ADDITIONAL LOADS ARE SHOWN. FBC 107.3.5 MINIMUM
 CRITERIA FOR PLAN REVIEW.
 3.LABEL ON FLOOR PLAN THE CIRCUIT NUMBER DESIGNATION
 FOR LIGHTING AND POWER BEING RELOCATED. FBC 107.3.5
 MINIMUM CRITERIA FOR PLAN REVIEW.
 4.LABEL RECEPTACLE OUTLETS IN LOCKERS TO BE GFCI
 PROTECTED PER NEC 2011 210.8B(7)
 5.ADDRESS FIRE COMMENTS REGARDING ELECTRICAL SHEETS.
 6.PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-03-31 Cont ID  
Sent By pleduc Date 2016-03-31 Time   Rev Time 0.00
Received By pleduc Date 2016-03-31 Time 13:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-03-03 Cont ID  
Sent By pleduc Date 2016-03-03 Time   Rev Time 0.00
Received By pleduc Date 2016-03-03 Time 10:54 Sent To  
Notes
2016-03-03 11:05:38THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF
 THE 5TH EDITION OF FLORIDA FIRE PREVENTION CODE
 INCLUDING THE 2012 EDITION OF NFPA 1 AND NFPA 101,
 INCLUDING CHAPTER 43, BUIULDING REHABILITATION, AND ALL
 OTHER APPLICABLE CODES OR STANDARDS.
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
  
 2. THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF
 THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE
 AND COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF
 WALLS REQUIRE AN EVALUATION.
  
 A. THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 B. ANY AND ALL WORK ON THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
 C. ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 3. SHEET FS 1.1 - 1.2 - THE INDICATED LOCATION OF THE
 EXISTING SPRINKLER HEADS AND NEW WALL LOCATIONS DO NOT
 APPEAR TO MEET THE CODE COVERAGE REQUIREMENTS OF NFPA
 13.
  
 PROVIDE A NOTE INDICATING FIRE SPRINKLER WORK SHALL BE
 SUBMITTED UNDER SEPARATE SHOP DRAWINGS.
  
 4. SHEET E 1.0 - 1.2 - THE INDICATED LOCATION OF THE
 EXISTING FIRE ALARM DEVICES AND NEW WALL LOCATIONS DO
 NOT APPEAR TO MEET THE CODE COVERAGE REQUIREMENTS OF
 NFPA 72.
  
 PROVIDE A NOTE INDICATING FIRE SPRINKLER WORK SHALL BE
 SUBMITTED UNDER SEPARATE SHOP DRAWINGS.
  
 5. THE NATURE OF THE REMODEL AFFECTS THE PREVIOSULY
 APPROVED LIFE SAFETY PLAN INCLUDING OCCUPANCY LOADS,
 COMMON PATHS OF TRAVEL, EXIT PATHS AND EXIT DOORS.
  
 PLEASE PROVIDE A LIFE SAFETY PLAN INDICATING COMPLIANCE
 WITH NFPA 101, CHAPTER 7, MEANS OF EGRESS.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-05 Cont ID  
Sent By jwitmer Date 2016-04-05 Time 12:31 Rev Time 0.00
Received By jwitmer Date 2016-03-30 Time 13:14 Sent To  
Notes
2016-03-30 13:14:27B26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-07 Cont ID  
Sent By vperez Date 2016-03-07 Time 08:58 Rev Time 0.00
Received By vperez Date 2016-03-07 Time 08:58 Sent To  
Notes
2016-03-07 08:58:463/7 TO CAROLINE FOR COMPLETION
2016-02-23 13:32:22B03

Review Stop P PLUMBING
Rev No 1 Status N Date 2016-02-28 Cont ID  
Sent By tklarge Date 2016-02-28 Time 05:19 Rev Time 0.00
Received By tklarge Date 2016-02-28 Time 05:04 Sent To  
Notes
***NONE***