Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-02-24 Cont ID  
Sent By jgomez Date 2016-02-24 Time 17:30 Rev Time 0.00
Received By jgomez Date 2016-02-24 Time 17:30 Sent To  
Notes
2016-02-24 17:39:39RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE: NONE OF THE COMMENTS WERE ADDRESSED.
  
  
 1- FLAT ROOF: PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7 ON
 LAST PAGE OF NOA 12-1003.05 SUBMITTED.
 NOTE: THIS PROPERTY IS LOCATED IN EXPOSURE "D".
 CALCULATIONS REQUIRED TO MEET THE DESIGN PRESSURES AS
 REQUIRED BY SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 2- NEED TO PROVIDE COMPLIANCE WITH THE ROOF TO WALL
 CONNECTIONS AS REQUIRED BY SEC. 708.8 OF FBC-EXISTING
 BUILDING.
  
 3- PROVIDE SKETCH SHOWING ROOF AREAS TO BE RE-ROOFED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-02-22 Cont ID  
Sent By jgomez Date 2016-02-22 Time 10:26 Rev Time 0.00
Received By jgomez Date 2016-02-22 Time 09:26 Sent To HIST
Notes
2016-02-22 11:00:30RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- FLAT ROOF: PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7 ON
 LAST PAGE OF NOA 12-1003.05 SUBMITTED.
 NOTE: THIS PROPERTY IS LOCATED IN EXPOSURE "D".
 CALCULATIONS REQUIRED TO MEET THE DESIGN PRESSURES AS
 REQUIRED BY SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 2- NEED TO PROVIDE COMPLIANCE WITH THE ROOF TO WALL
 CONNECTIONS AS REQUIRED BY SEC. 708.8 OF FBC-EXISTING
 BUILDING.
  
 3- PROVIDE SKETCH SHOWING ROOF AREAS TO BE RE-ROOFED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2016-02-24 Cont ID  
Sent By jgomez Date 2016-02-24 Time 17:40 Rev Time 0.00
Received By fmittner Date 2016-02-24 Time 15:52 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2016-02-22 Cont ID  
Sent By jgomez Date 2016-02-22 Time 11:00 Rev Time 0.00
Received By fmittner Date   Time   Sent To  
Notes
2016-02-22 11:16:09HISTORIC PROPERTY SHALL USE BARREL TILE NOT S. FHM
 SPOKE TO CONTRACTOR.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-02-29 Cont ID  
Sent By cthroop Date 2016-02-29 Time 11:33 Rev Time 0.00
Received By cthroop Date 2016-02-29 Time 11:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-24 Cont ID  
Sent By jgomez Date 2016-02-24 Time 17:40 Rev Time 0.00
Received By jgomez Date 2016-02-23 Time 15:17 Sent To HIST
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-22 Cont ID  
Sent By jgomez Date 2016-02-22 Time 09:26 Rev Time 0.00
Received By jgomez Date 2016-02-19 Time 09:39 Sent To  
Notes
2016-02-19 09:40:05JGOMEZ


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved