Plan Review Details - Permit 16020642
Plan Review Stops For Permit 16020642
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-03-14 Cont ID  
Sent By jwitmer Date 2016-03-14 Time 06:56 Rev Time 0.00
Received By jwitmer Date 2016-03-14 Time 06:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-02-26 Cont ID  
Sent By jwitmer Date 2016-02-26 Time 09:47 Rev Time 0.00
Received By jwitmer Date 2016-02-26 Time 07:30 Sent To  
Notes
2016-02-26 09:47:14BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16020642
 ADD: 421 BELVEDERE RD.
 CONT: L B ROWE
 TEL: 835-1499
 E-MAIL: ????????????
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. FEB. 26/2014
 ACTION: DENIED
  
 1) SHEET 1.0A :
  
 1A) THERE IS A NOTE ON THIS SHEET DOUBLE 2 X 10 X18 FT
 ROOF JOIST AT 16 INCHES O.C.(TOTAL OF 18) FASTENED
 TOGETHER.
 THE PLANS INDICATE 10 DOUBLED JOIST. THE ABOVE
 STATEMENT DOES NOT MAKE IT CLEAR IF 9 DOUBLED JOIST ARE
 BEING REPLACED OR IF 18 DOUBLED JOIST ARE BEING
 REPLACED SINCE THE COUNT DIFFERS FROM WHAT IS SHOWN ON
 THE PLANS? 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED. DISCREPANCY IN PLANS.
  
 1B) THIS SAME SHEET INDICATES THE INSTALATION OF DOUBLE
 2 X 10 X18 FT. ROOF JOIST AT 16 INCHES O.C. BUT THERE
 IS NO MENTION OF HOW THE JOIST ARE GOING TO BE FASTENED
 AT THE ENDS TO BECOME OF THE (MWFRS) MAIN WIND FORCE
 RESISTING SYSTEM AS WELL AS THE ROOF FRAMING THAT THE
 ROOF DIAPHRAGM WILL FASTEN INTO?
 2014 FBC-B 2309.9.3 JOIST HNGERS AND FRAMING ANCHORS.
 2304.10.3 ROOF FRAMING. EVERY ROOF GIRDER AND AT LEAST
 EVERY ALTERNATE ROOF BEAM SHALL BE ANCHORED TO ITS
 SUPPORTING MEMBER; AND EVERY MONITOR AND EVERY SAWTOOTH
 CONSTRUCTION SHALL BE ANCHORED TO THE MAIN ROOF
 CONSTRUCTION. SUCH ANCHORS SHALL CONSIST OF STEEL OR
 IRON BOLTS OF SUFFICIENT STRENGTH TO RESIST VERTICAL
 UPLIFT OF THE ROOF.
  
 1C) THE PLANS INDICATE THE USE OF DOUBLE 2 X 10 X 18
 FT. BUT THE DESIGNER OF RECORD DOES NOT INDICATE THE
 SPECIES OF WOOD, GRADE, NOR THE MODULUS OF ELASTICITY
 (E-VALUE) NOR THE (FB-VALUES BENDING) FOR SAWN LUMBER
 FRAMING MEMBERS. 2014 FBC-B 2307.1 LOAD & RESISTANCE
 FACTOR DESIGN. CLEAR SPAN NOT GIVEN AS WELL?
  
 1D) THE PLANS ALSO INDICATE THE REPLACEMENT OF THE ROOF
 SHEATHING BUT NO NAILING SCHEDULE FOR ROOF SHEATHING
 NAILING PATTERN WAS PROVIDED? 107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED. FBC-B TABLE 2304.9.1 SEE
 FOOTNOTES "N & O".
  
 1E) ADDITIONAL INFORMATION REQUIRED 107.2.1.3. ON THIS
 PLAN THERE IS ON THE EAST WALL A WINDOW IDENTIFIED AS
 (1) AND A DOOR IDENTIFIED AS (5) BOTH OF THESE WERE IN
 THE FIRE AREA BUT THE PLANS AARE NOT CLEAR IF THESE
 AREAS WERE DESTROYED DURING THE FIRE AND WERE TO BE
 REPLACED.
 THE NORTH WALL IN THE FIRE AREA THERE IS A DASHED LINE,
 EITHER A DOOR OR WINDOW, PLEASE IDENTIFY, WAS THIS AREA
 ALSO BREACHED DURING THE FIRE?
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-12 Cont ID  
Sent By vperez Date 2016-03-12 Time 06:42 Rev Time 0.00
Received By vperez Date 2016-03-12 Time 06:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-22 Cont ID  
Sent By vperez Date 2016-02-22 Time 13:25 Rev Time 0.00
Received By vperez Date 2016-02-22 Time 13:25 Sent To  
Notes
2016-02-22 13:26:30INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1.PLEASE UPDATE ALL FBC 2104 5TH EDITION REFERENCES TO
 THE ELECTRICAL NOTES ON SHEET E2.1E AS SHOWN ON
 ARCHITECTURAL SHEETS. FBC 107.5.3
 2.SHOW WINDOW RECEPTACLES REQUIRED PER NEC 210.62-
 220.14G, NOT SHOWN ON FLOOR PLAN OR PANEL LOAD
 SCHEDULES.
 3.PLEASE PROVIDE SIZE OF THE SERVICE CONDUCTORS,
 GROUNDING ELECTRODE CONDUCTOR, CONDUIT SIZES AND
 FEEDERS TO BE LEGIBLE FOR THE SERVICE SHOWN, FBC
 107.3.5- NEC 310.15B16 TABLE, 250.22 TABLE.
 4.PROVIDE A NOTE ON RISER DIAGRAM TO BOND THE GAS
 PIPING, PER NEC 250.104B
 5.SHOW ON PANEL SCHEDULES THE AIC RATING FOR ALL 3
 PANEL BOARDS. FBC 107.3.5
 6.PLEASE CLARIFY PANEL B MCB 150AMPS. SHOW THE LOAD
 CALCULATIONS ON PANEL A AS IT ORIGINATES THERE. SHOW
 WHAT CIRCUIT SPACES ARE DESIGNATED FOR THIS 3 POLE
 BREAKER FEEDING PANEL B. NEC 240.4 FBC 107.3.5
 7.PROVIDE A WP/GFCI RECEPTACLE FOR SERVICE AT THE A/C
 LOCATION WITHIN 25 FT OF UNIT PER NEC 210.63
 8.COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-03-10 Cont ID  
Sent By rlindow Date 2016-03-10 Time   Rev Time 0.00
Received By rlindow Date 2016-03-10 Time   Sent To  
Notes
2016-03-10 09:27:39 
  
 PASSED WITH PROVISO:
 ADD 1 ADDITIONAL EXIT/EMERGENCY LIGHT COMBO AT SW
 EXIT(AS SHOWN ON PLAN).
 ADD 1 EMERGENCY LIGHT AT CENTER OF BACK AREA(AS SHOWN
 ON PLAN).
 LINDOW 3/10/16

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-03-01 Cont ID  
Sent By rlindow Date 2016-03-01 Time 16:00 Rev Time 0.00
Received By rlindow Date 2016-03-01 Time   Sent To  
Notes
2016-03-01 16:02:34 
  
 SHOW FIRE RESISTANCE RATINGS ON PLANS FOR BOILER ROOM
 WALLS AND WALLS SEPARATING WOOD WORKING AREA FROM REST
 OF BUILDING.
  
 LINDOW, 3/01/16

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2016-03-17 Cont ID  
Sent By tklarge Date 2016-03-17 Time 09:58 Rev Time 0.00
Received By tklarge Date 2016-03-17 Time 09:58 Sent To  
Notes
2016-03-17 09:58:49GAS REVIEW DONE BY GEORGE JOHNSON UNDER PLUMBING
 REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-14 Cont ID  
Sent By vperez Date 2016-03-12 Time 06:56 Rev Time 0.00
Received By jwitmer Date 2016-03-12 Time 06:43 Sent To  
Notes
2016-03-12 06:43:533/12 TO B1
2016-03-04 15:38:14B01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-04 Cont ID  
Sent By lmarchan Date 2016-03-04 Time 15:37 Rev Time 0.00
Received By lmarchan Date 2016-02-22 Time 13:27 Sent To  
Notes
2016-02-22 13:28:10TO B6 BIN
2016-02-18 13:15:28B06

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-02-26 Cont ID  
Sent By jwitmer Date 2016-02-26 Time 09:47 Rev Time 0.00
Received By jwitmer Date 2016-02-26 Time 09:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-02-25 Cont ID  
Sent By ccole Date 2016-02-25 Time 09:58 Rev Time 0.00
Received By ccole Date 2016-02-25 Time 09:58 Sent To  
Notes
2016-02-25 10:00:23MECHANICAL PROVISO
 PERMIT #16020642
 2/25/16
  
 1) A SEPARATE PERMIT WILL BE REQUIRED FOR MECHANICAL
 ALTERATIONS OR EQUIPMENT INSTALLATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-02-27 Cont ID  
Sent By gjohnson Date 2016-02-26 Time 07:18 Rev Time 0.00
Received By gjohnson Date 2016-02-26 Time 14:40 Sent To FIRE
Notes
***NONE***