Plan Review Details - Permit 16020613
Plan Review Stops For Permit 16020613
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-04-13 Cont ID  
Sent By jwitmer Date 2016-04-13 Time 07:30 Rev Time 0.00
Received By jwitmer Date 2016-04-13 Time 06:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-14 Cont ID  
Sent By jwitmer Date 2016-03-14 Time 16:58 Rev Time 0.00
Received By jwitmer Date 2016-03-14 Time 13:01 Sent To  
Notes
2016-03-14 16:55:42BUILDING PLAN REVIEW
 W. P. B. PERMIT : 16020613
 ADD: : 310 EVERNIA ST.
 CONT: ANDERSON MOORE
 TEL: 662-1819
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY/ MARCH 14/ 2016
 ACTION: DENIED
  
 1A) THE RENDERING ON THE FRONT COVER IS DECEIVING IT
 APPEARS THAT YOU ARE VIEWING THROUGH THE FRONT GLAZING
 OF THE BUILDING INTO A HOLLOW TUBE ABOVE THE CONFERENCE
 ROOM. SHEET 004_A1.1.1 SHOWS A CROSS SECTION THROUGH
 THE LENGTH OF THE CONFERENCE ROOM NORTH TO SOUTH, BUT
 IT ACTUALLY ONLY SHOWS THE GLASS WALL, IT DOES NOT
 PROVIDE A DETAIL THROUGH THE GLASS WALL ONLY. SHEET
 005_A1.1.2 THE CEILING PLANS ALSO SHOW A SECTION
 THROUGH THE CEILING/ SOFFIT DETAIL 2/ A3.01 BUT THIS IS
 THE SAME GLASS WALL.
  
 1B) PLEASE PROVIDE BOTH A SECTION NORTH/SOUTH THROUGH
 THE SOFFIT AREA AS WELL AS EAST WEST, PLEASE INCLUDE
 THE WALL THAT SEPARATES THE 2ND CONFERENCE ROOM AND
 FRONT ENTRY. PLEASE PROVIDE HOW THE 2ND STORY OF THE
 ATRIUM WALL IS GOING TO BE BUILT, IS THE WALL GOING TO
 BE HUNG FROM THE 2ND FLOOR CEILING FRAMING. SHEET
 009_A.0.1. SHOWS MOTORIZED WINDOW TREATMENT BUT THERE
 ARE NO DETAILS OF HOW THE SOFFIT AREA SURROUNDING THIS
 ROOM IS GOING TO BE FRAMED/ HUNG? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 2) THE STRUCTURAL SHEETS 015_S1.0 SHOW WELDED AND
 BOLTED CONNECTIONS REQUIRING NORMALLY REQUIRING A
 RESIDENT INSPECTOR. WE ARE REQUESTING THIRD PARTY
 CERTIFICATION FOR THE BOLTED CONNECTIONS AND WELDERS?
 CERTIFICATE FOR ANY FIELD WELDS SINCE THERE IS A
 MINIMUM AMOUNT OF THIS TYPE OF WORK. 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 110.3.9 OTHER INSPECTION SERVICES.
  
 3)SHEET 004_A1.1.1. PLEASE PROVIDE WHAT TYPE OF DRYWALL
 IS GOING TO BE ON THE WALLS OF STAIR # 104 AND CLOSET
 105 THE WALLS AND CEILING OF CLOSET.
 FBC-B 1009.9.3 ENCLOSURES UNDER INTERIOR STAIRWAYS. THE
 WALLS AND SOFFITS WITHIN ENCLOSED USABLE SPACES UNDER
 ENCLOSED AND UNENCLOSED STAIRWAYS SHALL BE PROTECTED BY
 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION OR THE
 FIRE-RESISTANCE RATING OF THE STAIRWAY ENCLOSURE,
 WHICHEVER IS GREATER. ACCESS TO THE ENCLOSED SPACE
 SHALL NOT BE DIRECTLY FROM WITHIN THE STAIR ENCLOSURE.
 DOOR 105 STORAGE UNDER THE STAIR, DOES NOT SHOW A FIRE
 RATING IN THE DOOR SCHEDULE, NEITHER DOES DOOR 104 NOR
 DOOR 202. BLDG. TYPE VB/SPRINKLERED. FBC-B TABLE 716.5.
 4) SHEET A1.1.1. SHOWS A 2 STORY ATRIUM PLEASE PROVIDE
 WHERE THE 1 HOUR FIRE RATING IS TAKING PLACE FROM THE
 REMAINING PORTION OF THE BUILDING FBC-B 404.6.
 5) SHEET A1.1.1. ON THE 2ND FLOOR INDICATES A GLASS
 WALL THAT SEPARATES THE ATRIUM FROM THE 2ND FLOOR AREA
 FORMING A SMOKE PARTITION, PLEASE SHOW COMPLIANCE WITH
 404.6 EXCEPTION 1.1-1.3.
 6) SHEET A1.1.1 DOES NOT SHOW THE ELEVATOR IN A 1 HOUR
 FIRE RATED SHAFT. FBC-B 713.4.
 7) SHEET A1.1.1. THE REAR STAIRWAY # 2 THE PLANS SHOW A
 ONE HOUR STAIR ENCLOSURE, IS THE AREA UNDER THE STAIR
 PART OF THE ELECTRIC ROOM, OR IS THE AREA UNDER THIS
 STAIR NOT USED AND THE ONE HOUR FIRE WALL IS THE
 ELECTRICAL ROOM WALL WHERE ALL PENETRATIONS HAVE TO BE
 FIRE SEALED? FBC-B 714.3.1.
 8) BOTH THE DOORS 117& 213 SHOULD BE FIRE RATED DOORS
 SINCE THEY ARE IN THE 1 HOUR VERTICAL EXIT. 2014 FBC-B
 TABLE 716.5.
 9) THERE IS NO SECTION THROUGH THE REAR STAIRWAY BUT IT
 APPEARS THAT THE STAIR STRINGER WILL BE LOW THE CEILING
 LEVEL OF THE LADIES CEILING IN ROOM 114 REQUIRING THE
 ONE HOUR FIRE RATING TO ALSO CONTINUE INTO THIS ROOM.
 10) SHEET A1.1.1. THE 1ST FLOOR INDICATES THE USE OF A
 SINGLE DRINKING FOUNTAIN, THE NOTE # 12 INDICATES ANEW
 SINGLE ADA DRINKING FOUNTAIN W/ BOTTLE FILLING STATION,
 PLEASE SHOW COMPLIANCE WITH 2014 FBC-ACCESSIBILITY CODE
 211.2 MINIMUM NUMBER. NO FEWER THAN TWO DRINKING
 FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH 602.7.
 11) THE LIFE SAFETY PLANS INDICATE THE OCCUPANT LOAD OF
 110 OCCUPANTS. THE LIFE SAFETY PLAN DOES NOT INDICATE
 IF THERE ARE (2) ACCESSIBLE EXITS, LEVEL WITH THE
 EXTERIOR OF THE BUILDING. 2014 FBC-ACCESSIBILITY CODE
 207.1 GENERAL. MEANS OF EGRESS SHALL COMPLY WITH
 SECTION 1003.2.13 OF THE INTERNATIONAL BUILDING CODE
 (2000 EDITION AND 2001 SUPPLEMENT) OR SECTION 1007 OF
 THE INTERNATIONAL BUILDING CODE (2003 EDITION)
 (INCORPORATED BY REFERENCE, SEE ?REFERENCED STANDARDS?
 IN CHAPTER 1).
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-31 Cont ID  
Sent By vperez Date 2016-03-31 Time 09:26 Rev Time 0.00
Received By vperez Date 2016-03-31 Time 09:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-23 Cont ID  
Sent By vperez Date 2016-02-23 Time 06:23 Rev Time 0.00
Received By vperez Date 2016-02-23 Time 06:23 Sent To  
Notes
2016-02-23 06:24:07INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1.PLEASE LABEL FLOOR PLAN ROOM #112 RECEPTACLES WITHIN
 6FT OF SINK TO BE GFCI PROTECTED PER NEC 210.8B5
 2.CLARIFY IF SHOW WINDOW RECEPTACLES REQUIRED PER NEC
 210.62- 220.14G, NOT SHOWN ON FLOOR PLAN OR PANEL LOAD
 SCHEDULES.
 3.SHOW ON FLOOR PLAN EXISTING WP/GFCI RECEPTACLE FOR
 SERVICE AT THE A/C LOCATION WITHIN 25 FT OF UNIT PER
 NEC 210.63, CIRCUIT H-8
 4.CLARIFY REQUIRED BRANCH CIRCUIT FOR DEDICATED SIGN
 OUTLET PER NEC 600.5A
 5.PLEASE CORRECT PANEL SCHEDULE H-15, 17 THAT SHOWS A
 60 AMP OVERCURRENT FOR THE RTU#3 WITH A #12 CONDUCTOR.
 CORRECT TYPO TO REFLECT ACTUAL CONDUCTOR SIZE BASED ON
 NEC 310.15B16.
 6.PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-04-06 Cont ID  
Sent By pleduc Date 2016-04-06 Time   Rev Time 0.00
Received By pleduc Date 2016-03-31 Time 16:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-02-23 Cont ID  
Sent By pleduc Date 2016-02-23 Time   Rev Time 0.00
Received By pleduc Date 2016-02-23 Time 14:32 Sent To  
Notes
2016-02-23 15:53:20THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1. FIRE SPRINKLER PROTECTION IS NOT SHOWN IN THE SPACE
 ABOVE THE CONFERENCE ROOM. PROVIDE FIRE SPRINKLER
 PROTECTION PER NFPA 13.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-04-14 Cont ID  
Sent By jwitmer Date 2016-04-14 Time 10:29 Rev Time 0.00
Received By jwitmer Date 2016-04-14 Time 09:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-13 Cont ID  
Sent By jwitmer Date 2016-04-13 Time 08:50 Rev Time 0.00
Received By jwitmer Date 2016-03-30 Time 08:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-14 Cont ID  
Sent By vperez Date 2016-03-14 Time 16:58 Rev Time 0.00
Received By jwitmer Date 2016-02-23 Time 06:24 Sent To  
Notes
2016-02-23 06:25:21EMAIL CAROLINE ELECTRICAL 2/23

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-04-04 Cont ID  
Sent By ccole Date 2016-04-04 Time 16:21 Rev Time 0.00
Received By ccole Date 2016-04-04 Time 16:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-02-26 Cont ID  
Sent By ccole Date 2016-02-26 Time 09:30 Rev Time 0.00
Received By ccole Date 2016-02-26 Time 09:30 Sent To  
Notes
2016-02-26 09:40:141ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16020613
 2/26/16
  
 1) SHEET M1.2: THE SUPPLY AIR PLENUM FOR RTU- 2 CANNOT
 BE LOCATED IN THE FIRE-RATED ENCLOSURE OF STAIR #1- SEE
 SECTIONS 1022.5 AND 1022.6 FBC-14 BUILDING.
 2) M1.2: IT APPEARS THAT FIRE DAMPERS ARE MISSING FOR
 THE SUPPLY AND RETURN DUCTS DROPPING INTO THE FIRST
 FLOOR FROM RTU-3.
 3) M1.2: IT APPEARS THAT CORRIDOR 205 IS BEING USED AS
 A MEANS OF RETURNING AIR BACK TO RTU-2 FROM THE
 ADJOINING OFFICES AND COPY ROOM- SEE SECTION 601.2
 MECHANICAL AND CORRECT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-04-11 Cont ID  
Sent By gjohnson Date 2016-04-11 Time 11:47 Rev Time 0.00
Received By gjohnson Date 2016-04-11 Time 11:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-02-27 Cont ID  
Sent By tklarge Date 2016-02-27 Time 03:44 Rev Time 0.00
Received By tklarge Date 2016-02-27 Time 02:38 Sent To  
Notes
2016-02-27 03:43:561) SUBMIT A SANITARY AND WATER RISER FOR THE ADDITION
 OF THE DRINKING FOUNTAIN ON THE FIRST FLOOR AND ANY
 OTHER CHANGES TO THE PLUMBING SYSTEM.. 2014 FBC SEC.
 107.3.5.1.3.
 2) A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER
 THE 2014 FBC-ACCESSIBILITY SEC.211.2 OR THE
 INSTALLATION OF A HI-LO UNIT.
 3) THE COFFEE MACHINE WATEER SUPPLY SHALL BE PROTECTED
 WITH A BACKFLOW PREVENTER PER 2014 FPC SEC.608.16.10.
 4) SHT. P0.1 - PLUMBING FIXTURE SPECIFICATIONS - WATER
 COOLER NOTES REFER TO SEC.410.2 FOR AN EXCEPTION TO THE
 DRINKING FOUNTAIN REQUIREMENTS. THIS SECTION OF THE
 ACCESSIBILITY CODE REFERS TO PLATFORM LIFTS. CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2016-04-14 Cont ID  
Sent By jwitmer Date 2016-04-14 Time 10:29 Rev Time 0.00
Received By jwitmer Date 2016-04-14 Time 10:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2016-04-13 Cont ID  
Sent By jwitmer Date 2016-04-13 Time 08:45 Rev Time 0.00
Received By jwitmer Date 2016-04-13 Time 08:45 Sent To  
Notes
2016-04-13 08:50:47PLEASE NOTE SHEET 015BDB_S1.0 DOES NOT HAVE A
 ELECTRONIC SIGNATURE AT ALL. EITHER PROVIDE COMPLIANCE
 WITH FLORIDA ADMINISTRATIVE CODE 61G15-23.005
 PROCEDURES FOR SIGNING AND SEALING ELECTRONICALLY
 TRANSMITTED PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS OR SUBMIT A SIGNED AND SEALED PAPER ORIGINAL
 IN COMPLIANCE WITH 61G15-23.002(2) FL. ADMIN. CODE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  